Plan Review Notes
Plan Review Notes For Permit 05100222
Permit Number 05100222
Review Stop M
Sequence Number 1
Notes
Date Text
2005-11-13 00:00:00PLAN DENIED
 1) PLEASE SHOW TERMINATION OF BATHROOM
 EXHAUST DUCTON MECHANICAL PLANS.
 2) PLEASE REFER TO SECTION 601.4 2004
 FBC(M)BALANCED RETURN AIR.
 3) PLEASE SHOW TERMINATION OF CONDENSATE
 LINE ON MECHANICAL PLANS.
 4) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.2004 FBC(M)
 5) EQUIPMENT ON PLANS AND ANERGY
 CALCULATIONS DO NOT MATCH.(SEER)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732