2005-12-25 00:00:00************ UNSAT *************
  
  
 DIXIE MEWS / AQUA TERRACE
  
 1)NOTE: PLEASE PROVIDE SIGNED, DATED AND
 SEALED PLANS BY ARCHITECT AND
 ENGINEER(S) OF RECORD.
 FS 481.221 AND 471.025
 PLEASE SEE PLANS CONTAIN SOME SORT OF
 "CORPORATE SEAL' WHICH IS NOT
 ACCEPTABLE.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADE REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE COMPLETE AND INCLUDE ALL
 INFORMATION ON SAID TITLE BLOCKS FOR
 ARCHITECTUAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODES
 61G1-16.004 (ARCH) AND 61G15-23.002
 (ENG).
 PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES.
  
 3)NOTE: PLEASE SEE THERE IS REFERENCE TO
 BLDGS AS "TOWNHOUSES", PLEASE SEE THESE
 DO NOT APPEAR TO BE FEE SIMPLE?
 PLEASE SEE BUILDING AND ZONING COMMENTS
 AS THIS WILL COMPLETELY CHANGE
 ELECTRICAL DESIGN IF INDEED FEE SIMPLE
 "TOWNHOUSES".
  
 4)NOTE: PLEASE VERIFY CLEARENCES FOR
 ELECTRICAL SERVICE PER 110.26,
 APPEARS TO SHOW DOORS WHICH WILL SLIDE
 OPEN ON EACH SIDE, HOWEVER THIS WILL
 ALWAYS CREATE A COMMON POINT IN THE
 CENTER WHICH WOULD NOT MEET CODE.
 PLEASE PROVIDE AN ELEVATION AS HEIGHT
 AND WIDTH IS TO BE VERIFIED.
 PLEASE ALSO VERIFY IT APPEARS THIS
 ROOM/AREA IS ALSO THE GRESS FROM COMMON
 STAIR TOWER AND LOBBY AREA?
 PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE
 SEPARATION AS STAIRS EXIT INTO THIS AREA
 AND NO DOORS ARE SHOWN WHICH MAY ALLOW
 EXISTING BACK INTO COMMON LOBBY AREA
 PLEASE SEE THIS IS SHOWING SWITCHING FOR
 LTS?
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE CIRCUIT SHOWN.
  
 5)NOTE: PLEASE SEE HOUSE CIRCUIT SHOWN
 FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN
 FEEDING OTHER AREAS. PLEASE SEE 620.23
 WHICH REQUIRES THE BRANCH CIRCUIT FOR
 LTS AND RECEPTS TO BE DEDICATED.
 PLEASE ADJUST.
  
 6)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 COMMON AREAS FOR EGRESS LIGHTING. PLEASE
 SEE THIS WOULD INCLUDE LOBBY AREAS,
 STAIR TOWERS, SHOW ALL FT CANDLES TO THE
 EXIT/PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES 10 FT CANDLES UNDER
 NORMAL POWERE AND A MIN OF 1FT CANDLE
 UNDER EM POWER.
 PLEASE ALSO SEE FURTHER COMMENTS WIHT
 RESPECT TO FIXTURES.
  
 7)NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE FOR ALL FIXTURES. PLEASE SEE
 COMPLIANCE FOR STAIR TOWERS, CLOSETS ETC
 NEED TO BE VERIFIED.
 215.5
  
 8)NOTE: PLEASE COMPLETE A/C CU LAYOUT ON
 ROOFTOP PLANS FOR ALL UNITS. 8 SHOWN
 WHICH SHOULD SHOW A TOTAL OF 16 UNITS TO
 CORRELATE WITH PANEL SCHEDULES AND
 UNITS.
 PLEASE ALSO CLARIFY CU DETAIL WHICH IS
 SHOWING THEDISCONNECTS BEING MOUNTED
 TO THE CU?
 PLEASE VERIFY OCP SHOWN AT 40A'S?(TYP)
 PLEASE SEE M-SHEETS WHICH SHOW MORE THAN
 ONE TYPE OF UNIT. 15A'S, 30A'S ETC.
 PLEASE ADJUST DISCONNECT DETAIL AS
 NEEDED.
 PLEASE SEE IF CHANGING OUT UNIT, UNIT
 WOULD STILL HAVE POWER COMING TO UNIT.
  
