2005-11-17 00:00:00********* UNSAT *******
  
 1)NOTE: PLEASE VERIFY LOADS/LAOD
 CALCUALTIONS FOR TRACK LIGHTING, SHOW
 WINDOWS PER 220.12A&B
  
 2)NOTE: LOAD CALCULATIONS COULD NOT BE
 LOCATED.
 PLEASE VERIFY ALL CONTINUOUS @ 125%,
 215.3,230.42 ETC.
  
 3)NOTE: PLEASE SEE TRANSFORMER DOES
 INDICATE GROUNDINF ELECTRODE FOR
 SEPARTELY DERIVED SYSTEM TO BLDG STEEL
 AND CWP, HOWEVER PLEASE INDICATE TO MAIN
 GE SYSTEM.
 250.30
 PLEASE ALSO INDICATE THE "EQUIPMENT
 GROUNDING CONDUCTOR FROM PANEL "H" TO
 TRANSFORMER.
 250.30,250.110,,,,
 ONLY THE NEUTRAL IS NOT BROUGHT TO THE
 TRANSFORMER.
  
 4)NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR THE NEW ELECTRICAL SERVICE
 EQUIPMENT.
 110.9,215.5
  
 5)NOTE: PLEASE VERIFY MIN OCP FOR AHU'S
 CONTAINING HEAT , SHALL BE BASED ON MIN
 OCP AT 125% PER 424.3B
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETSFOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD SHEETS FOR
 REFERENCE.
  