2005-12-25 00:00:00 | ************ UNSAT ************* |
| |
| |
| DIXIE MEWS / AQUA TERRACE |
| |
| 1)NOTE: PLEASE PROVIDE SIGNED, DATED AND |
| SEALED PLANS BY ARCHITECT AND |
| ENGINEER(S) OF RECORD. |
| FS 481.221 AND 471.025 |
| PLEASE SEE PLANS CONTAIN SOME SORT OF |
| "CORPORATE SEAL' WHICH IS NOT |
| ACCEPTABLE. |
| PLEASE KNOW THIS IS REQUIRED OF ALL |
| SHEETS AND FOR ALL TRADE REVIEWS WHETHER |
| OR NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| |
| 2)NOTE: PLEASE COMPLETE AND INCLUDE ALL |
| INFORMATION ON SAID TITLE BLOCKS FOR |
| ARCHITECTUAL AND ENGINEERING FIRMS. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODES |
| 61G1-16.004 (ARCH) AND 61G15-23.002 |
| (ENG). |
| PLEASE KNOW THIS IS REQUIRED FOR ALL |
| SHEETS AND FOR ALL TRADES. |
| |
| 3)NOTE: PLEASE SEE THERE IS REFERENCE TO |
| BLDGS AS "TOWNHOUSES", PLEASE SEE THESE |
| DO NOT APPEAR TO BE FEE SIMPLE? |
| PLEASE SEE BUILDING AND ZONING COMMENTS |
| AS THIS WILL COMPLETELY CHANGE |
| ELECTRICAL DESIGN IF INDEED FEE SIMPLE |
| "TOWNHOUSES". |
| |
| 4)NOTE: PLEASE VERIFY CLEARENCES FOR |
| ELECTRICAL SERVICE PER 110.26, |
| APPEARS TO SHOW DOORS WHICH WILL SLIDE |
| OPEN ON EACH SIDE, HOWEVER THIS WILL |
| ALWAYS CREATE A COMMON POINT IN THE |
| CENTER WHICH WOULD NOT MEET CODE. |
| PLEASE PROVIDE AN ELEVATION AS HEIGHT |
| AND WIDTH IS TO BE VERIFIED. |
| PLEASE ALSO VERIFY IT APPEARS THIS |
| ROOM/AREA IS ALSO THE GRESS FROM COMMON |
| STAIR TOWER AND LOBBY AREA? |
| PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE |
| SEPARATION AS STAIRS EXIT INTO THIS AREA |
| AND NO DOORS ARE SHOWN WHICH MAY ALLOW |
| EXISTING BACK INTO COMMON LOBBY AREA |
| PLEASE SEE THIS IS SHOWING SWITCHING FOR |
| LTS? |
| PLEASE ALSO SEE NEXT COMMENT WITH |
| RESPECT TO THE CIRCUIT SHOWN. |
| |
| 5)NOTE: PLEASE SEE HOUSE CIRCUIT SHOWN |
| FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN |
| FEEDING OTHER AREAS. PLEASE SEE 620.23 |
| WHICH REQUIRES THE BRANCH CIRCUIT FOR |
| LTS AND RECEPTS TO BE DEDICATED. |
| PLEASE ADJUST. |
| |
| 6)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR |
| COMMON AREAS FOR EGRESS LIGHTING. PLEASE |
| SEE THIS WOULD INCLUDE LOBBY AREAS, |
| STAIR TOWERS, SHOW ALL FT CANDLES TO THE |
| EXIT/PUBLIC RIGHT OF WAY. |
| PLEASE SEE 2003 NFPA-101 7.8 AND 7.9 |
| WHICH REQUIRES 10 FT CANDLES UNDER |
| NORMAL POWERE AND A MIN OF 1FT CANDLE |
| UNDER EM POWER. |
| PLEASE ALSO SEE FURTHER COMMENTS WIHT |
| RESPECT TO FIXTURES. |
| |
| 7)NOTE: PLEASE PROVIDE A FIXTURE |
| SCHEDULE FOR ALL FIXTURES. PLEASE SEE |
| COMPLIANCE FOR STAIR TOWERS, CLOSETS ETC |
| NEED TO BE VERIFIED. |
| 215.5 |
| |
| 8)NOTE: PLEASE COMPLETE A/C CU LAYOUT ON |
| ROOFTOP PLANS FOR ALL UNITS. 8 SHOWN |
| WHICH SHOULD SHOW A TOTAL OF 16 UNITS TO |
| CORRELATE WITH PANEL SCHEDULES AND |
| UNITS. |
| PLEASE ALSO CLARIFY CU DETAIL WHICH IS |
| SHOWING THEDISCONNECTS BEING MOUNTED |
| TO THE CU? |
| PLEASE VERIFY OCP SHOWN AT 40A'S?(TYP) |
| PLEASE SEE M-SHEETS WHICH SHOW MORE THAN |
| ONE TYPE OF UNIT. 15A'S, 30A'S ETC. |
| PLEASE ADJUST DISCONNECT DETAIL AS |
| NEEDED. |
| PLEASE SEE IF CHANGING OUT UNIT, UNIT |
| WOULD STILL HAVE POWER COMING TO UNIT. |
| |
| 9)NOTE: PLEASE SHOW THE CONDUCTORS FROM |
| HOUSE GUTTER TO EACH DISCONNECT. |
| 215.5 |
| |
| 10)NOTE: PLEASE VERIFY WITH THE FIRE |
| MARSHAL'S OFFICE IF INDEED THE UNIT SD'S |
| WILL BE TIED INTO BASE BLDG PROTECTION |
| SYSTEM. |
| PLEASE KNOW, IF THESE ARE 120V WIRED |
| INLINE IN UNITS, THEN CIRCUITING WILL BE |
| REQUIRED ALONG WITH ARC FAULT |
| PROTECTION. |
| 215.5,210.12 |
| THIS WOULD ALSO BE AFFECTED BY THE |
| "TOWNHOUSE" DECLARATION. |
| |
| 11)NOTE: PLEASE PROVIDE ALL AREA AND |
| ROOM DESIGNATIONS ON PLANS FOR UNITS. |
| NEED TO VERIFY CIRCUITING. |
| 215.5 |
| |
| 12)NOTE: PLEASE INCLUDE ELECTRICAL |
| CONNECTION FOR JACUZZI, WILL THIS BE A |
| HARDWIRED UNIT WITH A DISCONNECTING |
| MEANS OR A RECEPT? |
| PANEL SCHEDULE SHOWS THE GFI PROTECTION. |
| PLEASE ALSO SEE ONLY THE CIRCUIT IS |
| SHOWN ON PLANS. |
| PLEASE SHOW THE ACCESS, PLEASE SEE SOME |
| CIRCUIT #'S SHOWN APPEAR TO BE LOCATED |
| AT THE REAR OF THE UNIT. IS THERE A |
| CLOSET ACCESS.? |
| |
| 13)NOTE: PLEASE VERIFY IN SOME UNITS A |
| RECEPT IS BEING SHOWN IN CLOSET? CIRCUIT |
| #1. |
| PLEASE KNOW, IF THIS IS FOR A PLUG IN |
| TYOE TRANSFORMER, THE LOCATION OF THE |
| RECEPT WOULD ONLY BE PERMITTED DIRECTLY |
| ABOVE THE DOOR OR RECEPT FOR ANY |
| TRANSFORMER WOULD BE REQUIRED TO BE |
| MOVED. |
| PLEASE KNOW, THE PLUG IN TYPE |
| TRANSFORMERS, MANY CONTAING OCP ETC |
| BECOME EXTREMELY HOT AND HAVE MELTED IN |
| THIS AND OTHER JURISTICTIONS CUASING |
| FIRES. |
| THE COMBUSTIBLES IN CLOSET AREA WOULD |
| ONLY ACT AS AN ACCELERANT. |
| |
| 14)NOTE: PLEASE SEE OTHER CLOSETS, |
| MOSTLY IN UPPER UNITS ARE SHOWING LTS |
| WHICH DO NOT MEET MIN CLEARENCE |
| REQUIREMENTS PER 410.8. PLEASE ALSO SEE |
| PREVIOUS COMMENT WITH RESPECT TO THE |
| FIXTURE SCHEDULE TO BE PROVIDED FOR |
| REVIEW. |
| |
| 15)NOTE: PLEASE SEE SOME UNITS APPEAR TO |
| SHOW SOME SORT OF CEILING LINE , AS IF |
| THE HALL AREA CEILING MAY BE LOWER THAN |
| ACTUAL BEDRM CEILING HEIGHTS? |
| PLEASE SEE NFPA-72 11.8.3.5 WHICH |
| REQUIRES ALL SD'S TO BE LOCATED AT THE |
| HIGHEST POINT POSSIBLE ON A FLAT |
| CEILING. |
| IF WALL MOUNTED, THEN THIS WOULD REQUIRE |
| THESE TO BE LOCATED WITHIN 12" OF |
