2006-02-08 00:00:00PROVISO:
 PLAN SHEET M1.1, RETURN AIR FROM RTU-2
 IS INDICATED IN THE RESTROOM AREAS.
 PLEASE NOTE, AIR FROM BATHROOMS SHALL
 NOT BE RECIRCULATED, EXHAUST ONLY IN
 ACCORDANCE WITH 2004 FMC TABLE 403.3.
 PLEASE REMOVE RETURN AIR FROM THE
 BATHROOM AREAS.
  