2006-01-30 00:00:00 | ************** UNSAT 2ND REVIEW ******* |
| |
| |
| ** PLEASE SEE MANY NOTESFROM PREVIOUS |
| REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE NEW NOTES DUE TO CHANGES |
| IN PLANS. |
| |
| |
| 1) NOTE: NOTE # 1 OK. |
| |
| 2) NOTE: NOTE #2 OK. |
| |
| 3)NOTE: NOTE #3 NO, PLEASE SEE LOCATIONS |
| REDLINED ON PLANS. |
| |
| ** PLEASE SEE 210.52D, WHICH |
| REQUIRES THE GFI RECEPTS WITHIN 3' OF |
| SINK'S EGDE. PLEASE SEE MISSING ON |
| REDLINED PLANS.PLEASE ALSO SEE THESE MAY |
| NOT PLACED AS TOCROSS OVER SINK TO GET |
| TO RECEPT. |
| PLEASE EITHER ADD ONE OR MOVE EXISTING |
| SHOWN. |
| PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 |
| |
| 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S |
| WERE ADDED, HOWEVER, PLEASE SEE SD |
| MISSING AT THE TOP OF STATIRWAY AND ON |
| LOWER LEVEL. |
| |
| **SMOKE DETECTORS ARE REQUIRED INSIDE |
| AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER: NFPA-72 11.5.1.1 |
| |
| 5) NOTE: NOTE #5 NO, PLEASE SEE MANY |
| MISSING. |
| |
| ** PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| PLEASE SEE REDLINED PLANS FOR MANY |
| MISSING. |
| |
| 6 ) NOTE: NOTE #6 NO. |
| |
| ** PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 7)NOTE: NOTE #7 OK, HOWEVER PLEASE SEE |
| DISC'S NOW SHOWN FOR CU'S DO NOT MEET |
| 110.26 |
| |
| 8 )NOTE: NOTE #8 NO. |
| |
| ** PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| PLEASE SEE MANY MISSING, PLEASE ALSO SEE |
| WHAT APPEARS TO BE ISLAND SHOWS A |
| J-BOX?? |
| |
| 9)NOTE: NOTE #9 NO,PLEASE SEE THE |
| FOLLOWING COMMENTS FOR LIGHTING |
| REQUIRED. |
| |
| ** PLEASE SEE J-BOXES ARE SHOWN IN |
| MANY ROOMS, HOWEVER, PLEASE INDICATE IF |
| THESE ARE GOING TO BE "FAN" J-BOXES. |
| |
| 10)NOTE: NOTE #10 NO, PLEASE SEE ROOMS |
| AND AREAS ARE SHOWN WITH J-BOXES , |
| HOWEVER LT FIXTURES OF SOME SORT WILL BE |
| REQUIRED. PLEASE SEE LS 101 7.8.1.3 |
| WHICH REQUIRES A MIN OF 10FT CANDLES |
| DURING NORMAL POWER AND PLEASE SEE |
| 7.9.1.3 WHICH REQUIRES AN EM FIXTURE TO |
| PROVIDE A MIN OF 1FT CANDLE OF LT TO THE |
| PUBLIC RIGHT OF WAY. |
| |
| ** PLEASE SEE MISSING EGRESS LIGHTING AT |
| FIRST FLR APT PLANS, APPEARS TO BE SHOWN |
| ON 2ND FLR? |
| PLEASE ALSO SEE EGRESS CONTROL REQUIRED |
| ON MULTI-LEVELS/LANDING. |
| 210.70 |
| |
| 11)NOTE: NOTE #11 OK. |
| |
| 12)NOTE: NOTE #12 OK. |
| |
| 13)NOTE: NOTE # 13 OK. |
| |
| 14)NOTE: NOTE #14 OK. |
| |
| 15)NOTE: NOTE #15 OK/ NO, PLEASE SEE |
| THESE WERE ADDED , HOWEVER PLEASE SEE |
| EQUIPMENT GROUNDING CONDUCTORS ARE NOW |
| SHOWN BEFORE THE FIRST MEANS OF |
| DISCONNECT. PLEASE SEE THESE ARE ONLY |
| INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT.250.6 |
| |
| ** PLEASE INCLUDE ALL EQUIPMENT |
| GROUNDING CONDUCTORS WHERE REQUIRED. |
| 250.110,250.122, 250.24 |
| |
| 16)NOTE: NOTE #16 NO, PLEASE SEE A SIZE |
| WAS ADDED FOR GUTTER, HOWEVER PLEASE SEE |
| THIS AS BEING SHOWN 8"X 8" AND BY 4"?? |
| |
| **PLEASE INDICATE THE MIN SIZE OF |
| GUTTER PER 366 |
| |
| 17)NOTE: NOTE #17 OK, HOWEVER PLEASE SEE |
| AN ADDITIONAL GRND ROD WILL BE REQUIRED. |
| |
| |
| **PLEASE SEE 250.66 FOR MIN SIZE |
| OF THE GROUNDING ELECTRODE CONDUCTOR. |
| |
| 18)NOTE:NOTE #18 OK. |
| |
| NEW NOTES: |
| |
| 1)NOTE: PLEASE SEE WATER HEATER ON FIRST |
| FLR IS BEING SHOWN WITH A RECEPT FOR THE |
| CONNECTION. PLEASE SEE422.31 WHICH |
| REQUIRES A DISCONNECT. |
| |
| 2)NOTE: PLEASE SEE DRYER DOES NOT |
| INDICATE ANY RECEPT? |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONALS AND PLANS WITH REPEAT CODE |
| COMMENTS 3 OR MORE TIMES. |
| PLEASE SEE THIS IS ONLY ATTACHED THIS |
| TIME AS A NOTICE. |
| |
| |
| *** PLEASE SEE MOST OF THE ABOVE ITEMS |
| ARE REDLINED ON ONE OF THE SETS OF PLANS |
| FOR NOTES ABOVE. |
| |
| **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| PLANS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |