Plan Review Notes For Permit 05100075 |
Permit Number |
05100075 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-01-04 00:00:00 | DENIED; | | 1.SECOND REQUEST; SHOW COMPLIANCE TO | | FBC-2004 PLUMBING TABLE 403.1. SHOW | | OCCUPANCY CLASSIFICATION, NUMBER OF | | EMPLOYEES | | 2.WATER RISER; WATER HAMMER ARRESTORS | | ARE REQUIRED BY MANUFACTOR'S | | INSTALLATION INSTRUCTIONS TO BE AS CLOSE | | TO THE SORCE OF HAMMER. PLEASE INSTALL | | WHA'S AT THE BOTTOM OF DROPS. | | 3.BREAK ROOM SINK DOES NOT COMPLY WITH | | FBC-2004 CHAPTER 11 SEC.11-4.24.3 KNEE | | CLEARANCE; 19" REQUIRED. | | 4.SANITARY RISER DIAGRAM; PLEASE INSTALL | | URINALS USING SANITARY TEE'S (ONE SET OF | | PLANS MARKED IN RED) | | | | DO NOT SHOW TRAPS ON URINALS TRAPS | | BUILT INTO FIXTURE. | | 5.SANITARY RISER DIAGRAM; 3" PIPE | | REQUIRED TO WET VENT BOTH FLOOR DRAINS | | IN BATHROOMS FBC-2004 PLUMBING TABLE | | 909.3 WET VENT SIZE. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|