2005-11-15 00:00:00 | ********* UNSAT *********** |
| |
| 1)NOTE: PLEASE KNOW THAT ALL |
| DESIGNS/PLANS SUBMITTED FOR PERMIT AFTER |
| OCT 1ST, 2005 SAHLL FALLUNDER THE 2004 |
| FBC. |
| PLEASE ADJUST ALL SHEETS CONTAINGIN |
| REFERENCE TO THE 2001 FBC. PLEASE ALSO |
| SEE ALL MEP'S ,A-SHEETS WITH RESPECT TO |
| REFERENCED CODES, TABLES ETC. |
| |
| 2)NOTE: PLEASE SEE MISSSING CONDUCTORS |
| ON RISER DIAGRAM FROM GUTTER TO METER, |
| METER TO MAIN AND TO SUB PANEL. |
| 215.5, 310.16,240.4 ETC. |
| |
| 3)NOTE: PLEASE SEE THAT ALL CONTINUOUS |
| LOADS AND LARGEST MOTOR LOADS ARE SHOWN |
| AT 125%. |
| 215.3,230.42 ETC. |
| |
| 4)NOTE: PLEASE INDICATE ATTACHMENT |
| LOCATION FOR TRANSFORMER PER 250.30 |
| |
| 5)NOTE: PLEASE SEE MAIN IS LABLED 1OF 1, |
| HOWNER RISER SHOWS TWO MAINS. THE OTHER |
| IS SHOWN 2 OF 2. , THE OTHER SHOULD BE |
| LABLED 1 OF 2. |
| |
| 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| IT IS NOTED THAT THE AIC RATINGS WERE |
| SHOWN FOR PANELS , HOWEVER SHOW NEW MAIN |
| DISCONNECT RATING ALSO. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THEREARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |