2005-12-06 00:00:00DENIED;
 1) COMPLY WITH FBC-2004 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2004 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4)FBC-2004 424.2.9 WATER SUPPLY, LOCAL
 0RD. #2853-95,BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 5.FBC-2004 424.2.13.2 JOINTS AND
 CONNECTIONS, PLUMBING SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6.FBC 2004 424. 2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
 7) FBC-2004424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 8) FBC-2004424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. PLEASE SHOW LOCATION ON
 PAGE 1