2006-04-05 00:00:00******** PLANS REDLINED *********
  
 1) NOTE: PLEASE SEE A "J" BOX IS BEING
 SHOWN IN STAIR CASE EGRESS AREA, PLEASE
 SEE A LT FIXTURE WILL BE REQUIED, NO
 EXCEPTIONS. 210.70, LS101 7.8
  
 2) NOTE: PLEASE SEE FAN/LT "J" BOX IS
 BEING SHOWN IN BEDRMS, HOWEVER EITHER A
 SWITCHED RECEPT IS TO BE ADDED OT THE
 FAN/LT WILL BE REQUIRED, NOT JUST A
 "J-BOX". 210.70,LS101 7.8
  
 3) NOTE: PLEASE SEE SWITCHES AR 2ND FLR
 FOR STAIR LIGHTING WILL BE REQUIRED TO
 BE LOCATED IN CLOSE PROXIMITY TO THE
 EGRESS OF STAIRS IN THE AREA AT THE TOP
 OF STAIRS.
  
 ** PLEASE KNOW, ALL OF THE ABOVE ITEMS
 WERE REDLINED ON PLANS AND DO NOT NEED
 TO BE CORRECTED AT THIS TIME. IF PLANS
 COME BACK FOR ANY OTHER COMMENTS, THESE
 CAN BE REVISED OR THEY WILL BE REQUIRED
 TO BE REVISED AND SUBMITTED BEFORE ROUGH
 ELECTRICAL INSPECTION SHOWING LT
 FIXTURES OF SOME SORT.
 THIS WAS ON PREVIOUS REVIEW AND THE ONLY
 ITEM WHICH WAS DELETED IN MEETING WAS
 NOT TO PORVIDE BATTERY BACK UP AND THE
 10 FT CANDLES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]