2005-11-30 00:00:00DENIED;
 1.SHOW WATER RISER DIAGRAM, SIZE ALL
 PIPES.
 2.IF BOTH APTS. ON SAME WATER SERVICE A
 BACKFLOW PROVENTOR IS REQUIRED, IF NOT
 2ND FLOOR APT. NEEDS A WATER HEATER.
 3.SHOW DIAMETER OF WATER HEATER AND THE
 OPENING. MUST BE ABLE TO REMOVE W/H FOR
 REPLACEMENT.
 4.SANITARY RISER DIAGRAM NOT TO CODE.
 (MARKED IN RED)
 A.WET VENT SIZE SEE TABLE 909.3
 B.W/M MUST BE DOWN STREAM OF BATH-
 ROOM GROUP SEC.909.1
 C. CLEANOUT ON W/M STACK TO BE
 48" AFF.
 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR
 USES? SEE TABLE 403.1(7)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695