2006-07-05 00:00:00 | DENIED:2001 FBC/BUILDING #11 |
| RESPONSE TO COMMENTS DATED 1/13/06 |
| |
| COMMENT #1 - OK |
| COMMENT #2 - OK |
| COMMENT #3 - OK |
| COMMENT #4 - OK PLEASE CLARIFY PLAN |
| SHEET M-8 EXHAUST DUCT ROOF CAP DETAIL. |
| WILL EACH TOILET EXHAUST TERMINATE TO |
| THE OUTDOORS OR WILL THIS BE A |
| 'SUB-DUCT' METHOD? |
| COMMENT #5 - OK |
| COMMENT #6 - OK |
| COMMENT #7 - PLEASE DNOTE, THE 2001 FMC |
| DOES NOT GIVE THE OPTION FOR THE |
| INSTALLATION OF BOOSTER FANS ON THE |
| DRYER EXHAUST.THIS MUST BE SUBMITTED |
| TO THE BUILDING OFFICAL UNDER "ALTERNATE |
| MATERIALS & METHODS" 2001 AMENDMENTS TO |
| THE 2001 FBC 103.7.1.PLEASE PROVIDE |
| SUBMITTAL FOR THE BOOSTER FAN.NOTE #3 |
| ON M-3 INDICATES THE BOOSTER FAN IS |
| "MANUFACTURER'S RECOMMENDED" UL LISTED |
| BOOSTER FAN.PLEASE ALSO PROVIDE A |
| LETTER FROM AN ENGINEER EMPLOYED BY THE |
| MANUFACTURER GIVING THE MANUFACTURER'S |
| APPROVAL FOR THIS INSTALLATION. |
| COMMENT #8 - OK |
| COMMENT #9- PLEASE NOTE, SHAFT |
| ENCLOSING THE REFRIGERANT LINES SHALL BE |
| VENTED IN ACCORDANCE WITH ASHRAE 15-1992 |
| SECTUIB 11.12.3 (B). |
| COMMENT #10 - OK |
| COMMENT #11 - AHU-L DUCT SHALL BE IN A |
| RATED SHAFT IN ACCORDANCE WITH 2001 FMC |
| 607.4. |
| COMMENT #12 - OK |
| COMMENT #13 - RESPONSE INDICATES PRODUCT |
| APPROVAL FOR THE CONDENSING UNIT STANDS |
| IS ATTACHED TO THE PLANS.PLEASE NOTE, |
| PRODUCT APPROVAL IS NOT ATTACHED TO |
| PERMIT APPLICATION OR PLAN.PLEASE |
| PROVIDE FLORIDA STATE PRODUCT APPROVAL. |
| COMMENT #14 - OK |
| COMMENT #15 - OK |
| COMMENT #16 - OK |
| COMMENT #17 - OK |
| COMMENT #18 - RESPONSE INDICATES FLOAT |
| SWITCH FOR OVERFLOW PROTECTION.PLEASE |
| INDICATE LOCATION OF THE FLOAT SWITCH. |
| PLEASE NOTE, FLOAT SWITCH IS NOT TO BE |
| INSTALLED IN THE PRIMARY DRAIN PAN.IT |
| SHALL BE INSTALLED IN THE OVERFLOW OR |
| SECONDARY DRAIN SHOULD THIS UNIT BE A |
| BOTTOM RETURN. SHOULD THE RETURN BE |
| LOCATED IN THE SIDE AN AUXILIARY DRAIN |
| PAN WILL BE REQUIRED. |
| |
| ****************NEW COMMENTS************ |
| 19. PLAN SHEET M-3 NOTE 2 INDICATES |
| RETURN AIR THROUGH LOUVERED DOOR AT THE |
| AHU CLOSET.PLEASE NOTE, LOUVERED DOOR |
| & FRAME SHALL BE NON-COMBUSTIBLE AS |
| REQUIRED PER 2001 FMC 602.2.1. |
| |
| 20. PLAN SHEET M-5 SHOWS REFRIGERANT |
| LINES THROUGH THE STAIRWELL.PER 2001 |
| FBC 1006.1.3.1 THIS IS PROHIBITED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATT KRAUSS AT (561)805-6719. |