Plan Review Notes
Plan Review Notes For Permit 05100222
Permit Number 05100222
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-01 00:00:00********** UNSAT 3RD REVIEW **********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS TWO REVIEWS.
  
  
  
 1)NOTE: NOTE #1 OK
  
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE:NOTE #3 OK/ NO, PLEASE SEE ONLY
 ONE SHEET WAS REVISED AND 2ND FLR PLANS
 ARE THE SAME PLANS FROM PREVIOUS REVIEW.
  
 **PLEASE VERIFY LOCATION OF
 PANELS, BOTH APT UNITS DOWN STAIRS SHOWS
 PANELS INSIDE UNITS, HOWEVER UPSTAIRS
 UNITS DO NOT INDICATE PANELS?
 PLEASE SEE 240.24 FOR LOCATION OF
 ACCESSIBILITY TO OCCUPANTS FOR OCP>.
 215.5
 PLEASE ALSO SHOW LOCATION OF SERVICE ON
 PLANS AS AN ELECTRICAL ROOM IS SHOWN,
 HOWEVER SERVICE IS NOT SHOWN.?
 215.5
  
 4)NOTE:NOTE #4 NO, PLEASE SEE RECEPTS DO
 NOT MEET 210.52C1.
 PLEASE SEE DISPOSAL IS STILL BEING SHOWN
 AS GFI?
  
 ** PLEASE SEE PLANS ONLY INDICATE
 THE DIPOSAL AND DISHWASHER. BOTH OF
 THESE ARE SHOWN AS GFI? PLEASE SEE NO
 APPLIANCE GFI RECEPTS ARE SHOWN, YET
 THESE ARE REQUIRED. 210.52C1, 210.8A6
  
 5)NOTE: NOTE #5 NO, PANEL SCHEDULE NOW
 INDICATES A ARC FAULT CIRCUIT, YET THIS
 IS SHOWING ALL DEVICES IN BOTH BEDRMS,
 LTS, SD'SRECEPTS ONLY ONE ONE CIRCUIT?
 PLEASE SEE PREVIOUS PANEL SCHEDULE AND
 THIS PANEL SCHEDULE INDICATES MORE THAN
 5 GEN LT CIRCUITS??
  
 **PLEASE SEE PLANS INDICATE ARC
 FAULT BEING ADDED TO BEDRMS, HOWEVER
 PANEL SCHEDULE DOES NOT SHOW THIS?
 PLEASE KNOW, RECEPTS DO NOT COME AS
 BEING ARC FAULT TYPE AS GFI'S ARE. THE
 ONLY ARC FAULT PROTECTION AT THIS TIME
 IS THE BRANCH BRKR.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8, OK, THIS SHALL BE FEILD
 VERIFIED.
  
  
 9)NOTE:NOTE #9 NO,PLEASE SEE NOT ALL
 NEW PLANS WERE SUBMITTED. PLEASE ALSO
 SEE THE SET OF OLD/VOIDED SHEETS
 SUBMITTED FOR REFERENCE ARE FROM ANOTHER
 PERMIT AND NOT THIS PROJECT.
 ** PLEASE KNOW, IF ALL COMMENTS ARE NOT
 ADDRESSED A 4X FEE WILL BE ACCESSED.
  
 ****PLEASE SEE 553.80(2)(B) IN
 FLORIDA STATUES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 NEW NOTE:
  
 1)NOTE: PLEASE ADJUST NOTE ON PLANS WITH
 RESPECT TO SCOPE OF WORK AND WHAT
 DEVICES ARE BEING REPLACED AND WHAT
 AREAS ARE BEING REMODELED/RE-WIRED.
 PLEASE SEE KITCHEN AREA SHALL MEET ALL
 CURRENTS CODES AS THIS ARE IS BEING
 REPLACED WITH NEW CABINETS.
 PLEASE SEE CENTRAL AIR IS BEING ADDED ,
 IF CEILINGS ARE BEING OPENED, THEN A 20A
 CIRCUIT WILL BE REQUIRED FOR BATHRM
 (210.11C3 AND RECEPT SPACING ON TWO
 INNER WALLS WILL REQUIRE SPACING PER
 210.52.
  
 2)NOTE: PLEASE SEE PLANS ARE BEING SENT
 TO BLDG AS ENERGY CALCULATIONS SUBMITTED
 BACK WITH PLANS ARE NOT COMPLETE, NOT
 FILLED OUT COMPLETELY, SIGNED, DATED
 ETC.
 IF THERE ARE CALCS WHICH WERE DONE
 CORRECTLY AND STAMPED ON PREVIOUS
 REVIEW, PLEASE BRING THOSE BACK IN TO
 THE BLDG REVIEWER ASAP.
  
  
 **PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]