 9)NOTE: PLEASE SHOW THE CONDUCTORS FROM
 HOUSE GUTTER TO EACH DISCONNECT.
 215.5
  
 10)NOTE: PLEASE VERIFY WITH THE FIRE
 MARSHAL'S OFFICE IF INDEED THE UNIT SD'S
 WILL BE TIED INTO BASE BLDG PROTECTION
 SYSTEM.
 PLEASE KNOW, IF THESE ARE 120V WIRED
 INLINE IN UNITS, THEN CIRCUITING WILL BE
 REQUIRED ALONG WITH ARC FAULT
 PROTECTION.
 215.5,210.12
 THIS WOULD ALSO BE AFFECTED BY THE
 "TOWNHOUSE" DECLARATION.
  
 11)NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS FOR UNITS.
 NEED TO VERIFY CIRCUITING.
 215.5
  
 12)NOTE: PLEASE INCLUDE ELECTRICAL
 CONNECTION FOR JACUZZI, WILL THIS BE A
 HARDWIRED UNIT WITH A DISCONNECTING
 MEANS OR A RECEPT?
 PANEL SCHEDULE SHOWS THE GFI PROTECTION.
 PLEASE ALSO SEE ONLY THE CIRCUIT IS
 SHOWN ON PLANS.
 PLEASE SHOW THE ACCESS, PLEASE SEE SOME
 CIRCUIT #'S SHOWN APPEAR TO BE LOCATED
 AT THE REAR OF THE UNIT. IS THERE A
 CLOSET ACCESS.?
  
 13)NOTE: PLEASE VERIFY IN SOME UNITS A
 RECEPT IS BEING SHOWN IN CLOSET? CIRCUIT
 #1.
 PLEASE KNOW, IF THIS IS FOR A PLUG IN
 TYOE TRANSFORMER, THE LOCATION OF THE
 RECEPT WOULD ONLY BE PERMITTED DIRECTLY
 ABOVE THE DOOR OR RECEPT FOR ANY
 TRANSFORMER WOULD BE REQUIRED TO BE
 MOVED.
 PLEASE KNOW, THE PLUG IN TYPE
 TRANSFORMERS, MANY CONTAING OCP ETC
 BECOME EXTREMELY HOT AND HAVE MELTED IN
 THIS AND OTHER JURISTICTIONS CUASING
 FIRES.
 THE COMBUSTIBLES IN CLOSET AREA WOULD
 ONLY ACT AS AN ACCELERANT.
  
 14)NOTE: PLEASE SEE OTHER CLOSETS,
 MOSTLY IN UPPER UNITS ARE SHOWING LTS
 WHICH DO NOT MEET MIN CLEARENCE
 REQUIREMENTS PER 410.8. PLEASE ALSO SEE
 PREVIOUS COMMENT WITH RESPECT TO THE
 FIXTURE SCHEDULE TO BE PROVIDED FOR
 REVIEW.
  
 15)NOTE: PLEASE SEE SOME UNITS APPEAR TO
 SHOW SOME SORT OF CEILING LINE , AS IF
 THE HALL AREA CEILING MAY BE LOWER THAN
 ACTUAL BEDRM CEILING HEIGHTS?
 PLEASE SEE NFPA-72 11.8.3.5 WHICH
 REQUIRES ALL SD'S TO BE LOCATED AT THE
 HIGHEST POINT POSSIBLE ON A FLAT
 CEILING.
 IF WALL MOUNTED, THEN THIS WOULD REQUIRE
 THESE TO BE LOCATED WITHIN 12" OF
 CEILING BUT NOT CLOSER THAN 4" IF INDEED
 THE CEILINGS IN BEDRMS ARE HIGHER,
 PLEASE MOVE SD'S TO BE LOCATED TO MEET
 CODE.
  
