Plan Review Notes
Plan Review Notes For Permit 05100075
Permit Number 05100075
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)GOVERNING CODE IS FBC2004 EFFECTIVE
 10/1/2005.
  
 2.)BUILDING DATA (UNNUMBERED SHEET)
 PROVIDES INCORRECT TABLE FOR INTERIOR
 FINISH CLASSIFICATION, FBC TABLE 803.5.
  
 3.)THE APPLICATION STATES THAT THIS IS
 A TENANT IMPROVEMENT.PLANS SHOW A NEW
 EXTERIOR STAIR AND WHEELCHAIR LIFT.
 REVISE THE PERMIT APPLICATION.
  
 4.)THE WHEELCHAIR LIFT IS TO COMPLY
 WITH ASME A17.1, FBC3001.2.
  
 5.)SHOW COMPLIANCE WITH FBC11-4.11.2,
 FBC11-4.2.4 FOR THE LIFT.INDICATE THAT
 THE SURFACE IS LEVEL.
  
 6.)SHOW COMPLIANCE WITH ALL
 REQUIREMENTS OF FBC11-4.27.
  
 7.)PROVIDE A DETAIL FOR THE BREAKROOM
 SINK, FBC11-24.PLEASE NOTE THE
 REQUIREMENT FOR KNEE CLEARANCE,
 FBC11-24.3.
  
 8.)SHOW MANEUVERING CLEARANCE FOR DOOR
 106, PUSH SIDE, FBC11 FIGURE 25.
  
 9.)THE STAIR HANDRAIL AT THE BOTTOM OF
 THE STAIR IS TO COMPLY WITH
 FBC11-4.8.5(6), FIGURE 11-19.
  
 10.)SHOW THE DIMENSION OF THE HANDRAIL
 EXTENSION AT THE TOP OF THE STAIR,
 FBC1009.11.5.
  
 11.)SHOW LANDING AND DOOR DIMENSIONS,
 FBC1009.4, EXCEPTION 2.
  
 12.)PROVIDE EITHER AN APPROVED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FOR THE 1 HOUR WALL, FBC7.