Plan Review Notes
Plan Review Notes For Permit 05100090
Permit Number 05100090
Review Stop E
Sequence Number 1
Notes
Date Text
2005-10-06 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS ARE MISSING
 REQUIRED TITLE BLOCK AND REQUIRED
 INFORMATION ON TITLE BLOCK AS SET FORTH
 UNDER FAC 61G1-16.004.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SPECIFYNEW OCCUPANCY
 AND USE. PLANS CALL FOR NEW ACTIVITY
 ROOMS YET UNCLEAR WHAT USAGE WILL BE.
  
 3)NOTE: PLEASE SEE PLANS MENTION NEW
 LIGHTING, HOWEVER NO INFORMATION FOR
 FIXTURES, LAYOUT ETC IS SHOWN?
  
 4)NOTE: PLEASE SEE CIRCUITING ON PLANS
 IS TO CORRELATE AND BE IDENTIFIED TO
 PANEL IN WHICH CIRCUIT IS TO BE RUN TO.
 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 PLEASE BE SURE ALL EXISTING AS SHOWN IS
 CIRCUITED TO THE LOCAL BRANCH CIRTCUIT
 IN AREA.
  
 5)NOTE: PLEASE SEE PLANS APPEAR TO BE
 SIGNED WITH INITIALS? IF INDEED THIS IS
 THE LEGAL SIGNATURE, PLEASE PROVIDE A
 SIGNED, DATED AND SEALED, NOTORIZED
 LETTER FOR VERIFICATION OF THIS AS LEGAL
 SIGNATURE. PLEASE BE SURE LETTER IS
 PRPOERLY NOTORIZED AS REQUIRED UNDER FS
 117.05
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR FUTURE REFERENCE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  