Plan Review Notes
Plan Review Notes For Permit 05091714
Permit Number 05091714
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-07-18 00:00:00***DENIED***
  
 PLEASE NOTE THAT A RESPONSE LETTER
 ADDRESSING THE FIRE REVIEW WAS NOT FOUND
 WITH THIS SUBMITTAL. PLEASE BE ADVISED
 THAT THIS WILL HELP EXPEDITE THE PLAN
 REVIEW PROCESS.
  
 1) COMPLETE CIVIL DRAWINGS ARE TO BE
 SUBITTED ILLUSTRATING FIRE HYDRANTS AND
 WATER AND FIRE MAIN SIZES. ALL BACK FLOW
 PREVENTION DEVICES ARE TO BE SHOWN.
  
 2) FIRE HYDRANT SPACING IS NOT TO EXCEED
 300-500' APART.
  
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 4) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR EMERGENCY
 EQUIPMENT.
  
 5) BUILDING ADDRESSES ARE REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 6) ALL FIRE HYDRANTS ARE TO BE PROVIDED
 WITH PROPER CLEARANCES TO THE FRONT AND
 SIDES OF THEM.
  
 7) ALL HANDRAILS AND GUARDS ARE TO MEET
 PRESCIPTIVE STRENGTH REQUIREMENTS PER
 THE FLORIDA BUILDING CODE AND THE
 FLORIDA FIRE PREVENTION CODE.
  
 8) PLEASE EXPLAIN STORAGE AREAS NEAR
 EXIT STAIRS LOCATED ON THE SECOND FLOOR,
 CENTER CORE.
  
 9) A COMPLETE AUTOMATIC SUPERVISED FIRE
 SPRINKLER SYSTEM IS REQUIRED IN ALL (3)
 STORY BUILDINGS. PLEASE COMPLETE PLANS
 AND PERMITS AS REQUIRED.
  
 10) THE FIRE ALARM SYSTEM IS TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE. COMPLETE PLANS AND
 PERMITS REQUIRED PRIOR TO INSTALLATION.
  
 11) FIRE LINE BACKFLOW DEVICE SHALL BE
 EQUIPPED WITH TAMPER SWITCHES, CHAIN AND
 LOCK.
  
 12) A REVIEW OF THE CIVIL DRAWINGS
 INDICATE THAT ADDITIONAL FIRE HYDRANTS
 ARE NEEDED. FIRE DEPARTMENT SPRINKLER
 CONNECTIONS SHALL BE LOCATED NO FURTHER
 THAN 150' FROM A FIRE HYDRANT.
  
 13) THERE APPEARS TO BE NO FIRE HYDRANTS
 LOCATED ON THE APPROACH OR INTO THE
 COMPLEX.
  
 14) ALL SMOKE DETECTORS ARE TO BE
 INSTALLED A MINIMUM OF (3)' FROM HVAC
 DIFFUSERS.
  
 15) FIRE ALARM VISIBLE SIGNALS SHALL BE
 PROVIDED IN ROOMS DESIGNED FOR THE
 HEARING IMPAIRED.
  
 16)PLEASE INDICATE THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 17) ALL RESIDENTIAL BUILDINGS ARE TO
 COMPLY WITH CHAPTER 30, NFPA 101, 2003
 EDITION.
  
 18) ALL COMMON BUILDING STAIRS ARE TO BE
 PROVIDED WITH EMERGENCY LIGHTING
 EQUIPMENT.
  
 19) PLEASE EXPLAIN EXIT DISCHARGE FROM
 COMMON STAIRS. IT APPEARS THAT BOTH
 EMPTY INTO THE BUILDING. PLEASE EXPLAIN
 WHAT ALLOWS THIS TO OCCUR.
  
 20) EMERGENCY INSTRUCTIONS FOR RESIDENTS
 OR GUESTS ARE REQUIRED.
  
 21) KNOX BOXES WILL BE REQUIRED FOR THE
 COMMON ELEMENTS OF THE BUILDING.
  
 22) PORTABLE FIRE EXTINGUISHERS WITH BE
 REQUIRED.
  
 23) ARE THE GARAGE DOORS PROPERLY RATED?
 IT APPEARS THAT THE DOOR SCHEDULE
 DISPLAYS 45 MINUTES BUT THE GARAGE WALL
 IS OF GREATER VALUE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  