Plan Review Notes
Plan Review Notes For Permit 05100303
Permit Number 05100303
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-14 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} SMOKE DETECTORS ARE REQUIRED TO BE
 INSTALLED IN THE GAME ROOM ( SINCE IT IS
 COMPARTMENTED FROM THE REST OF THE UPPER
 FLOOR, AND THEREFORE OTHER DETECTORS)
 AND ON THE FIRST FLOOR. FBC RES. 313.1
  
 3} THE PANEL(A)INDICATES IT IS 400 AMP
 RATED, THE RISER INDICATES 200 AMPS.
 PLEASE CORRELATE.
  
 4} PLEASE CHECK AND CORRELATE THE A/C
 AND AHU LOADS WITH THE MECHANICAL PLAN.
 NOTE THE COMPRESSER LOADS ARE SHOWN
 LARGER THAN THE AHU LOADS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved