Plan Review Notes For Permit 05100510 |
Permit Number |
05100510 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-17 00:00:00 | ********* UNSAT ******* | | | | 1)NOTE: PLEASE VERIFY LOADS/LAOD | | CALCUALTIONS FOR TRACK LIGHTING, SHOW | | WINDOWS PER 220.12A&B | | | | 2)NOTE: LOAD CALCULATIONS COULD NOT BE | | LOCATED. | | PLEASE VERIFY ALL CONTINUOUS @ 125%, | | 215.3,230.42 ETC. | | | | 3)NOTE: PLEASE SEE TRANSFORMER DOES | | INDICATE GROUNDINF ELECTRODE FOR | | SEPARTELY DERIVED SYSTEM TO BLDG STEEL | | AND CWP, HOWEVER PLEASE INDICATE TO MAIN | | GE SYSTEM. | | 250.30 | | PLEASE ALSO INDICATE THE "EQUIPMENT | | GROUNDING CONDUCTOR FROM PANEL "H" TO | | TRANSFORMER. | | 250.30,250.110,,,, | | ONLY THE NEUTRAL IS NOT BROUGHT TO THE | | TRANSFORMER. | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATINGS | | FOR THE NEW ELECTRICAL SERVICE | | EQUIPMENT. | | 110.9,215.5 | | | | 5)NOTE: PLEASE VERIFY MIN OCP FOR AHU'S | | CONTAINING HEAT , SHALL BE BASED ON MIN | | OCP AT 125% PER 424.3B | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY AFFECT | | ELECTRICAL PLANS. | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS | | AND ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETE SETSFOR REVIEW AND STAMPING. | | PLEASE SUBMIT ONE SET OF OLD SHEETS FOR | | REFERENCE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|