Plan Review Notes For Permit 05100240 |
Permit Number |
05100240 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-13 00:00:00 | *** DENIED *** | | | | 1) DRAIN LINES NOT SHOWING ON PLANS. PER | | FBC/R M1411.3 . | | 2) PLANS ARE CALLING FOR A 34,000 BTU | | A/C SYSTEM AND MANUAL 'J' IS CALLING FOR | | 21,641 BTU'S OF COOLING THE TWO MUST | | COINCIED. | | 3) PLEASE SHOW ON PLANS WHERE DOORS AND | | OPENINGS IN WALLS ARE. | | 4) PLANS NOT SHOWING LOCATION OF | | CONDENSER UNIT. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|