| CEILING BUT NOT CLOSER THAN 4" IF INDEED |
| THE CEILINGS IN BEDRMS ARE HIGHER, |
| PLEASE MOVE SD'S TO BE LOCATED TO MEET |
| CODE. |
| |
| 16)NOTE: PLEASE SEE A "NOTE" ON E-4 |
| WHICH MENTIONS A "CONTINUOUS ROW OF |
| FLOUR LTS" ETC TO BE MOUNTED IN COVE? |
| PLEASE KNOW, THESE COULD NOT BE LOCATED |
| ON 2ND FLR OF UNITS AS NOTED. |
| ONLY LOCATED ON E-3 2ND FLR COMMON AREA. |
| |
| 17)NOTE: PLEASE SEE 210.52 FOR RECEPTS |
| MISSING FOR 2' OR MORE OF WALL SPACE. |
| PLEASE SEE MOST IF THESE LOCATIONS ARE |
| REDLINED ON PLANS. (SEE MOSTLY 3RD FLR. |
| |
| 18)NOTE: PLEASE CLARIFYLOCATIONS OF |
| WASHER/DRYERS ON 3RD FLR UNITS. PLANS |
| SHOW THE LOCATION OF RECEPT FOR DRYERS, |
| HOWEVER WITH THE LAYOUT AS SHOWN, THE |
| DRYER WOULD NOT FIT IN THESE LOCATIONS?? |
| |
| 19)NOTE: PLEASE SEE 3RD FLR UNITS WHICH |
| SHOW LIGHTING BEING CIRCUITED TO THE |
| DINING RM / SMALL APPLIANCE CIRCUIT. |
| PLEASE SEE 210.52B1 WHICH ONLY PERMITS |
| THE RECEPTS WITH SOME EXCEPTIONS, |
| HOWEVER LTS AS SHOWN MAY NOT BE ON THIS |
| CIRCUIT. PLEASE ADJUST. |
| |
| 20)NOTE: PLEASE SEE TOP FLR UNIT, WHICH |
| DOES NOT SEEM TO SHOW A FIXTURE AT THE |
| END OF THE SW LEG IN WHAT APPEARS TO BE |
| A BEDRM. |
| (MISPRINT). |
| |
| 21)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| PLEASE SEE IT IS NOTED FORALL BUT |
| HOUSE MAIN DISCONNECT. |
| |
| 22)NOTE: PLEASE VERIFY THE CONNECTION |
| POINT AS NOTED FOR GROUNDING ELECTRODE |
| CONDUCTOR TO THE REBAR/FOOTER STEEL. |
| IT IS UNCLEAR WHAT "THREE SETS OF WRAP |
| TO BOND"? THIS METHOD IS UNLCEAR AND NOT |
| KNOWN. |
| PLEASE PROVIDE THE PERMITTED CONNECTION |
| AS SET-FORTH IN THE NEC. 250.50 OR |
| PROVIDE FUTHER DETAIL FOR THIS. |
| ABOVE IS NOTED AS ALL CONNECTIONS BEING |
| EXOTHERMIC, IS THIS FOR THIS LOCAITON |
| ALSO? |
| |
| 23)NOTE: PLEASE SEE PANEL "P" WHICH |
| SHOWS THE LOAD FOR GEN LT AND RECEPTS, |
| HOWEVER THEER SEEMS TO BE SOME SORT OF |
| NUMERICAL NOTE ADDED TO THE CIRCUITS 2 |
| AND 4? |
| MISPRINT? CLARIFY. |
| |
| 24)NOTE: PLEASE SEE "CLUBHOUSE" PERMIT |
| #05091714 FOR REVIEW. |
| |
| 25)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| ALL SD'S TO BE INSTALLED PER 2002 |
| NFPA-72 11.8.3.5 |
| |
| ** PLEASE SEE ONE SET OF PLANS HAS MUCH |
| OF THE ABOVE REDLINED FOR AREAS OF |
| COMMENTS. THIS MAY HELP IN AREAS AS |
| NOTED. (RECEPTS ETC) |
| |
| ** PLEASE KNOW, A RESPONSE LETTER WITH |
| RESPECT TO COMMENTS AND WHAT ACTIONS |
| WERE TAKEN WOULD GREATLY HELP IN |
| EXPEDITING THE PLAN REVIEW PROCESS. |
| PLEASE KEEP IN MIND TO CLOUD/TRIANGLE |
| ANY REVISED LOCATIONS ON PLANS. |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |
2005-12-24 00:00:00 | IN ELEC FOR REVIEW |