Date |
Text |
2005-12-23 00:00:00 | *** UNSAT 2ND REVIEW *** |
| |
| PLEASE SEES SOME NOTES FROM PREVIOUS |
| REVEW STILL NEED TO BE ADDRESSED. |
| PLEASE SEE BELOW NOTES ARE TAKEN |
| DIRECTLY FROM THOSE NOTES. |
| |
| 1)NOTE: NOTE #1 NO, PLEASE KNOW THAT ALL |
| DESIGNS/PLANS SUBMITTED FOR PERMIT AFTER |
| OCT 1ST, 2005 SHALL FALLUNDER THE 2004 |
| FBC. |
| PLEASE ADJUST ALL SHEETS CONTAINING |
| REFERENCE TO THE 2001 FBC. PLEASE ALSO |
| SEE ALL MEP'S ,PLEASE SEE NOTES ON THESE |
| SHEETS WITH REFERENCE TO THE 2001. |
| PLEASE SEE SOME SHEETS HAD THESE CHANGES |
| MADE. PLEASE SEE ELECTRICAL SHEET NOW |
| HAS MISSING NOTES, PLEASE BE SURE TO |
| SPECIFY THE NEC CURRENTLY IN |
| EFFECT.(2002), NFPA-101 2003, NFPA-72, |
| 2002 |
| |
| 2)NOTE: NOTE #2 NO/YES,PLEASE SEE |
| MISSSING CONDUCTORS FROM GUTTER TO |
| METER. PLEASE SEE OTHER TO PANEL FROM |
| TENANT DISCONNECT WERE ADDED. |
| 215.5, 310.16,240.4 ETC. |
| |
| 3)NOTE:NOTE #3 NO, PLEASE SEE THAT ALL |
| CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| ARE SHOWN AT 125%. |
| 215.3,230.42 ETC. |
| |
| 4)NOTE: NOTE #4 NO, PLEASE INDICATE |
| ATTACHMENT LOCATION FOR TRANSFORMER PER |
| 250.30 |
| PLEASE SEE THIS IS REQUIRED TO BE SHOWN |
| BACK TO THE EXISTING GROUNDING ELECTRODE |
| SYSTEM.(NOTES, ONE LINE) ETC |
| |
| 5)NOTE: NOTE #5 NO, PLEASE SEE MAIN IS |
| LABLED 1OF 1, HOWEVER RISER SHOWS TWO |
| MAINS. THE OTHER IS SHOWN 2 OF 2. , THE |
| OTHER SHOULD BE LABLED 1 OF 2. |
| |
| 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC |
| RATINGS FOR ALL NEW SERVICE EQUIPMENT |
| BEING INSTALLED. MAINS/BRKRS AND PANELS |
| ARE ALL TO BE RATED FOR THE AVAILABLE |
| FAULT CURRENT.PER 110.9/215.5 |
| ** IT IS NOTED THAT THE AIC RATINGS WERE |
| SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN |
| DISCONNECT RATING ALSO. |
| |
| NEW NOTE: |
| 7)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| PROFESSIONAL AND REPEAT COMMENTS. THIS |
| IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| AND ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONLY ONE COPY OF THE OLD VOIDED SHEETS |
| NEED TO BE SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THEREARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |