 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} THE #5 BARE COPPER GEC IS NOT A AWG
 SIZE. GEC MUST BE A MINIMUM OF #1/0 PER
 250.66.
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250.50. 250.52(A)(3)
 INDICATES HOW THE GEC MUST BE CONNECTED
 TO BUILDING (FOOTER) STEEL, PLEASE
 INDICATE SAME ON THE PLAN.
  
 4} INDICATE DISCONNECTING MEANS PER
 230.71. THE PANELS SHOWN ON THE RISER DO
 NOT SPECIFY MAIN BREAKERS.
  
 5} PLEASE SHOW THE LOCATION OF ALL
 SERVICE AND GENERATOR EQUIPMENT ON THE
 FLOOR PLAN. THE RISER SHOWS A GUTTER,
 THIS AND THE TRANSFER SWITCH ARE NOT
 LOCATED ON THE PLAN, AND PANELS ARE
 SHOWN INSIDE?
  
 6} PLEASE SIZE THE GUTTER SO THAT
 COMPLIANCE WITH ARTICLE 366 CAN BE
 DETERMINED.
  
 7} PLEASE NOTE THE GENERATOR MUST BE
 GROUNDED PER MANUFACTURERS SPEC'S.THIS
 IS NOT A SEPARATELY DERIVED SYSTEM AND
 MUST USE THE SERVICE NEUTRAL AND GROUND,
 THE GENERATOR NEUTRAL CANNOT BE BONDED
 TO THE FRAME AND THEN TO A ROD. THIS IS
 JUST A NOTE AS IT HAS BEEN BROUGHT TO MY
 ATTENTION BY CONTRACTORS THAT THESE
 MODELS HAVE A JUMPER FROM THE NEUTRAL TO
 THE FRAME, WHICH OF COURSE MUST BE
 REMOVED WHEN USING A TWO POLE SWITCH.
  
 8} REGARDING CIRCUIT A8, PLEASE SEE
 210.11(C)(3) 20 AMP.THAT CIRCUIT IS
 CONFINED TO A SINGLE BATHROOM OR TO ALL
 BATH GFI'S ONLY. THE GFI'S IN THE
 LAUNDRY MUST NOT BE ON THAT CIRCUIT.
 ALSO NOTE 1 GFI IN THE MASTER BATH IS ON
 B4.
  
 9} CIRCUIT #2, PANEL A, DINING ROOM
 RECEPTACLES MUST COMPLY WITH 210.5(B)(1)
 & (2), LIVING ROOM CANT BE ON THAT
 CIRCUIT.
  
 10} ALL OUTLETS, INCLUDING LIGHTING,
 RECEPTACLES, FANS AND SMOKE DETECTORS
 INSTALLED IN BEDROOMS MUST BE ARC FAULT
 PROTECTED PER 210.12. SEE DEFINITION OF
 "OUTLET" IN ARTICLE 100 FOR
 CLARIFICATION OF 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  