Plan Review Notes
Plan Review Notes For Permit 05100075
Permit Number 05100075
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-23 00:00:00*** UNSAT 2ND REVIEW ***
  
 PLEASE SEES SOME NOTES FROM PREVIOUS
 REVEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE BELOW NOTES ARE TAKEN
 DIRECTLY FROM THOSE NOTES.
  
 1)NOTE: NOTE #1 NO, PLEASE KNOW THAT ALL
 DESIGNS/PLANS SUBMITTED FOR PERMIT AFTER
 OCT 1ST, 2005 SHALL FALLUNDER THE 2004
 FBC.
 PLEASE ADJUST ALL SHEETS CONTAINING
 REFERENCE TO THE 2001 FBC. PLEASE ALSO
 SEE ALL MEP'S ,PLEASE SEE NOTES ON THESE
 SHEETS WITH REFERENCE TO THE 2001.
 PLEASE SEE SOME SHEETS HAD THESE CHANGES
 MADE. PLEASE SEE ELECTRICAL SHEET NOW
 HAS MISSING NOTES, PLEASE BE SURE TO
 SPECIFY THE NEC CURRENTLY IN
 EFFECT.(2002), NFPA-101 2003, NFPA-72,
 2002
  
 2)NOTE: NOTE #2 NO/YES,PLEASE SEE
 MISSSING CONDUCTORS FROM GUTTER TO
 METER. PLEASE SEE OTHER TO PANEL FROM
 TENANT DISCONNECT WERE ADDED.
 215.5, 310.16,240.4 ETC.
  
 3)NOTE:NOTE #3 NO, PLEASE SEE THAT ALL
 CONTINUOUS LOADS AND LARGEST MOTOR LOADS
 ARE SHOWN AT 125%.
 215.3,230.42 ETC.
  
 4)NOTE: NOTE #4 NO, PLEASE INDICATE
 ATTACHMENT LOCATION FOR TRANSFORMER PER
 250.30
 PLEASE SEE THIS IS REQUIRED TO BE SHOWN
 BACK TO THE EXISTING GROUNDING ELECTRODE
 SYSTEM.(NOTES, ONE LINE) ETC
  
 5)NOTE: NOTE #5 NO, PLEASE SEE MAIN IS
 LABLED 1OF 1, HOWEVER RISER SHOWS TWO
 MAINS. THE OTHER IS SHOWN 2 OF 2. , THE
 OTHER SHOULD BE LABLED 1 OF 2.
  
 6)NOTE: NOTE #6 NO, PLEASE SUBMIT AIC
 RATINGS FOR ALL NEW SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/BRKRS AND PANELS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.PER 110.9/215.5
 ** IT IS NOTED THAT THE AIC RATINGS WERE
 SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN
 DISCONNECT RATING ALSO.
  
 NEW NOTE:
 7)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS. THIS
 IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONLY ONE COPY OF THE OLD VOIDED SHEETS
 NEED TO BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.