2006-03-01 00:00:00 | ********** UNSAT 3RD REVIEW ********** |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS TWO REVIEWS. |
| |
| |
| |
| 1)NOTE: NOTE #1 OK |
| |
| |
| 2)NOTE: NOTE #2 OK |
| |
| 3)NOTE:NOTE #3 OK/ NO, PLEASE SEE ONLY |
| ONE SHEET WAS REVISED AND 2ND FLR PLANS |
| ARE THE SAME PLANS FROM PREVIOUS REVIEW. |
| |
| **PLEASE VERIFY LOCATION OF |
| PANELS, BOTH APT UNITS DOWN STAIRS SHOWS |
| PANELS INSIDE UNITS, HOWEVER UPSTAIRS |
| UNITS DO NOT INDICATE PANELS? |
| PLEASE SEE 240.24 FOR LOCATION OF |
| ACCESSIBILITY TO OCCUPANTS FOR OCP>. |
| 215.5 |
| PLEASE ALSO SHOW LOCATION OF SERVICE ON |
| PLANS AS AN ELECTRICAL ROOM IS SHOWN, |
| HOWEVER SERVICE IS NOT SHOWN.? |
| 215.5 |
| |
| 4)NOTE:NOTE #4 NO, PLEASE SEE RECEPTS DO |
| NOT MEET 210.52C1. |
| PLEASE SEE DISPOSAL IS STILL BEING SHOWN |
| AS GFI? |
| |
| ** PLEASE SEE PLANS ONLY INDICATE |
| THE DIPOSAL AND DISHWASHER. BOTH OF |
| THESE ARE SHOWN AS GFI? PLEASE SEE NO |
| APPLIANCE GFI RECEPTS ARE SHOWN, YET |
| THESE ARE REQUIRED. 210.52C1, 210.8A6 |
| |
| 5)NOTE: NOTE #5 NO, PANEL SCHEDULE NOW |
| INDICATES A ARC FAULT CIRCUIT, YET THIS |
| IS SHOWING ALL DEVICES IN BOTH BEDRMS, |
| LTS, SD'SRECEPTS ONLY ONE ONE CIRCUIT? |
| PLEASE SEE PREVIOUS PANEL SCHEDULE AND |
| THIS PANEL SCHEDULE INDICATES MORE THAN |
| 5 GEN LT CIRCUITS?? |
| |
| **PLEASE SEE PLANS INDICATE ARC |
| FAULT BEING ADDED TO BEDRMS, HOWEVER |
| PANEL SCHEDULE DOES NOT SHOW THIS? |
| PLEASE KNOW, RECEPTS DO NOT COME AS |
| BEING ARC FAULT TYPE AS GFI'S ARE. THE |
| ONLY ARC FAULT PROTECTION AT THIS TIME |
| IS THE BRANCH BRKR. |
| |
| 6)NOTE: NOTE #6 OK. |
| |
| 7)NOTE: NOTE #7 OK |
| |
| 8)NOTE: NOTE #8, OK, THIS SHALL BE FEILD |
| VERIFIED. |
| |
| |
| 9)NOTE:NOTE #9 NO,PLEASE SEE NOT ALL |
| NEW PLANS WERE SUBMITTED. PLEASE ALSO |
| SEE THE SET OF OLD/VOIDED SHEETS |
| SUBMITTED FOR REFERENCE ARE FROM ANOTHER |
| PERMIT AND NOT THIS PROJECT. |
| ** PLEASE KNOW, IF ALL COMMENTS ARE NOT |
| ADDRESSED A 4X FEE WILL BE ACCESSED. |
| |
| ****PLEASE SEE 553.80(2)(B) IN |
| FLORIDA STATUES. |
| THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| |
| NEW NOTE: |
| |
| 1)NOTE: PLEASE ADJUST NOTE ON PLANS WITH |
| RESPECT TO SCOPE OF WORK AND WHAT |
| DEVICES ARE BEING REPLACED AND WHAT |
| AREAS ARE BEING REMODELED/RE-WIRED. |
| PLEASE SEE KITCHEN AREA SHALL MEET ALL |
| CURRENTS CODES AS THIS ARE IS BEING |
| REPLACED WITH NEW CABINETS. |
| PLEASE SEE CENTRAL AIR IS BEING ADDED , |
| IF CEILINGS ARE BEING OPENED, THEN A 20A |
| CIRCUIT WILL BE REQUIRED FOR BATHRM |
| (210.11C3 AND RECEPT SPACING ON TWO |
| INNER WALLS WILL REQUIRE SPACING PER |
| 210.52. |
| |
| 2)NOTE: PLEASE SEE PLANS ARE BEING SENT |
| TO BLDG AS ENERGY CALCULATIONS SUBMITTED |
| BACK WITH PLANS ARE NOT COMPLETE, NOT |
| FILLED OUT COMPLETELY, SIGNED, DATED |
| ETC. |
| IF THERE ARE CALCS WHICH WERE DONE |
| CORRECTLY AND STAMPED ON PREVIOUS |
| REVIEW, PLEASE BRING THOSE BACK IN TO |
| THE BLDG REVIEWER ASAP. |
| |
| |
| **PLEASE SEE ANY COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. ONE COPY OF OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |