Plan Review Notes For Permit 05100903 |
Permit Number |
05100903 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-06 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE GROUNDING ELECTRODE CONDUCTOR | | MUST COMPLY WITH 250.66, 1/0 MINIMUM FOR | | 400MCM. | | | | 2} A RECEPTACLE PER 210.52(E) IS | | REQUIRED IN THE FRONT AND REAR OUTSIDE, | | AND PER 210.63 FOR THE CONDENSERS, BUT | | ONE IN THE REAR (WITHIN 25'),WILL | | SUFFICE. | | | | 3} THE FANS IN THE LIVING ROOM MUST HAVE | | A LIGHT KIT OR A RECEPTACLE SWITCHED. | | 210.70(A)(1). | | | | 4} THE TITLE BLOCK MUST CONTAIN THE | | CORPORATE NUMBER OF THE FIRM PER | | 61G1-16.003 FAC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|