Plan Review Notes For Permit 05100328 |
Permit Number |
05100328 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-30 00:00:00 | DENIED; | | 1.SHOW WATER RISER DIAGRAM, SIZE ALL | | PIPES. | | 2.IF BOTH APTS. ON SAME WATER SERVICE A | | BACKFLOW PROVENTOR IS REQUIRED, IF NOT | | 2ND FLOOR APT. NEEDS A WATER HEATER. | | 3.SHOW DIAMETER OF WATER HEATER AND THE | | OPENING. MUST BE ABLE TO REMOVE W/H FOR | | REPLACEMENT. | | 4.SANITARY RISER DIAGRAM NOT TO CODE. | | (MARKED IN RED) | | A.WET VENT SIZE SEE TABLE 909.3 | | B.W/M MUST BE DOWN STREAM OF BATH- | | ROOM GROUP SEC.909.1 | | C. CLEANOUT ON W/M STACK TO BE | | 48" AFF. | | 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR | | USES? SEE TABLE 403.1(7) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|