Plan Review Notes
Plan Review Notes For Permit 05100095
Permit Number 05100095
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-10-11 00:00:00DENIED:
  
 1) PLEASE PROVIDE CUT SHEETS AND SPEC'S
 FOR THE EQUIPMENT YOU ARE INSTALLING.
  
 2) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 3) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 4) ALL FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM SYSTEM.
  
 5) SURVIVABILITY FROM ATTACK BY FIRE
 CODE REQUIREMENTS SHALL APPLY TO BOTH
 AUDIBLE AND VISIBLE NOTIFICATION
 APPLIANCE CIRCUITS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754