Plan Review Notes For Permit 05100075 |
Permit Number |
05100075 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2006-02-08 00:00:00 | PROVISO: | | PLAN SHEET M1.1, RETURN AIR FROM RTU-2 | | IS INDICATED IN THE RESTROOM AREAS. | | PLEASE NOTE, AIR FROM BATHROOMS SHALL | | NOT BE RECIRCULATED, EXHAUST ONLY IN | | ACCORDANCE WITH 2004 FMC TABLE 403.3. | | PLEASE REMOVE RETURN AIR FROM THE | | BATHROOM AREAS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|