1 |
|
Notes |
Date |
Text |
2005-11-17 00:00:00 | **** UNSAT ****** | | | | 1)NOTE: PLEASE SUBMIT MIN PLANS FOR 2002 | | NEC CODE COMPLIANCE. | | | | PLEASE SEE: | | 210.52 FOR RECEPTS, | | 210.52C1, 210.8A6 FOR KITCHEN RECEPTS | | 210.52D,210.11C3, 210.8A FOR BATH RMS. | | 310.16 MIN CONDUCTORS FOR SERVICE, PANEL | | CHANGE. | | 110.9 AIC RATINGS | | 440.11 DISCONNECTS | | 210.63 GFI(S) | | 215.5 PANEL SCHEDULE MIN CIRCUITS. | | 21012 ARC FAULT. | | 215.5 RISER DIAGRAM | | 250.50 | | ETC | | | | PLEASE ALSO SEE THAT THERE IS NOT ENOUGH | | INFORMATION FOR REVIEW OF CODE COMPIANCE | | OF PANEL CHANGE OUT. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|