2006-07-16 00:00:00 | PAUL SCHMITZ |
| FBC 2001 FUEL GAS CODE PLAN REVIEW |
| FBC 2001 PLUMBING CODEPLAN REVIEW |
| FBC 2001 FL ACESSIBILITY CODE PLAN |
| REVIEW |
| |
| UNSAT |
| THE FOLLOWING COMMENTS HAVE NOT BEEN |
| ADDRESSED, FROM PREVIOUS PLAN REVIEW |
| DATED 01-25-06 BY KEN STEVENS. |
| |
| 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS |
| REQUIRED ON THE WATER SERVICE OF EACH |
| BUILDING. SECTION 608.13.2. |
| |
| 6. SHT A.18 LAVS IN THE POWDER ROOMS OF |
| THE TOWNHOUSES SHALL BE COVERED PER FHA |
| DESIGN MANUAL PAGES 7, 7.33, & 7.35 |
| EXCEPTION. LAV SHALL BE CENTERED ON THE |
| 48" LENGTH OF THE PARALLEL CLEAR FLOOR |
| SPACE, OR BE A FRONTAL APPROACH. PAGE |
| 7.47. LAVS SHALL BE 34" TO RIM PER PAGE |
| 7.52. (SEE DETAIL #2). |
| |
| 7. SHT A.18 FIRST DETAIL #3, SHOWER |
| CLEAR FLOOR SPACE SHALL BE PARALLEL TO |
| THE FIXTURE AND FLUSH WITH THE CONTROL |
| WALL. PAGE 7.56. LAV PARALLEL CLEAR |
| FLOOR SPACE SHALL BE CENTERED ON THE LAV |
| A MINIMUM OF 2' OFF THE WALL. INDICATE |
| MEASUREMENT FROM WALL TO CENTER OF LAV |
| FOR ALL DETAILS. |
| |
| 9. SHT A.19 ALL BATHROOM DETAILS, SHOW |
| HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF |
| WALL TO CENTER OF FIXTURE & MEASUREMENTS |
| FOR ALL W/C OPENINGS TO SHOWN ON PLANS. |
| MINIMUM 33" REQUIRED. SEE PAGES 7.43, |
| 7.44, 7.45, & 7.46. |
| |
| 16. SHTS P-9 & P-10 WATER RISER DIAGRAM |
| ISOMETRICS, AIR CHAMBERS ARE NOT |
| APPROVED. AND WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9, (W/M, ICE |
| MAKER, DISHWASHER), SHALL BE LOCATED |
| NEAR THE FIXTURES IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. |
| PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. |
| |
| 18. SUBMIT A WATER HEATER DETAIL SHOWING |
| ALL PIPE SIZES, VALVES, THERMAL |
| EXPANSION CONTROL, P/T VALVE SHOWING |
| PIPING AND INDICATING THE TERMINATION |
| POINT. SECTIONS 104.2.1, 504.7.1, AND |
| 607.3.2. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS, QUESTIONS 561-805-6692 |
| |