Text |
2006-07-18 00:00:00 | ***DENIED*** |
| |
| PLEASE NOTE THAT A RESPONSE LETTER |
| ADDRESSING THE FIRE REVIEW WAS NOT FOUND |
| WITH THIS SUBMITTAL. PLEASE BE ADVISED |
| THAT THIS WILL HELP EXPEDITE THE PLAN |
| REVIEW PROCESS. |
| |
| 1) COMPLETE CIVIL DRAWINGS ARE TO BE |
| SUBITTED ILLUSTRATING FIRE HYDRANTS AND |
| WATER AND FIRE MAIN SIZES. ALL BACK FLOW |
| PREVENTION DEVICES ARE TO BE SHOWN. |
| |
| 2) FIRE HYDRANT SPACING IS NOT TO EXCEED |
| 300-500' APART. |
| |
| 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 4) SUITABLE ROADS ARE TO BE PROVIDED |
| DURING CONSTRUCTION FOR EMERGENCY |
| EQUIPMENT. |
| |
| 5) BUILDING ADDRESSES ARE REQUIRED. A |
| MINIMUM OF AT LEAST 6" HIGH NUMBERS ARE |
| REQUIRED. |
| |
| 6) ALL FIRE HYDRANTS ARE TO BE PROVIDED |
| WITH PROPER CLEARANCES TO THE FRONT AND |
| SIDES OF THEM. |
| |
| 7) ALL HANDRAILS AND GUARDS ARE TO MEET |
| PRESCIPTIVE STRENGTH REQUIREMENTS PER |
| THE FLORIDA BUILDING CODE AND THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| 8) PLEASE EXPLAIN STORAGE AREAS NEAR |
| EXIT STAIRS LOCATED ON THE SECOND FLOOR, |
| CENTER CORE. |
| |
| 9) A COMPLETE AUTOMATIC SUPERVISED FIRE |
| SPRINKLER SYSTEM IS REQUIRED IN ALL (3) |
| STORY BUILDINGS. PLEASE COMPLETE PLANS |
| AND PERMITS AS REQUIRED. |
| |
| 10) THE FIRE ALARM SYSTEM IS TO BE |
| MONITORED BY A LICENSED UL LISTED |
| CENTRAL STATION APPROVED FOR CENTRAL |
| STATION SERVICE. COMPLETE PLANS AND |
| PERMITS REQUIRED PRIOR TO INSTALLATION. |
| |
| 11) FIRE LINE BACKFLOW DEVICE SHALL BE |
| EQUIPPED WITH TAMPER SWITCHES, CHAIN AND |
| LOCK. |
| |
| 12) A REVIEW OF THE CIVIL DRAWINGS |
| INDICATE THAT ADDITIONAL FIRE HYDRANTS |
| ARE NEEDED. FIRE DEPARTMENT SPRINKLER |
| CONNECTIONS SHALL BE LOCATED NO FURTHER |
| THAN 150' FROM A FIRE HYDRANT. |
| |
| 13) THERE APPEARS TO BE NO FIRE HYDRANTS |
| LOCATED ON THE APPROACH OR INTO THE |
| COMPLEX. |
| |
| 14) ALL SMOKE DETECTORS ARE TO BE |
| INSTALLED A MINIMUM OF (3)' FROM HVAC |
| DIFFUSERS. |
| |
| 15) FIRE ALARM VISIBLE SIGNALS SHALL BE |
| PROVIDED IN ROOMS DESIGNED FOR THE |
| HEARING IMPAIRED. |
| |
| 16)PLEASE INDICATE THE MINIMUM INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS. |
| |
| 17) ALL RESIDENTIAL BUILDINGS ARE TO |
| COMPLY WITH CHAPTER 30, NFPA 101, 2003 |
| EDITION. |
| |
| 18) ALL COMMON BUILDING STAIRS ARE TO BE |
| PROVIDED WITH EMERGENCY LIGHTING |
| EQUIPMENT. |
| |
| 19) PLEASE EXPLAIN EXIT DISCHARGE FROM |
| COMMON STAIRS. IT APPEARS THAT BOTH |
| EMPTY INTO THE BUILDING. PLEASE EXPLAIN |
| WHAT ALLOWS THIS TO OCCUR. |
| |
| 20) EMERGENCY INSTRUCTIONS FOR RESIDENTS |
| OR GUESTS ARE REQUIRED. |
| |
| 21) KNOX BOXES WILL BE REQUIRED FOR THE |
| COMMON ELEMENTS OF THE BUILDING. |
| |
| 22) PORTABLE FIRE EXTINGUISHERS WITH BE |
| REQUIRED. |
| |
| 23) ARE THE GARAGE DOORS PROPERLY RATED? |
| IT APPEARS THAT THE DOOR SCHEDULE |
| DISPLAYS 45 MINUTES BUT THE GARAGE WALL |
| IS OF GREATER VALUE. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |