2006-01-30 00:00:00 | ******** UNSAT 2ND REVIEW ********* |
| |
| 1)NOTE: PLEASE SEE 310.16, 240.4,240.6 |
| FOR MIN SEC'S TO BE SHOWN. PLEASE SEE |
| 310.16, 400 MCM IS RATED FOR 335A'S, |
| NEXT SIZE OCP PER 240.6, 350A'S. PLEASE |
| SEE LOADS EXCEED THIS. |
| (500MCM MIN). |
| |
| 2)NOTE: PLEASE SEE LOAD CALCULATIONS FOR |
| SERVICE. THI SHOWS ALL 4 TYPICAL PANELS |
| AT 88A'S, HOWEVER TOTAL FOR ALL FORU |
| UNITS IS SHOWN AS 88A'S ALSO?? |
| 310.16,215.5 ETC |
| |
| 3)NOTE: PLEASE VERIFY LOCATION OF |
| PANELS, BOTH APT UNITS DOWN STAIRS SHOWS |
| PANELS INSIDE UNITS, HOWEVER UPSTAIRS |
| UNITS DO NOT INDICATE PANELS? |
| PLEASE SEE 240.24 FOR LOCATION OF |
| ACCESSIBILITY TO OCCUPANTS FOR OCP>. |
| 215.5 |
| PLEASE ALSO SHOW LOCATION OF SERVICE ON |
| PLANS AS AN ELECTRICAL ROOM IS SHOWN, |
| HOWEVER SERVICE IS NOT SHOWN.? |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE PLANS ONLY INDICATE |
| THE DIPOSAL AND DISHWASHER. BOTH OF |
| THESE ARE SHOWN AS GFI? PLEASE SEE NO |
| APPLIANCE GFI RECEPTS ARE SHOWN, YET |
| THESE ARE REQUIRED. 210.52C1, 210.8A6 |
| |
| 5)NOTE: PLEASE SEE PLANS INDICATE ARC |
| FAULT BEING ADDED TO BEDRMS, HOWEVER |
| PANEL SCHEDULE DOES NOT SHOW THIS? |
| PLEASE KNOW, RECEPTS DO NOT COME AS |
| BEING ARC FAULT TYPE AS GFI'S ARE. THE |
| ONLY ARC FAULT PROTECTION AT THSITIME IS |
| THE BRANCH BRKR. |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPTS FOR |
| CU'S BEING ADDED. 210.63 |
| PLEASE SEE ONLY TWO CU'S ARE SHOWN? |
| |
| 7)NOTE: PLEASE SEE PLANS AND MECHANICAL |
| PLANS SHOWS AHU'S WITH 5KW HEAT STRIPS, |
| HOWEVER PLEASE SEE PLANS, PANEL |
| SCHEDULE, LOAD CALCUALTIONS ETC DO NOT |
| SHOW ANY HEAT LOADS. PLEASE ADJUST ALL . |
| PLEASE ALSO SEE SIZE OF SERVICE MAY BE |
| AFFECTED. |
| |
| 8)NOTE: PLEASE VERIFY THE LOCATION OF |
| WATER HEATER AS DISCONNECTING MEANS AND |
| ACCESSIBILITY MAY BE AN ISSUE ION THE |
| LOCATION SHOWN. |
| |
| 9)NOTE: PLEASE SEE 553.80(2)(B) IN |
| FLORIDA STATUES. |
| THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| |
| **PLEASE SEE ANY COMMENTS FROM OTHER |
| REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| TWO COMPLETE SETS FOR REVIEW AND |
| STAMPING. ONE COPY OF OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |