Date |
Text |
2005-11-28 00:00:00 | DENIED |
| |
| 1) SUBMIT A DRAINAGE PLAN SHOWING |
| COMPLIANCE WITH 2004 FBC R401.3. |
| |
| 2) THE ORIGINAL WET SIGNATURE OF THE |
| TRUSS ENGINEER IS REQUIRED ON THE TRUSS |
| LAYOUT AND TRUSS DRAWINGS. SEE F.A.C. |
| 61G1-16.003 |
| |
| 3) THE TRUSS LAYOUT IS REQUIRED TO BE |
| REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD FOR THE STRUCTURE. |
| |
| 4) THE PRODUCT APPROVALS REQUIRED BY |
| RULE 9B-72 ARE REQUIRED TO BE REVIEWED |
| AND APPROVED BY THE DESIGNER OF RECORD |
| FOR THE STRUCTURE BY SECTION 106.3.3 OF |
| THE CITY AMENDMENTS TO THE 2004 FBC. |
| |
| 5) SUBMIT AN INSTALLATION SCHEDULE FOR |
| THE STORM PANELS. SPECIFY THE ANCHORS |
| THAT WILL BE USED, THE ANCHOR SPACING, |
| THE MOUNT TYPE (SECTION # FROM PRODUCT |
| APPROVAL) AND EDGE DISTANCE. THE PLANS |
| SPECIFY TAPCONS WITH AN EDGE DISTANCE OF |
| 3". THE PRODUCT APPROVAL SPECIFIES |
| 3-1/2" EDGE DISTANCE. THE INFORMATION ON |
| THE PLANS MUST CORRESPOND WITH THE |
| INSTALLATION SELECTED FROM THE PRODUCT |
| APPROVAL. |
| |
| 6) THE NOAS SUBMITTED FOR THE SH |
| WINDOWS, WINDOW MULLIONS AND GAF |
| SHINGLES HAVE BEEN UPDATED FOR THE 2004 |
| FBC ON THE STATE WEBSITE. SUBMIT THE |
| NOAS THAT ARE LISTED ON THE WEBSITE FOR |
| THE PRODUCT. SEE WWW.FLORIDABUILDING.ORG |
| |
| 7) THE INSTALLATION INSTRUCTIONS THAT |
| WERE SUBMITTED FOR THE THERMA-TRU DOORS |
| ARE MIAMI-DADE NOAS AND THE EVALUATION |
| ENTITY SUBMITTED FOR STATE APPROVAL WAS |
| NAMI. SUBMIT THE CORRESPONDING REPORTS. |
| SEE FL 5262 AND THE CORRESPONDING PDF |
| FILES. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |