Plan Review Notes
Plan Review Notes For Permit 05100339
Permit Number 05100339
Review Stop E
Sequence Number 2
Notes
Date Text
2006-03-29 00:00:00 
 THE MANUAL TRANSFER SWITCH'S THIRD POLE
 DISCONNECTING THE NEUTRAL WOULD APPEAR
 TO ALSO DISCONNECT THE GROUNDING
 ELECTRODE CONDUCTOR SYSTEM. UNLESS THE
 GENERATOR NEUTRAL IS CONNECTED TO THE
 GEC IN THE OPTIONAL MODE , IT WOULD BE
 NECESSARY TO ESTABLISH A GROUNDING
 SYSTEM AT THE GENERATOR, COMPLYING WITH
 ALL PROVISIONS OF ARTICLE 250.52 AND
 250.66.
 IT WOULD BE BETTER APPLICATION TO
 INSTALL A 2POLE DISCONNECTING THE
 UNGROUNDED CONDUCTORS AND LEAVE THE
 GROUNDED CONDUCTOR SOLIDLY CONNECTED TO
 THE GEC.
  
 PLEASE SUBMIT DOCUMENTS INDICATING A 2
 POLE SWITCH OR INDICATING COMPLIANCE
 WITH 250.52 FOR A SEPERATELY DERIVED
 SYSTEM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  