Notes |
Date |
Text |
2005-11-13 00:00:00 | PLAN DENIED | | 1) PLEASE SHOW TERMINATION OF BATHROOM | | EXHAUST DUCTON MECHANICAL PLANS. | | 2) PLEASE REFER TO SECTION 601.4 2004 | | FBC(M)BALANCED RETURN AIR. | | 3) PLEASE SHOW TERMINATION OF CONDENSATE | | LINE ON MECHANICAL PLANS. | | 4) PLEASE REFER TO SECTION 307.2.3 | | AUXILIARY DRAIN PANS.2004 FBC(M) | | 5) EQUIPMENT ON PLANS AND ANERGY | | CALCULATIONS DO NOT MATCH.(SEER) | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|