Plan Review Notes
Plan Review Notes For Permit 05100222
Permit Number 05100222
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00**** UNSAT ******
  
 1)NOTE: PLEASE SUBMIT MIN PLANS FOR 2002
 NEC CODE COMPLIANCE.
  
 PLEASE SEE:
 210.52 FOR RECEPTS,
 210.52C1, 210.8A6 FOR KITCHEN RECEPTS
 210.52D,210.11C3, 210.8A FOR BATH RMS.
 310.16 MIN CONDUCTORS FOR SERVICE, PANEL
 CHANGE.
 110.9 AIC RATINGS
 440.11 DISCONNECTS
 210.63 GFI(S)
 215.5 PANEL SCHEDULE MIN CIRCUITS.
 21012 ARC FAULT.
 215.5 RISER DIAGRAM
 250.50
 ETC
  
 PLEASE ALSO SEE THAT THERE IS NOT ENOUGH
 INFORMATION FOR REVIEW OF CODE COMPIANCE
 OF PANEL CHANGE OUT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  