2006-02-21 00:00:00DENIED;
 1.RISER DIAGRAM DOES NOT FOLLOW FLOOR
 PLAN. MASTER BATH AND BATH 2 ARE FLIPPED
 ON RISER DIAGRAM.
 2.THE VENT FOR THE 1/2 BATH ON FIRST
 FLOOR CANNOT BE THE RISER FOR THE
 BATHROOM ON SECOND FLOOR.
 3.SHOW THE LAUNDRY TUB ABOVE THE WASHING
 MACHINE A SANITARY CROSS IS NOT PERMITED
 AND CLEANOUT SHOULD BE 48" ABOVE FINISH
 FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695