2006-02-04 00:00:00 | PLUMBING PLAN REVIEW EXAMINER |
| PAUL SCHMITZ 561-805-6692 |
| [email protected] |
| FBC PLUMBING 2001 |
| \DENIED 2ND TIME |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PREVIOUS PLAN REVIEW NOTES BY JOHN LEECH |
| DATED 11-30-05 NOT ADDRESSED. |
| DENIED; |
| 1.SHOW WATER RISER DIAGRAM, SIZE ALL |
| PIPES. |
| 2.IF BOTH APTS. ON SAME WATER SERVICE A |
| BACKFLOW PROVENTOR IS REQUIRED, IF NOT |
| 2ND FLOOR APT. NEEDS A WATER HEATER. |
| 3.SHOW DIAMETER OF WATER HEATER AND THE |
| OPENING. MUST BE ABLE TO REMOVE W/H FOR |
| REPLACEMENT. |
| 4.SANITARY RISER DIAGRAM NOT TO CODE. |
| (MARKED IN RED) |
| A.WET VENT SIZE SEE TABLE 909.3 |
| B.W/M MUST BE DOWN STREAM OF BATH- |
| ROOM GROUP SEC.909.1 |
| C. CLEANOUT ON W/M STACK TO BE |
| 48" AFF. |
| 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR |
| USES? SEE TABLE 403.1(7) |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 805-6695 |
| ADDITIONAL COMMENTS |
| 1) PERMIT APPLICATION.DISCRIPTION OF |
| WORK, AND PLANS SUBMITTED APTS #1,2 |
| SHOULD INCLUDE BUILDING #1 ON THE |
| APPLICATION. |
| 2)ENERGY CALCULATIONS SUBMITTED ARE FOR |
| SIX UNITS,THREE BUILDINGS. PLEASE |
| CLARIFY.OR REMOVE FROM SUBMITTED PLANS. |
| 3)VOIDED SHT.M-2, WAS REMOVED FROM RED |
| LINED PACKAGE. THIS IS REFERENCED IN |
| NOTE (4) PREVIOUS COMMENTS. |
| END OF COMMENTS, QUESTIONS 561-805-6692 |