Notes
Date Text
2005-11-14 00:00:00DENIED:
  
 1) THE CUT SHEETS AND SPEC'S NOTES UNDER
 OPERATION STATES THAT WHEN POWER FAILS
 THE DOORS WILL BE LOCKED AND SECURED.
  
 2) THESE LOCKING DEVICES ON THE DOORS
 MUST COMPLY WITH NFPA 101 LIFE SAFETY
 CODE CHAPTER 7.2.1.6 SPECIAL LOCKING
 ARRANGEMENTS.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL