Date |
Text |
2005-12-06 00:00:00 | DENIED; |
| 1) COMPLY WITH FBC-2004 SEC 424.2 |
| PRIVATE SWIMMING POOLS. |
| 2) FBC-2004 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-5. (ADD TO NOTES) |
| 3) FBC-2004 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 4)FBC-2004 424.2.9 WATER SUPPLY, LOCAL |
| 0RD. #2853-95,BACKFLOW REQUIRED ON WATER |
| SERVICE. (ADD TO NOTES) |
| 5.FBC-2004 424.2.13.2 JOINTS AND |
| CONNECTIONS, PLUMBING SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 6.FBC 2004 424. 2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| AND PERMIT REQUIRED. (ADD TO NOTES) |
| 7) FBC-2004424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 8) FBC-2004424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. PLEASE SHOW LOCATION ON |
| PAGE 1 |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 805-6695 |