Date |
Text |
2005-10-18 00:00:00 | ************ UNSAT ************* |
| |
| 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 2) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| MUST BE 20A AND #12. |
| |
| 3)NOTE: PLEASE SEE 210.52D, WHICH |
| REQUIRE STHE GFI RECEPT PLEASE SEE |
| MISSING ON REDLINED PLANS.PLEASE ALSO |
| SEE THESE MAY NOT PLACED AS TOCROSS |
| OVER SINK TO GET TO RECEPT. |
| PLEASE EITHER ADD ONE OR MOVE EXISTING |
| SHOWN. |
| PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 |
| |
| 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER: NFPA-72 11.5.1.1 |
| |
| 5) NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| PLEASE SEE REDLINED PLANS FOR MANY |
| MISSING. |
| |
| 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 7)NOTE: PLEASE SEE PLANS ARE MISSING THE |
| LOCATION OF CU'S ALONG WITH MISSING |
| DISC;S PER 440.11 AND GFI'S PER |
| 210.8,210.63 |
| |
| 8 )NOTE: PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| PLEASE SEE MANY MISSING, PLEASE ALSO SEE |
| WHAT APPEARS TO BE ISLAND SHOWS A |
| J-BOX?? |
| |
| 9)NOTE: PLEASE SEE J-BOXES ARE SHOWN IN |
| MANY ROOMS, HOWEVER, PLEASE INDICATE IF |
| THESE ARE GOING TO BE "FAN" J-BOXES. |
| |
| 10)NOTE: PLEASE SEE MISSING EGRESS |
| LIGHTING AT FIRST FLR APT PLANS, APPEARS |
| TO BE SHOWN ON 2ND FLR? |
| PLEASE ALSO SEE EGRESS CONTROL REQUIRED |
| ON MULTI-LEVELS/LANDING. |
| 210.70 |
| |
| 11)NOTE: PLEASE LIST ALL THE REQUIRED |
| ARC FAULT CIRCUITS ON PANEL SCHEDULE. |
| PLEASE SEE 2002 NEC 210.12, WHICH |
| REQUIRES ARC FAULT FOR ALL OUTLETS IN |
| BEDRMS. |
| |
| 12)NOTE: PLEASE SIZE SERVICE ENT |
| CONDUCTORS FOR SERVICE AND LOAD |
| PROVIDED.240.4 SEC'S ARE NOT LARGE |
| ENOUGH. |
| |
| 13)NOTE: PLEASE SEE PANELS ARE BEING |
| SHOWN AS 150A WITH 158 LOAD, AND BEING |
| FED FROM A 125A DISC????? |
| PLEASE CORRELATE ALL TO MIN REQUIRED BY |
| CODE. |
| PLEASE ALSO SEE #4'S SHOWN FROM GUTTER |
| TO MAINS. THESE ARE ONLY REATED FOR |
| 85A'S?? |
| 240.4,310.16, 215.5, 90.7 ETC. |
| |
| 14)NOTE: PLEASE INDICATE WHAT APPEARS TO |
| BE ADDITIONAL DISCONNECT SON RISER |
| DIAGRAM?? THESE ITEMS ARE NOT LABELED. |
| |
| 15)NOTE: PLEASE INCLUDE ALL EQUIPMENT |
| GROUNDING CONDUCTORS WHERE REQUIRED. |
| 250.110,250.122, 250.24 |
| |
| 16)NOTE: PLEASE INDICATE THE MIN SIZE OF |
| GUTTER PER 366 |
| |
| 17)NOTE: PLEASE SEE 250.66 FOR MIN SIZE |
| OF THE GROUNDING ELECTRODE CONDUCTOR. |
| |
| 18)NOTE: PLEASE SHOW ALL SERVICE |
| EQUIPMENT ON PLANS. |
| |
| 215.5 |
| |
| **PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| ** PLEASE BE SURE TO REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| PLANS FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |