Plan Review Notes
Plan Review Notes For Permit 05100075
Permit Number 05100075
Review Stop E
Sequence Number 3
Notes
Date Text
2006-02-08 00:00:00******** UNSAT 3RD REVIEW **********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 TWO REVIEWS ARE NOT ADDRESSED.
 PLEASE SEE NEW NOTE FOR CHANGE IN PLANS.
 PLEASE SEE NOTES BELOW WHICH ARE
 DIRECTLY TAKEN FROM PREVIOUS REVIEW.
  
 *** UNSAT 2ND REVIEW ***
  
 PLEASE SEES SOME NOTES FROM PREVIOUS
 REVEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE BELOW NOTES ARE TAKEN
 DIRECTLY FROM THOSE NOTES.
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE:NO. PLEASE SEE PANEL SCHEDULES
 OR LOAD CALCUALTIONS DO NOT INDICATE ANY
 CONTINUOUS OR LARGEST MOTOR LOADS??
  
 ** NOTE #3 NO, PLEASE SEE THAT ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: OK
  
 5)NOTE: OK
  
 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.PER 110.9/215.5
 ** IT IS NOTED THAT THE AIC RATINGS WERE
 SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN
 DISCONNECT RATING ALSO.
  
 NEW NOTE:
 7)NOTE:NO, PLEASE SEE THE FEE AS
 REQUIRED UNDER FLORIDA STATUE HAS NOW
 BEEN ACCESSED AND IS REQUIRED TO BE PAID
 BEFORE PLANS CAN BE RESUBMITTED.
 A FEE OF $4,293.60 IS NOW OWED.
 PLEASE SEE ONE SET OF PLANS ARE NOW
 BEING RETAINED FOR FILE.
 IT IS STRONGLY RECOMMEDED A MEETING BE
 HELD BEFORE RESUBMITTING PLANS TO
 ALLEAVIATE ANY FURTHER DELAYS OR FINES.
 PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS. THIS
 IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ******* NEW NOTE ********
  
 1)NOTE: PLEASE SEE RISER NOW INDICATES A
 NEW UPS SYSTEM BEING INSTALLED HOWEVE NO
 INFORMATION HAS BEEN SUBMITTED FOR THIS
 SYSTEM. PLEASE ALSO BE SURE VALUE FOR
 THIS SCOPE OF WORK IS ADJUSTED EVEN IF
 OWNER SUPPLIED. FBC 108.3 ADMINISTRATIVE
 SECTION OF THE LOCAL ADMINISTRATIVE
 CODE.
 UNABLE TO REVIEW AS NOT ENOUGH
 INFORMATION IS SUBMITTED.
 PLEASE ALSO SEE ROOM IS NOW BEING LABLED
 AS A "NETWORK ROOM"?? PLEASE CLARIFY USE
 AS IF THIS ROOM IS AN IT ROOM,
 REQUIREMENTS OF 645 AND NFPA-75 MAY
 APPLY.
 THIS MAY ALSO AFFECT MECHANICAL, AND
 BLDG SHEETS.
  
 2)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1ABC.1.1,.2
 PLEASE KNOW, THIS WAS NOT ON PREVIOUS
 REVIEW, HOWEVER IS REQUIRED UNDER THE
 2004 FBC WHICH PLANS ARE NOW SHOWN TO BE
 DESIGNED UNDER.
  
  
 ** ONE COPY OF ALL OLD VOIDED SHEETS
 WERE NOT SUBMITTED AS REQUESTED.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD VOIDED SHEETS
 NEED TO BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
 561-805-6717
 [email protected]