2006-01-30 00:00:00************** UNSAT 2ND REVIEW *******
  
  
 ** PLEASE SEE MANY NOTESFROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO CHANGES
 IN PLANS.
  
  
 1) NOTE: NOTE # 1 OK.
  
 2) NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE LOCATIONS
 REDLINED ON PLANS.
  
 ** PLEASE SEE 210.52D, WHICH
 REQUIRES THE GFI RECEPTS WITHIN 3' OF
 SINK'S EGDE. PLEASE SEE MISSING ON
 REDLINED PLANS.PLEASE ALSO SEE THESE MAY
 NOT PLACED AS TOCROSS OVER SINK TO GET
 TO RECEPT.
 PLEASE EITHER ADD ONE OR MOVE EXISTING
 SHOWN.
 PLEASE ALSO INDICATE ALL AS GFI. 210.8A1
  
 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S
 WERE ADDED, HOWEVER, PLEASE SEE SD
 MISSING AT THE TOP OF STATIRWAY AND ON
 LOWER LEVEL.
  
 **SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
  
 5) NOTE: NOTE #5 NO, PLEASE SEE MANY
 MISSING.
  
 ** PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED PLANS FOR MANY
 MISSING.
  
 6 ) NOTE: NOTE #6 NO.
  
 ** PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 7)NOTE: NOTE #7 OK, HOWEVER PLEASE SEE
 DISC'S NOW SHOWN FOR CU'S DO NOT MEET
 110.26
  
 8 )NOTE: NOTE #8 NO.
  
 ** PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MANY MISSING, PLEASE ALSO SEE
 WHAT APPEARS TO BE ISLAND SHOWS A
 J-BOX??
  
 9)NOTE: NOTE #9 NO,PLEASE SEE THE
 FOLLOWING COMMENTS FOR LIGHTING
 REQUIRED.
  
 ** PLEASE SEE J-BOXES ARE SHOWN IN
 MANY ROOMS, HOWEVER, PLEASE INDICATE IF
 THESE ARE GOING TO BE "FAN" J-BOXES.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE ROOMS
 AND AREAS ARE SHOWN WITH J-BOXES ,
 HOWEVER LT FIXTURES OF SOME SORT WILL BE
 REQUIRED. PLEASE SEE LS 101 7.8.1.3
 WHICH REQUIRES A MIN OF 10FT CANDLES
 DURING NORMAL POWER AND PLEASE SEE
 7.9.1.3 WHICH REQUIRES AN EM FIXTURE TO
 PROVIDE A MIN OF 1FT CANDLE OF LT TO THE
 PUBLIC RIGHT OF WAY.
  
 ** PLEASE SEE MISSING EGRESS LIGHTING AT
 FIRST FLR APT PLANS, APPEARS TO BE SHOWN
 ON 2ND FLR?
 PLEASE ALSO SEE EGRESS CONTROL REQUIRED
 ON MULTI-LEVELS/LANDING.
 210.70
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE # 13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK/ NO, PLEASE SEE
 THESE WERE ADDED , HOWEVER PLEASE SEE
 EQUIPMENT GROUNDING CONDUCTORS ARE NOW
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE THESE ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.250.6
  
 ** PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS WHERE REQUIRED.
 250.110,250.122, 250.24
  
 16)NOTE: NOTE #16 NO, PLEASE SEE A SIZE
 WAS ADDED FOR GUTTER, HOWEVER PLEASE SEE
 THIS AS BEING SHOWN 8"X 8" AND BY 4"??
  
 **PLEASE INDICATE THE MIN SIZE OF
 GUTTER PER 366
  
 17)NOTE: NOTE #17 OK, HOWEVER PLEASE SEE
 AN ADDITIONAL GRND ROD WILL BE REQUIRED.
  
  
 **PLEASE SEE 250.66 FOR MIN SIZE
 OF THE GROUNDING ELECTRODE CONDUCTOR.
  
 18)NOTE:NOTE #18 OK.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE WATER HEATER ON FIRST
 FLR IS BEING SHOWN WITH A RECEPT FOR THE
 CONNECTION. PLEASE SEE422.31 WHICH
 REQUIRES A DISCONNECT.
  
 2)NOTE: PLEASE SEE DRYER DOES NOT
 INDICATE ANY RECEPT?
 215.5
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT CODE
 COMMENTS 3 OR MORE TIMES.
 PLEASE SEE THIS IS ONLY ATTACHED THIS
 TIME AS A NOTICE.
  
  
 *** PLEASE SEE MOST OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS OF PLANS
 FOR NOTES ABOVE.
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 PLANS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  