 PLEASE SUBMIT GENERATOR MANUFACTURER
 SPECIFICATIONS FOR REVIEW. NOTE THAT
 2(TWO) COPIES ARE NEEDED AS WITH ALL
 DOCUMENTS SUBMITTED FOR REVIEW, PER
 104.2.1,FBC.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A CALCULATION FOR THE
 INTENDED LOAD OF THE GENERATOR TO BE
 TRANSFERRED TO THE 30 CKT PANEL SHOWN ON
 THE PLAN. SEE GEN SPEC'S FOR MAX AND
 USEABLE OUTPUT (PROBABLY 80%).
 THE 38.2KW TOTAL HOUSE LOAD SOBMITTED IS
 TOO LARGE FOR A 20KW GENERATOR.
  
 2} PLEASE LOCATE THE SERVICE AND
 GENERATOR ON THE SITE PLAN SO THAT
 COMPLIANCE WITH ARTICLE 225 CAN BE
 DETERMINED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW