Date Text
2005-10-07 00:00:00REDLINED
  
 110.26 FOR MIN CLEARENCE IN NEW
 ELECTRICAL CLOSET. IF USING SCALE ON
 PLANS, CLEARENCE DOES NOT SEEM TO MET.
  
 REDLINED
  
 GROUNDING OF TRANSFORMER NOT INDICATED.
 PLEASE SEE 250.30