2005-11-21 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| 1.)GOVERNING CODE IS FBC2004 EFFECTIVE |
| 10/1/2005. |
| |
| 2.)BUILDING DATA (UNNUMBERED SHEET) |
| PROVIDES INCORRECT TABLE FOR INTERIOR |
| FINISH CLASSIFICATION, FBC TABLE 803.5. |
| |
| 3.)THE APPLICATION STATES THAT THIS IS |
| A TENANT IMPROVEMENT.PLANS SHOW A NEW |
| EXTERIOR STAIR AND WHEELCHAIR LIFT. |
| REVISE THE PERMIT APPLICATION. |
| |
| 4.)THE WHEELCHAIR LIFT IS TO COMPLY |
| WITH ASME A17.1, FBC3001.2. |
| |
| 5.)SHOW COMPLIANCE WITH FBC11-4.11.2, |
| FBC11-4.2.4 FOR THE LIFT.INDICATE THAT |
| THE SURFACE IS LEVEL. |
| |
| 6.)SHOW COMPLIANCE WITH ALL |
| REQUIREMENTS OF FBC11-4.27. |
| |
| 7.)PROVIDE A DETAIL FOR THE BREAKROOM |
| SINK, FBC11-24.PLEASE NOTE THE |
| REQUIREMENT FOR KNEE CLEARANCE, |
| FBC11-24.3. |
| |
| 8.)SHOW MANEUVERING CLEARANCE FOR DOOR |
| 106, PUSH SIDE, FBC11 FIGURE 25. |
| |
| 9.)THE STAIR HANDRAIL AT THE BOTTOM OF |
| THE STAIR IS TO COMPLY WITH |
| FBC11-4.8.5(6), FIGURE 11-19. |
| |
| 10.)SHOW THE DIMENSION OF THE HANDRAIL |
| EXTENSION AT THE TOP OF THE STAIR, |
| FBC1009.11.5. |
| |
| 11.)SHOW LANDING AND DOOR DIMENSIONS, |
| FBC1009.4, EXCEPTION 2. |
| |
| 12.)PROVIDE EITHER AN APPROVED |
| ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| FOR THE 1 HOUR WALL, FBC7. |