2005-10-11 00:00:00 | DENIED: | | | | 1) PLEASE PROVIDE CUT SHEETS AND SPEC'S | | FOR THE EQUIPMENT YOU ARE INSTALLING. | | | | 2) THE FIRE ALARM SYSTEM SHALL BE CLASS | | "A" OR FULLY ADDRESSABLE. | | | | 3) NEW FIRE ALARM SYSTEMS SHALL BE UL | | LISTED FOR CENTRAL STATION SERVICE. | | | | 4) ALL FIRE ALARM SYSTEMS THAT SUPERVISE | | FIRE SPRINKLER SYSTEMS SHALL BE UL | | CERTIFICATED AND HAVE DOCUMENTS | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | FINAL APPROVAL OF THE FIRE ALARM SYSTEM. | | | | 5) SURVIVABILITY FROM ATTACK BY FIRE | | CODE REQUIREMENTS SHALL APPLY TO BOTH | | AUDIBLE AND VISIBLE NOTIFICATION | | APPLIANCE CIRCUITS. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|