2005-11-15 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE PROVIDE MANUFACTURERS |
| SPECIFICATIONS FOR THE GENERATOR AND |
| TRANSFER SWITCH. |
| |
| 2} THE #5 BARE COPPER GEC IS NOT A AWG |
| SIZE. GEC MUST BE A MINIMUM OF #1/0 PER |
| 250.66. |
| |
| 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| COMPLY WITH 250.50. 250.52(A)(3) |
| INDICATES HOW THE GEC MUST BE CONNECTED |
| TO BUILDING (FOOTER) STEEL, PLEASE |
| INDICATE SAME ON THE PLAN. |
| |
| 4} INDICATE DISCONNECTING MEANS PER |
| 230.71. THE PANELS SHOWN ON THE RISER DO |
| NOT SPECIFY MAIN BREAKERS. |
| |
| 5} PLEASE SHOW THE LOCATION OF ALL |
| SERVICE AND GENERATOR EQUIPMENT ON THE |
| FLOOR PLAN. THE RISER SHOWS A GUTTER, |
| THIS AND THE TRANSFER SWITCH ARE NOT |
| LOCATED ON THE PLAN, AND PANELS ARE |
| SHOWN INSIDE? |
| |
| 6} PLEASE SIZE THE GUTTER SO THAT |
| COMPLIANCE WITH ARTICLE 366 CAN BE |
| DETERMINED. |
| |
| 7} PLEASE NOTE THE GENERATOR MUST BE |
| GROUNDED PER MANUFACTURERS SPEC'S.THIS |
| IS NOT A SEPARATELY DERIVED SYSTEM AND |
| MUST USE THE SERVICE NEUTRAL AND GROUND, |
| THE GENERATOR NEUTRAL CANNOT BE BONDED |
| TO THE FRAME AND THEN TO A ROD. THIS IS |
| JUST A NOTE AS IT HAS BEEN BROUGHT TO MY |
| ATTENTION BY CONTRACTORS THAT THESE |
| MODELS HAVE A JUMPER FROM THE NEUTRAL TO |
| THE FRAME, WHICH OF COURSE MUST BE |
| REMOVED WHEN USING A TWO POLE SWITCH. |
| |
| 8} REGARDING CIRCUIT A8, PLEASE SEE |
| 210.11(C)(3) 20 AMP.THAT CIRCUIT IS |
| CONFINED TO A SINGLE BATHROOM OR TO ALL |
| BATH GFI'S ONLY. THE GFI'S IN THE |
| LAUNDRY MUST NOT BE ON THAT CIRCUIT. |
| ALSO NOTE 1 GFI IN THE MASTER BATH IS ON |
| B4. |
| |
| 9} CIRCUIT #2, PANEL A, DINING ROOM |
| RECEPTACLES MUST COMPLY WITH 210.5(B)(1) |
| & (2), LIVING ROOM CANT BE ON THAT |
| CIRCUIT. |
| |
| 10} ALL OUTLETS, INCLUDING LIGHTING, |
| RECEPTACLES, FANS AND SMOKE DETECTORS |
| INSTALLED IN BEDROOMS MUST BE ARC FAULT |
| PROTECTED PER 210.12. SEE DEFINITION OF |
| "OUTLET" IN ARTICLE 100 FOR |
| CLARIFICATION OF 210.12. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |
| |
| |
| |
| |