 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250.66, 1/0 MINIMUM FOR
 400MCM.
  
 2} A RECEPTACLE PER 210.52(E) IS
 REQUIRED IN THE FRONT AND REAR OUTSIDE,
 AND PER 210.63 FOR THE CONDENSERS, BUT
 ONE IN THE REAR (WITHIN 25'),WILL
 SUFFICE.
  
 3} THE FANS IN THE LIVING ROOM MUST HAVE
 A LIGHT KIT OR A RECEPTACLE SWITCHED.
 210.70(A)(1).
  
 4} THE TITLE BLOCK MUST CONTAIN THE
 CORPORATE NUMBER OF THE FIRM PER
 61G1-16.003 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  