2006-02-14 00:00:00 | *** DENIED *** |
| 1) PLEASE PROVIDE DETAILED MANUFACTURE'S |
| SPECIFICATION'S AND INSTALLATION |
| INSTRUCTIONS FOR GAS FIRE PLACE IN |
| LIBRARY. |
| |
| 2) PLEASE PROVIDE COMBUSTION AIR |
| CALCULATIONS FOR GAS FIRE PLACE IN |
| LIBRARY, PER 2004 FBC/R M1702. |
| |
| 3) PLEASSE SHOW ON MECHANICAL PLANS HOW |
| YOU ARE PROVIDING COMBUSTION AIR IN |
| LAUNDRY ROOM FOR GAS CLOTHES DRYER, AND |
| TANKLESS WATER HEATER, PER 2004 FBC/R |
| M1703. |
| |
| 4) NEED COMBUSTION AIR CALCULATIONS FOR |
| EACH GAS TANKLESS WATER HEATER, PER 2004 |
| FBC/RCH.17 . |
| |
| 5) MASTER BATHROOM NEEDS A EXHAUST FAN |
| BY THE TUB AREA (ON MECH. PLANS), PER |
| 2004 FBC/R M1506. |
| |
| 6) EXHAUST FAN IN LAUNDRY ROOM NEED TO |
| BE REMOVED FROM MECH. PLANS, PER 2004 |
| FBC/R M1701.2 . |
| |
| 7) RETURN AIR TRANSFER DUCTS IN THE |
| LIBRARY, AND STUDIO ARE TO SMALL, SEE |
| NOTE #8. |
| |
| 8)BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 8) RETURN AIR GRILL 30X18 TO AHU #1 IS |
| TO SMALL FOR A 5 TON UNIT. |
| |
| 9) PLEASE SEE YELLOW HIGH LIGHTS ON DUCT |
| SIZES AS THEY ARE TO SMALL. REFER TO |
| YOUR MANUAL J AND LOOK UNDER MIN. & MAX. |
| VELOCITY, PLEASE CORRECT DUCT SIZES. |
| |
| 10) ENERGY CALCULATIONS AND MANUAL J ARE |
| DIFFICULT TO READ ALL PARTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 |
| .PLEASE SUBMIT CLEARER COPYS. |
| |