Plan Review Notes For Permit 05100079 |
Permit Number |
05100079 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-10-05 00:00:00 | DENIED; | | 1.DRINKING FOUNTAIN REQUIRED. FBC-2004 | | PLUMBING TABLE 403.1 | | 2.WHERE ARE BATHROOM FACILITIES FOR | | WOMAN? | | 3.SANITARY RISER DIAGRAM KITCHEN SINK | | NOT VENTED. | | 4.WATER RISER DIAGRAM; WATER HAMMER | | ARRESTORS TO BE INSTALLED PER. | | MANUFACTORS SPEC'S. ( AS CLOSE TO SOURCE | | OF WATER HAMMER) MOVE TO BOTTOM OF | | DROPS. | | 5.WATER HEATER DETAIL; SHOW HOW IT WILL | | BE PIPED TO OUTSIDE. | | 6.WATER HEATER DETAIL; SHOW THERMAL | | EXPANSION CONTROL. SEC. 607.3. | | 7.ONE OF THE KITCHEN SINKS SHALL MEET | | HANDICAP REQUIRMENTS. (SHOW DETAIL ) | | MUST COMPLY WITH FBC-2004 CHAPTER 11 | | SEC. 11-4.23.1 THRU 11-4.23.7. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|