Date |
Text |
2006-01-26 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHTS 1 THRU 7 (CIVIL) SHEETS, THE |
| CERTIFICATE OF AUTHORIZATION IS REQUIRED |
| ON THE TITLE BLOCK OF EACH SHEET. FAC |
| 61G15-23.003 & FS 471.025. |
| 2. SHT 1 OF 7 PROPOSED CLUBHOUSE SHOWS |
| NO SANT. OR WATER SERVICE. PLEASE |
| CLARIFY. SECTION 104.2.1. |
| 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS |
| REQUIRED ON THE WATER SERVICE OF EACH |
| BUILDING. SECTION 608.13.2. |
| 4. SHT SP-1, SP-2, A1 THRU A.28 |
| ARCHITECTS BUSINESS NUMBER IS REQUIRED |
| IN THE TITLE BLOCK OF EACH SHEET. FAC |
| 61G1-16.004(2) & FS 481.219. |
| 5. SHT A-7 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| THE SF OF EACH DRAINED AREA, WITH 1/2 |
| AREA OF ALL VERTICAL WALLS INCLUDING |
| PARAPETS, AND AREA OFF ROOFS THAT DRAIN |
| ONTO THE ROOF AREAS FROM ABOVE IN |
| CALCULATIONS. SHOW THE LOCATION OF ALL |
| SECONDARY ROOF DRAINS/SCUPPERS. INDICATE |
| THE SF OF STAIR ROOF, AND SHOW THE SIZE |
| OF THE GUTTERS, SIZE OF DOWNSPOUTS, |
| SLOPE OF GUTTERS AND INDICATE HIGH POINT |
| OF GUTTERS. SECTIONS 1106 & 1107 AND ALL |
| SUBSECTIONS. |
| 6. SHT A.18 LAVS IN THE POWDER ROOMS OF |
| THE TOWNHOUSES SHALL BE COVERED PER FHA |
| DESIGN MANUAL PAGES 7, 7.33, & 7.35 |
| EXCEPTION. LAV SHALL BE CENTERED ON THE |
| 48" LENGTH OF THE PARALLEL CLEAR FLOOR |
| SPACE, OR BE A FRONTAL APPROACH. PAGE |
| 7.47. LAVS SHALL BE 34" TO RIM PER PAGE |
| 7.52. (SEE DETAIL #2). |
| 7. SHT A.18 FIRST DETAIL #3, SHOWER |
| CLEAR FLOOR SPACE SHALL BE PARALLEL TO |
| THE FIXTURE AND FLUSH WITH THE CONTROL |
| WALL. PAGE 7.56. LAV PARALLEL CLEAR |
| FLOOR SPACE SHALL BE CENTERED ON THE LAV |
| A MINIMUM OF 2' OFF THE WALL. INDICATE |
| MEASUREMENT FROM WALL TO CENTER OF LAV |
| FOR ALL DETAILS. |
| 8. SHT A.18 DETAIL #4, A 60" DIAMETER |
| TURNING CIRCLE IS REQUIRED IN A "U" |
| SHAPED KITCHEN THAT HAS A SINK, RANGE, |
| OR COOKTOP AT ITS BASE. THIS IS IN |
| ADDITION TO THE CLEAR FLOOR SPACE. PAGE |
| 7.9. |
| 9. SHT A.19 ALL BATHROOM DETAILS, SHOW |
| HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF |
| WALL TO CENTER OF FIXTURE & MEASUREMENTS |
| FOR ALL W/C OPENINGS TO SHOWN ON PLANS. |
| MINIMUM 33" REQUIRED. SEE PAGES 7.43, |
| 7.44, 7.45, & 7.46. |
| 10. ALL E,M & P SHEETS. ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME AND LICENSE |
| NUMBER ON EACH SHEET. FAC |
| 61G15-23.002(2) & FAC 471.025. |
