2006-02-14 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2.)SEE PREVIOUS LIST, ITEMS 1 AND 2. |
| THEY WERE TO BE CORRECTED ON THE |
| UNNUMBERED SHEET WITH BUILDING DATA. |
| THIS SHEET WAS NOT REVISED AND |
| RESUBMITTED.THIS SHEET PROVIDES |
| INFORMATION REQUIRED TO SHOW CODE |
| COMPLIANCE.SEE THE VOIDED SET. |
| |
| PLEASE REVISE OCCUPANT LOAD TO 97. |
| |
| 3.)SEE PREVIOUS LIST, ITEM #3.REVISE |
| APPLICATION TO REFLECT CORRECT SCOPE OF |
| WORK, INCLUDING EXTERIOR STAIR AND |
| WHEELCHAIR LIFT. |
| |
| THIRD REQUEST; PLEASE COMPLY BEFORE |
| PERMIT ISSUANCE. |
| |
| 4.)ADDRESSED. |
| |
| 5.)ADDRESSED. |
| |
| 5.)ADDRESSED. |
| |
| 7.)SEE PREVIOUS LIST, ITEM #9.THE |
| STAIR HANDRAIL EXTENSIONS ARE TO COMPLY |
| WITH FBC11-4.8.5(6), FIGURE 19.AS |
| DESIGNED THEY POSE A HAZARD. THEY ARE TO |
| BE ROUNDED OR RETURN TO THE FLOOR.NOT |
| ADDRESSED. |
| |
| THIS WAS ADDRESSED BUT A PREVIOUS |
| REQUEST FOR THE DIMENSION OF THE RAIL |
| LENGTH AT THE TOP OF THE STAIR WAS NOT |
| ADDRESSED.PLEASE PROVIDE THAT |
| DIMENSION. |
| |
| 8.)ADDRESSED. |
| |
| 9.)SEE PREVIOUS LIST, ITEM 12. |
| PROVIDE EITHER AN APPROVED ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE FOR THE 1 |
| HOUR WALL, FBC7. |
| |
| THE UL ASSEMBLY PROVIDED IS NOT VALID. |
| NOTE THAT YOU HAVE SPECIFIED D419; THIS |
| SHOULD BE A U ASSEMBLY. |
| |
| 10.)PROVIDE A FIRE SPRINKLER PLAN |
| FBC*106.3.5.1.1(5). |
| |
| THIS IS REQUIRED BY FLORIDA STATUE PRIOR |
| TO PERMIT ISSUANCE WHEN SPRINKLERS ARE |
| REQUIRED FOR CODE COMPLIANCE.PROVIDE A |
| SPRINKLER LAYOUT PLAN AS REQUESTED.IT |
| IS UNDERSTOOD THAT SPRINKLER DRAWINGS ON |
| A SEPARATE PERMIT WILL BE PROVIDED, BUT |
| A SPRINKLER PLAN IS REQUIRED AT THIS |
| TIME FOR THE RENOVATION PERMIT. |
| |
| 10.)SEE ATTACHED FS553.80(2)(B).A 4X |
| PLAN REVIEW FEE WILL BE CHARGED IF THE |
| ABOVE ITEMS ARE NOT ADDRESSED IN THE |
| THIRD REVIEW. |
| |
| A 4X FEE WAS CHARGED BY ELECTRIC.THERE |
| ARE ALSO BUILDING COMMENTS WHICH WERE |
| NOT ADDRESSED 3X.PLEASE NOTE THAT THE |
| FEE WILL BE CHARGED AGAIN IF THE |
| COMMENTS ARE NOT ADDRESSED A 4TH TIME. |