2005-10-18 00:00:00************ UNSAT *************
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12.
  
 3)NOTE: PLEASE SEE 210.52D, WHICH
 REQUIRE STHE GFI RECEPT PLEASE SEE
 MISSING ON REDLINED PLANS.PLEASE ALSO
 SEE THESE MAY NOT PLACED AS TOCROSS
 OVER SINK TO GET TO RECEPT.
 PLEASE EITHER ADD ONE OR MOVE EXISTING
 SHOWN.
 PLEASE ALSO INDICATE ALL AS GFI. 210.8A1
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
  
 5) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED PLANS FOR MANY
 MISSING.
  
 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 7)NOTE: PLEASE SEE PLANS ARE MISSING THE
 LOCATION OF CU'S ALONG WITH MISSING
 DISC;S PER 440.11 AND GFI'S PER
 210.8,210.63
  
 8 )NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MANY MISSING, PLEASE ALSO SEE
 WHAT APPEARS TO BE ISLAND SHOWS A
 J-BOX??
  
 9)NOTE: PLEASE SEE J-BOXES ARE SHOWN IN
 MANY ROOMS, HOWEVER, PLEASE INDICATE IF
 THESE ARE GOING TO BE "FAN" J-BOXES.
  
 10)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING AT FIRST FLR APT PLANS, APPEARS
 TO BE SHOWN ON 2ND FLR?
 PLEASE ALSO SEE EGRESS CONTROL REQUIRED
 ON MULTI-LEVELS/LANDING.
 210.70
  
 11)NOTE: PLEASE LIST ALL THE REQUIRED
 ARC FAULT CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE 2002 NEC 210.12, WHICH
 REQUIRES ARC FAULT FOR ALL OUTLETS IN
 BEDRMS.
  
 12)NOTE: PLEASE SIZE SERVICE ENT
 CONDUCTORS FOR SERVICE AND LOAD
 PROVIDED.240.4 SEC'S ARE NOT LARGE
 ENOUGH.
  
 13)NOTE: PLEASE SEE PANELS ARE BEING
 SHOWN AS 150A WITH 158 LOAD, AND BEING
 FED FROM A 125A DISC?????
 PLEASE CORRELATE ALL TO MIN REQUIRED BY
 CODE.
 PLEASE ALSO SEE #4'S SHOWN FROM GUTTER
 TO MAINS. THESE ARE ONLY REATED FOR
 85A'S??
 240.4,310.16, 215.5, 90.7 ETC.
  
 14)NOTE: PLEASE INDICATE WHAT APPEARS TO
 BE ADDITIONAL DISCONNECT SON RISER
 DIAGRAM?? THESE ITEMS ARE NOT LABELED.
  
 15)NOTE: PLEASE INCLUDE ALL EQUIPMENT
 GROUNDING CONDUCTORS WHERE REQUIRED.
 250.110,250.122, 250.24
  
 16)NOTE: PLEASE INDICATE THE MIN SIZE OF
 GUTTER PER 366
  
 17)NOTE: PLEASE SEE 250.66 FOR MIN SIZE
 OF THE GROUNDING ELECTRODE CONDUCTOR.
  
 18)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS.
  
 215.5
  
 **PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 PLANS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  