| 11. SHTS P-3 & P-4 SHOWS 4" UP TO THE |
| 3RD FLOOR FOR THE SANT. RISER. P-5 & P-6 |
| SHOW 3" ON ALL. PLEASE CORRELATE SECTION |
| 104.2.1. |
| 12. SHT P-7 SHOW 3" RWLS ROOF DRAINS |
| ISOMETRIC AS "3" RWL BELOW SLAB" PLEASE |
| CLARIFY. SECTION 104.2.1. |
| 13. SHT P-7 SHOW THE LOCATION OF ALL |
| SECONDARY ROOF DRAINS/SCUPPERS. SHOW THE |
| SIZE OF EACH DRAIN OR THE HEIGHT & WIDTH |
| OF EACH SCUPPER, PIPING WITH SIZING, |
| MEASUREMENT OFF THE ROOF TO THE FLOW |
| LINE ETC. SECTIONS 104.2.1, 1106, & 1107 |
| 14. SHT P-8 SANT. RISER DIAGRAM |
| ISOMETRIC DOES NOT REFLECT THE FLOOR |
| PLANS. THE RISER NUMBERS ARE OPPOSITE OF |
| THE FLOOR PLANS. THE LAYOUTS OF SOME |
| UNITS ON THE 1ST FLOOR DO NOT REFLECT |
| THE FLOOR PLAN. THE SECOND FLOOR RISER |
| DOES NOT REFLECT THE FLOOR PLAN AS THEY |
| ARE OPPOSITE OF THE FLOOR PLAN ON MOST |
| RISERS, AND SOME RISERS ARE MISSING |
| FIXTURES & RISERS. 3RD FLOOR RISERS ARE |
| OPPOSITE OF FLOOR PLAN. CORRELATE THE |
| RISER DIAGRAMS WITH THE FLOOR PLANS, |
| CHECK ALL PIPE SIZES WITH FLOOR PLANS. |
| INDICATE DFUS AS THEY ACCUMULATE IN THE |
| SYSTEM.SECTION 104.2.1 AND TABLE |
| 710.1(1). |
| 15. SHTS P-9 & P-10 WATER RISER DIAGRAM |
| ISOMETRIC DOES NOT REFLECT THE FLOOR |
| PLAN. RISER SHOWS 1" COLD WATER SERVICE |
| UP TO PENTHOUSE LEVEL, BUT FLOOR PLAN |
| SHOWS 1-1/2" COLD WATER SERVICE UP TO |
| PENTHOUSE LEVEL ON SHTS P-1 THRU P-4. |
| PLEASE CORRELATE FLOOR PLANS AND RISER |
| DIAGRAMS. |
| 16. SHTS P-9 & P-10 WATER RISER DIAGRAM |
| ISOMETRICS, AIR CHAMBERS ARE NOT |
| APPROVED. AND WATER HAMMER ARRESTORS |
| REQUIRED BY SECTION 604.9, (W/M, ICE |
| MAKER, DISHWASHER), SHALL BE LOCATED |
| NEAR THE FIXTURES IN AN "EFFECTIVE |
| RANGE" NOT IN THE CEILING AS SHOWN. |
| PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. |
| 17. SHT P-9 SHOWN THE WATER HEATERS IN |
| AN EMERGENCY PAN, WHERE AS P-10 SHOWS NO |
| PAN. W/H'S ON THE FIRST FLOOR ARE DO NOT |
| REQUIRE A HEATER PAN UNLESS THEY ARE ON |
| A SHELF. PLEASE CLARIFY. SECTIONS |
| 104.2.1. & 504.8. |
| 18. SUBMIT A WATER HEATER DETAIL SHOWING |
| ALL PIPE SIZES, VALVES, THERMAL |
| EXPANSION CONTROL, P/T VALVE SHOWING |
| PIPING AND INDICATING THE TERMINATION |
| POINT. SECTIONS 104.2.1, 504.7.1, AND |
| 607.3.2. |
| 19. SHT P-11 PLUMBING GENERAL NOTES: |
| E-22 AIR CHAMBERS ARE NOT APPROVED. |
| DELETE FROM REFERENCE. SECTION 604.9. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |