Plan Review Notes For Permit 05100075 |
Permit Number |
05100075 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-10 00:00:00 | 1. PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. THEY ARE TO BE TYPE 2A 10BC | | PORTABLE FIRE EXTINGUISHERS CURRENTLY | | SERVICE TAGGED AND MOUNTED. | | | | 2. AISLES BETWEEN THE WORK STATIONS | | LOCATED IN THE OPEN WORK AREA SHALL BE | | ARRANGED TO PROVIDE FOR THE MINIMUM | | CLEARNCE OF 44 INCHES. THE PLANS SEEM TO | | REFLECT MORE WHICH IS ACCEPTABLE. | | | | 3. CONSTRUCTION, DEMOLITION, AND | | RENOVATION TO COMPLY WITH NFPA 241. | | | | 4. DEBRIS SHALL BE REMOVED DAILY FROM | | THE SITE. | | | | 5. EXISTING HANDRAILS AND GUARDRAILS ARE | | TO MEET THE PRESCRIPTIVE STRENGTH | | REQUIREMENTS OF THE BUILDING AND FIRE | | CODES. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER. | | 804-4709 |
|