Date |
Text |
2006-02-08 00:00:00 | ******** UNSAT 3RD REVIEW ********** |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| TWO REVIEWS ARE NOT ADDRESSED. |
| PLEASE SEE NEW NOTE FOR CHANGE IN PLANS. |
| PLEASE SEE NOTES BELOW WHICH ARE |
| DIRECTLY TAKEN FROM PREVIOUS REVIEW. |
| |
| *** UNSAT 2ND REVIEW *** |
| |
| PLEASE SEES SOME NOTES FROM PREVIOUS |
| REVEW STILL NEED TO BE ADDRESSED. |
| PLEASE SEE BELOW NOTES ARE TAKEN |
| DIRECTLY FROM THOSE NOTES. |
| |
| 1)NOTE: OK |
| |
| 2)NOTE: OK |
| |
| 3)NOTE:NO. PLEASE SEE PANEL SCHEDULES |
| OR LOAD CALCUALTIONS DO NOT INDICATE ANY |
| CONTINUOUS OR LARGEST MOTOR LOADS?? |
| |
| ** NOTE #3 NO, PLEASE SEE THAT ALL |
| CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| ARE SHOWN AT 125%. |
| 215.3,230.42 ETC. |
| |
| 4)NOTE: OK |
| |
| 5)NOTE: OK |
| |
| 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC |
| RATINGS FOR ALL NEW SERVICE EQUIPMENT |
| BEING INSTALLED. MAINS/BRKRS AND PANELS |
| ARE ALL TO BE RATED FOR THE AVAILABLE |
| FAULT CURRENT.PER 110.9/215.5 |
| ** IT IS NOTED THAT THE AIC RATINGS WERE |
| SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN |
| DISCONNECT RATING ALSO. |
| |
| NEW NOTE: |
| 7)NOTE:NO, PLEASE SEE THE FEE AS |
| REQUIRED UNDER FLORIDA STATUE HAS NOW |
| BEEN ACCESSED AND IS REQUIRED TO BE PAID |
| BEFORE PLANS CAN BE RESUBMITTED. |
| A FEE OF $4,293.60 IS NOW OWED. |
| PLEASE SEE ONE SET OF PLANS ARE NOW |
| BEING RETAINED FOR FILE. |
| IT IS STRONGLY RECOMMEDED A MEETING BE |
| HELD BEFORE RESUBMITTING PLANS TO |
| ALLEAVIATE ANY FURTHER DELAYS OR FINES. |
| PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| PROFESSIONAL AND REPEAT COMMENTS. THIS |
| IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| ******* NEW NOTE ******** |
| |
| 1)NOTE: PLEASE SEE RISER NOW INDICATES A |
| NEW UPS SYSTEM BEING INSTALLED HOWEVE NO |
| INFORMATION HAS BEEN SUBMITTED FOR THIS |
| SYSTEM. PLEASE ALSO BE SURE VALUE FOR |
| THIS SCOPE OF WORK IS ADJUSTED EVEN IF |
| OWNER SUPPLIED. FBC 108.3 ADMINISTRATIVE |
| SECTION OF THE LOCAL ADMINISTRATIVE |
| CODE. |
| UNABLE TO REVIEW AS NOT ENOUGH |
| INFORMATION IS SUBMITTED. |
| PLEASE ALSO SEE ROOM IS NOW BEING LABLED |
| AS A "NETWORK ROOM"?? PLEASE CLARIFY USE |
| AS IF THIS ROOM IS AN IT ROOM, |
| REQUIREMENTS OF 645 AND NFPA-75 MAY |
| APPLY. |
| THIS MAY ALSO AFFECT MECHANICAL, AND |
| BLDG SHEETS. |
| |
| 2)NOTE: PLEASE SEE FBC CHAPTER 13, |
| 13-415.1ABC.1.1,.2 |
| PLEASE KNOW, THIS WAS NOT ON PREVIOUS |
| REVIEW, HOWEVER IS REQUIRED UNDER THE |
| 2004 FBC WHICH PLANS ARE NOW SHOWN TO BE |
| DESIGNED UNDER. |
| |
| |
| ** ONE COPY OF ALL OLD VOIDED SHEETS |
| WERE NOT SUBMITTED AS REQUESTED. |
| |
| ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONLY ONE COPY OF THE OLD VOIDED SHEETS |
| NEED TO BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THEREARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |