2006-07-13 00:00:00 | PLAN REVIEW DENIED |
| |
| ITEMS NEEDED TO BE INCLUDED WITH PLANS |
| FOR BEFORE PERMITTING. |
| |
| 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 4.PLANS SHALL BE SIGNED, SEALED AND |
| DATED BY THE ARCHITECT AND ENGINEERS OF |
| RECORD.FS 481.221 AND 471.025SEE |
| ELECTRICAL REVIEW REGARDING THIS AND |
| TITLE BLOCK ISSSUES. |
| |
| 7.SUBMIT TWO COMPLETE SETS OF PRODUCT |
| APPROVALS FOR THE FOLLOWING, FLAT |
| ROOFING AND SELECT THE ASSEMBLY USED |
| ALL EXTERIOR EQUIPTMENT DOORS, STRAPS |
| AND TIE-DOWNS. |
| |
| 8.SUBMIT THE FOLLOWING STATE PRODUCT |
| AND ATTACHE TO THE PRODUCT APPROVALS |
| USED. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 14.SHOW A SPRINKLER SYSTEM COMPLYING |
| WITH TABLE 500 NOTE "D". |
| |
| 15.SUBMIT TWO ORIGONALS OF A SOILS |
| REPORT SHOWING FOUNDATION AND FOOTING |
| RECOMMENDATIONS. |
| |
| 17.ROOF SHEATHING SHALL COMPLY WITH |
| FBC 2322.2.5 AND WEST PALM BEACH |
| AMMENDMENTS TABLE 2306.1.SHOW ROOF |
| FASTENING ZONES ON PLANS. |
| |
| 18.THE 2 HOUR RATED WALL BETWEEN |
| GARAGE AND LIVING SPACE SHALL HAVE A |
| DOOR RATED IN COMPLIANCE WITH FBC TABLE |
| 705.1.2. |
| |
| NEW COMMENTS: |
| A.HAND DRAWN CHANGES NOT PERMITTED TO |
| PLANS.FBC 2001 WPB AMMENDMENTS |
| 104.2.1.3 |
| |
| B.PLANS SPEC THAT THEY ARE DESIGNED TO |
| THE 2001 FBC YET PAGE SD1.O STILL |
| REFLECTS THE 2004 FBC. |
| |
| IMPORTANT: |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |