Plan Review Notes
Plan Review Notes For Permit 05100328
Permit Number 05100328
Review Stop P
Sequence Number 2
Notes
Date Text
2006-02-04 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2001
 \DENIED 2ND TIME
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PREVIOUS PLAN REVIEW NOTES BY JOHN LEECH
 DATED 11-30-05 NOT ADDRESSED.
 DENIED;
 1.SHOW WATER RISER DIAGRAM, SIZE ALL
 PIPES.
 2.IF BOTH APTS. ON SAME WATER SERVICE A
 BACKFLOW PROVENTOR IS REQUIRED, IF NOT
 2ND FLOOR APT. NEEDS A WATER HEATER.
 3.SHOW DIAMETER OF WATER HEATER AND THE
 OPENING. MUST BE ABLE TO REMOVE W/H FOR
 REPLACEMENT.
 4.SANITARY RISER DIAGRAM NOT TO CODE.
 (MARKED IN RED)
 A.WET VENT SIZE SEE TABLE 909.3
 B.W/M MUST BE DOWN STREAM OF BATH-
 ROOM GROUP SEC.909.1
 C. CLEANOUT ON W/M STACK TO BE
 48" AFF.
 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR
 USES? SEE TABLE 403.1(7)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
 ADDITIONAL COMMENTS
 1) PERMIT APPLICATION.DISCRIPTION OF
 WORK, AND PLANS SUBMITTED APTS #1,2
 SHOULD INCLUDE BUILDING #1 ON THE
 APPLICATION.
 2)ENERGY CALCULATIONS SUBMITTED ARE FOR
 SIX UNITS,THREE BUILDINGS. PLEASE
 CLARIFY.OR REMOVE FROM SUBMITTED PLANS.
 3)VOIDED SHT.M-2, WAS REMOVED FROM RED
 LINED PACKAGE. THIS IS REFERENCED IN
 NOTE (4) PREVIOUS COMMENTS.
 END OF COMMENTS, QUESTIONS 561-805-6692