 16)NOTE: PLEASE SEE A "NOTE" ON E-4
 WHICH MENTIONS A "CONTINUOUS ROW OF
 FLOUR LTS" ETC TO BE MOUNTED IN COVE?
 PLEASE KNOW, THESE COULD NOT BE LOCATED
 ON 2ND FLR OF UNITS AS NOTED.
 ONLY LOCATED ON E-3 2ND FLR COMMON AREA.
  
 17)NOTE: PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OR MORE OF WALL SPACE.
 PLEASE SEE MOST IF THESE LOCATIONS ARE
 REDLINED ON PLANS. (SEE MOSTLY 3RD FLR.
  
 18)NOTE: PLEASE CLARIFYLOCATIONS OF
 WASHER/DRYERS ON 3RD FLR UNITS. PLANS
 SHOW THE LOCATION OF RECEPT FOR DRYERS,
 HOWEVER WITH THE LAYOUT AS SHOWN, THE
 DRYER WOULD NOT FIT IN THESE LOCATIONS??
  
 19)NOTE: PLEASE SEE 3RD FLR UNITS WHICH
 SHOW LIGHTING BEING CIRCUITED TO THE
 DINING RM / SMALL APPLIANCE CIRCUIT.
 PLEASE SEE 210.52B1 WHICH ONLY PERMITS
 THE RECEPTS WITH SOME EXCEPTIONS,
 HOWEVER LTS AS SHOWN MAY NOT BE ON THIS
 CIRCUIT. PLEASE ADJUST.
  
 20)NOTE: PLEASE SEE TOP FLR UNIT, WHICH
 DOES NOT SEEM TO SHOW A FIXTURE AT THE
 END OF THE SW LEG IN WHAT APPEARS TO BE
 A BEDRM.
 (MISPRINT).
  
 21)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED FORALL BUT
 HOUSE MAIN DISCONNECT.
  
 22)NOTE: PLEASE VERIFY THE CONNECTION
 POINT AS NOTED FOR GROUNDING ELECTRODE
 CONDUCTOR TO THE REBAR/FOOTER STEEL.
 IT IS UNCLEAR WHAT "THREE SETS OF WRAP
 TO BOND"? THIS METHOD IS UNLCEAR AND NOT
 KNOWN.
 PLEASE PROVIDE THE PERMITTED CONNECTION
 AS SET-FORTH IN THE NEC. 250.50 OR
 PROVIDE FUTHER DETAIL FOR THIS.
 ABOVE IS NOTED AS ALL CONNECTIONS BEING
 EXOTHERMIC, IS THIS FOR THIS LOCAITON
 ALSO?
  
 23)NOTE: PLEASE SEE PANEL "P" WHICH
 SHOWS THE LOAD FOR GEN LT AND RECEPTS,
 HOWEVER THEER SEEMS TO BE SOME SORT OF
 NUMERICAL NOTE ADDED TO THE CIRCUITS 2
 AND 4?
 MISPRINT? CLARIFY.
  
 24)NOTE: PLEASE SEE "CLUBHOUSE" PERMIT
 #05091714 FOR REVIEW.
  
 25)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL SD'S TO BE INSTALLED PER 2002
 NFPA-72 11.8.3.5
  
 ** PLEASE SEE ONE SET OF PLANS HAS MUCH
 OF THE ABOVE REDLINED FOR AREAS OF
 COMMENTS. THIS MAY HELP IN AREAS AS
 NOTED. (RECEPTS ETC)
  
 ** PLEASE KNOW, A RESPONSE LETTER WITH
 RESPECT TO COMMENTS AND WHAT ACTIONS
 WERE TAKEN WOULD GREATLY HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS.
 PLEASE KEEP IN MIND TO CLOUD/TRIANGLE
 ANY REVISED LOCATIONS ON PLANS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
2005-12-24 00:00:00IN ELEC FOR REVIEW