2006-02-14 00:00:00*** DENIED ***
 1) PLEASE PROVIDE DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIRE PLACE IN
 LIBRARY.
  
 2) PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR GAS FIRE PLACE IN
 LIBRARY, PER 2004 FBC/R M1702.
  
 3) PLEASSE SHOW ON MECHANICAL PLANS HOW
 YOU ARE PROVIDING COMBUSTION AIR IN
 LAUNDRY ROOM FOR GAS CLOTHES DRYER, AND
 TANKLESS WATER HEATER, PER 2004 FBC/R
 M1703.
  
 4) NEED COMBUSTION AIR CALCULATIONS FOR
 EACH GAS TANKLESS WATER HEATER, PER 2004
 FBC/RCH.17 .
  
 5) MASTER BATHROOM NEEDS A EXHAUST FAN
 BY THE TUB AREA (ON MECH. PLANS), PER
 2004 FBC/R M1506.
  
 6) EXHAUST FAN IN LAUNDRY ROOM NEED TO
 BE REMOVED FROM MECH. PLANS, PER 2004
 FBC/R M1701.2 .
  
 7) RETURN AIR TRANSFER DUCTS IN THE
 LIBRARY, AND STUDIO ARE TO SMALL, SEE
 NOTE #8.
  
 8)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 8) RETURN AIR GRILL 30X18 TO AHU #1 IS
 TO SMALL FOR A 5 TON UNIT.
  
 9) PLEASE SEE YELLOW HIGH LIGHTS ON DUCT
 SIZES AS THEY ARE TO SMALL. REFER TO
 YOUR MANUAL J AND LOOK UNDER MIN. & MAX.
 VELOCITY, PLEASE CORRECT DUCT SIZES.
  
 10) ENERGY CALCULATIONS AND MANUAL J ARE
 DIFFICULT TO READ ALL PARTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .PLEASE SUBMIT CLEARER COPYS.
  