Plan Review Notes
Plan Review Notes For Permit 05091708
Permit Number 05091708
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-11 00:00:00IN ELEC
 ************ UNSAT 2ND REVIEW*********
  
  
 ** IT IS KNOWN THAT PLANS ARE UNDER THE
 2001 FBC, AS THE ELECTRICLA REVIEW WAS
 DONE UNDER THE 2001FBC AND OTHER ADOPTED
 CODES UNDER THE 2001 FBC.
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS FOR
 ITEMS ON PLANS.
  
 ************************************
 IMPORTANT
 PLEASE SEE BUILDING REVIEW COMMENTS AND
 PLEASE KNOW, IT WAS CONFIRMED BY THE
 ASST BUILDING OFFICAL THAT THIS JOB WILL
 REQUIRE A MIN OF A RESIDENT INPSECTOR.
 IN THIS CASE THREE SETS OF ALL PLANS
 UNDER EACH PERMIT WILL BE REQUIRED ONCE
 ALL IS READY TO BE ISSUED. IF THERE ARE
 NAY QUESTIONS, PLEASE CONTACT MR. ROBERT
 BROWN ASST BUILDING OFFICAL/LICENSE AND
 PEMRITS MANAGER.
 ***********************************
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTE(S) ARE ADDED BELOW.
  
 DIXIE MEWS / AQUA TERRACE
  
 1)NOTE: NOTE#1 NO, PLEASE SEE NOTE ALL
 SHEET COMPLY. PLEASE SEE CIVILS WHICH
 CONTAIN A RAISED SEAL OVER A
 PHOTO-COPIED SIGNATURE BY THE ENGINEER.
 PLEASE SEE THIS IS NOT PERMITTED AND
 SHALL BE SIGNED WITH AN ORIGINAL
 SIGNATURE AND DATE. PLANS MAY BE
 RETAINED.
 PLEASE SEE LANDSCAPE PLANS WHICH ARE
 SIGNED WITH WHAT APPEARS TO BE A CRAYON?
 PLEASE BE SURE THIS IS SIGNED IN INK.
 PLEASE SEE MEP PLANS APPEAR TO BE SIGNED
 WITH WHAT APPEARS TO BE "INITIALS"?
 PLEASE SEE FS 471.025 WHICH REQUIRES A
 SIGNATURE. THIS SHOULD BE THE DESIGNER'S
 LEGAL SIGNATURE. IF THIS IS INDEED THE
 "LEGAL SIGNATURE" OF ENGINEER, PLEASE
 PROVIDE A SIGNED, DATED, SEALED LETTER
 FOR ATTESTING TO THIS AS THE LEGAL
 SIGNATURE. THIS LETTER MUST ALSO BE
 NOTORIZED PER FS 117.05
 THIS LTR WILL THEN BE PLACED IN OUR
 SIGNATURE FILE FOR ANY FUTURE REFERENCE.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE SIGNED, DATED AND
 SEALED PLANS BY ARCHITECT AND
 ENGINEER(S) OF RECORD. FS 481.221 AND
 471.025.
 PLEASE SEE PLANS CONTAIN SOME SORT OF
 "CORPORATE SEAL' WHICH IS NOT
 ACCEPTABLE.
 PLEASE KNOW THIS IS REQUIRED OF ALL
 SHEETS AND FOR ALL TRADE REVIEWS WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING
 FIRM LICENSE NUMBER IN THE TITLE BLOCKS
 FOR THE ARCHITECTURAL FIRM, LANDSCAPE
 ARCH FIRM. PLEASE ALSO SEE THE "A"
 SHEETS SHALL ALSO INDICATE THE
 ARCHITECT'S PRINTED NAME. PLEASE SEE
 THIS WAS REQUESTED BY MORE THAN ONE
 REVIEWER ON PREVIOUS REVIEW AND THE
 RESPONSE LTR MENTIONS "FIRM NAME ADDED".
 PLEASE SEE THIS COMMENT WAS FOR ALL
 REQUIRED INFORMATION.
 PLEASE KNOW, THIS INFORMATION IS
 REQUIRED ON ALL TITLE BLOCKS, ALL SHEETS
 AND FOR ALL TRADES.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE AND INCLUDE ALL
 INFORMATION ON SAID TITLE BLOCKS FOR
 ARCHITECTUAL AND ENGINEERING FIRMS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODES
 61G1-16.004 (ARCH) AND 61G15-23.002
 (ENG).
 PLEASE KNOW THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES.
  
 3)NOTE: OK
  
 4)NOTE: NOTE #4 OK, DOORS REMOVED TO
 MEET 110.26, PLEASE SEE BUILDING REVIEW
 FOR ANY QUESTION FOR EGRESS.
 PLEASE KNOW, OTHERWISE THIS COMMENT WAS
 ADDRESSED.
  
 **PREVIOUS NOTE **
 PLEASE VERIFY CLEARENCES FOR
 ELECTRICAL SERVICE PER 110.26,
 APPEARS TO SHOW DOORS WHICH WILL SLIDE
 OPEN ON EACH SIDE, HOWEVER THIS WILL
 ALWAYS CREATE A COMMON POINT IN THE
 CENTER WHICH WOULD NOT MEET CODE.
 PLEASE PROVIDE AN ELEVATION AS HEIGHT
 AND WIDTH IS TO BE VERIFIED.
 PLEASE ALSO VERIFY IT APPEARS THIS
 ROOM/AREA IS ALSO THE GRESS FROM COMMON
 STAIR TOWER AND LOBBY AREA?
 PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE
 SEPARATION AS STAIRS EXIT INTO THIS AREA
 AND NO DOORS ARE SHOWN WHICH MAY ALLOW
 EXITING BACK INTO COMMON LOBBY AREA
 PLEASE SEE THIS IS SHOWING SWITCHING FOR
 LTS?
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE CIRCUIT SHOWN.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE THAT THE
 DEDICATED CIRCUITS PER 620.23,620.24
 SHALL NOT FEED ANY OTHER ITEMS. PLEASE
 SEE THE RECEPT IN ELEV RM, CAN NOT BE ON
 THE SAME CIRCUIT WITH PIT RECEPT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE HOUSE CIRCUIT SHOWN
 FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN
 FEEDING OTHER AREAS. PLEASE SEE 620.23
 WHICH REQUIRES THE BRANCH CIRCUIT FOR
 LTS AND RECEPTS TO BE DEDICATED.
 PLEASE ADJUST.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE SOME
 MENTION OF FC'S ARE NOTED ON PLANS,
 HOWEVER COMPLETE PHOTO-METRICS ARE
 NEEDED.
 PLEASE SUBMIT.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE PHOTOMETRICS FOR
 COMMON AREAS FOR EGRESS LIGHTING. PLEASE
 SEE THIS WOULD INCLUDE LOBBY AREAS,
 STAIR TOWERS, SHOW ALL FT CANDLES TO THE
 EXIT/PUBLIC RIGHT OF WAY.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES 10 FT CANDLES UNDER
 NORMAL POWERE AND A MIN OF 1FT CANDLE
 UNDER EM POWER.
 PLEASE ALSO SEE FURTHER COMMENTS WIHT
 RESPECT TO FIXTURES.
  
 7)NOTE: OK
  
 8)NOTE: OK.
  
 9)NOTE: NOTE #9 OK, HOWEVER SEE NEW
 NOTES FOR ADDED CONDUCTORS.
  
 ** PREVIOUS NOTE**
 PLEASE SHOW THE CONDUCTORS FROM
 HOUSE GUTTER TO EACH DISCONNECT.
 215.5
  
 10)NOTE: NOTE #10, THIS HAS NOT YET BEEN
 CONFIRMED. PLEASE SEE PLANS AND
 PAPERWORK NOW MENTION BUILDING SHALL
 CONTAIN NEW "CONDO UNITS" AS SINGLE
 FANILY RESIDENCES.
 PLEASE SEE THE SD'S IN THE RES CONDO
 UNITS MAY BE REQUIRED TO BE 120V WIRED
 INLINE AND WITH ARC FAULT PROTECTION PER
 210.12B
 CONTACT TO THE FIRE MARSHAL'S OFFICE AND
 CHIEF CARSILLO WILL BE MADE.
 IT SEEMS IF THESE ARE NOW SFR CONDO'S,
 TRIPPING OF THE SD'S IN EACH UNIT UPON
 SOME COOKING PRACTICES ETC WOULD CREATE
 TRIPPING OF THE ENTIRE BUILDINGS FIRE
 ALARM SYSTEM??
  
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY WITH THE FIRE
 MARSHAL'S OFFICE IF INDEED THE UNIT SD'S
 WILL BE TIED INTO BASE BLDG PROTECTION
 SYSTEM.
 PLEASE KNOW, IF THESE ARE 120V WIRED
 INLINE IN UNITS, THEN CIRCUITING WILL BE
 REQUIRED ALONG WITH ARC FAULT
 PROTECTION.
 215.5,210.12
 THIS WOULD ALSO BE AFFECTED BY THE
 "TOWNHOUSE" DECLARATION.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE: NOTE #17 NO, ALMOST ALL WERE
 DONE HOWEVER PLEASE SEE WALL SPACE 2' OR
 MORE EVEN BEHIND DOORS WILL BE REQUIRED
 TO HAVE A RECEPT. PLEASE SEE TWO
 REDLINED IN PH UNITS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.52 FOR RECEPTS
 MISSING FOR 2' OR MORE OF WALL SPACE.
 PLEASE SEE MOST IF THESE LOCATIONS ARE
 REDLINED ON PLANS. (SEE MOSTLY 3RD FLR.
  
 18)NOTE: OK.
  
 19)NOTE: OK, HOWEVER SEE NEW NOTES FOR
 DINGIN CIRCUITS ADDED.
  
 20)NOTE: OK.
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: NOTE #25 NO, COULD NOT FIND?
 RESPONSE MENTIONS THIS WAS ADDED?
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON PLANS FOR
 ALL SD'S TO BE INSTALLED PER 2002
 NFPA-72 11.8.3.5
  
 26)NOTE: NOTE #26 NO, AND NO RESPONSE
 WAS GIVEN FOR THE NOTE.
 THIS SHOULD BE ADDED TO NOTES ON E-10
  
 **PREIVOUS NOTE **
 PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
 *********** NEW NOTES ***********
  
 27) NOTE: PLEASE SEE DINING RM CIRCUITS
 AND THE LIKE SHALL BE SHOWN WITH THE MIN
 VA FIGURED FOR THE CIRCUIT AT 1.5VA.
 PLEASE SEE 210.52B1,210.11C1, 220.16
  
 28) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE PRINTED ON ELECTRICAL PLANS.
 NFPA-101 2003,NFPA-72 2002, NFPA-70
 2002.
  
 29) NOTE: PLEASE SEE RISER IS NOW
 SHOWING "EQUIPMENT GROUNDING CONDUCTORS"
 FOR SEC'S FROM GUTTER TO MAINS FOR
 HOUSE.
 PLEASE SEE 250.6,250.24B , THESE ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 30) NOTE: PLEASE SEE WHAT APPEARS TO BE
 A MISPRINT FOR THE RISER NOTE #5,
 MENTIONS "MLB" , SHOULD THIS BE "MCB"?
  
 31) NOTE: PLEASE SEE CIRCUITS FOR GEN
 LTS AND RECEPTS SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THESE CIRCUITS
 ARE FEEDING. IE: MASTER BEDRM RECEPTS.
 BATH #2 LTS, KITCHEN LTS ETC.
 408.4
  
 32) NOTE: PLEASE KNOW, AS PLANS WERE
 INDEED SUBMITTED FOR PERMIT, PLEASE SEE
 COPY OF FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS THREE OR MORE TIMES.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 *** IMPORTANT**
  
 WHEN RESUBMITTING PLANS, PLEASE BE SURE
 TO SUBMIT ONE COPY OF THE OLD PLANS FOR
 REFERENCE.
  
 ** PLEASE SEE ONE SET OF PLANS HAS MUCH
 OF THE ABOVE REDLINED FOR AREAS OF
 COMMENTS. THIS MAY HELP IN AREAS AS
 NOTED. (RECEPTS ETC)
  
 ** PLEASE KNOW, A RESPONSE LETTER WITH
 RESPECT TO COMMENTS AND WHAT ACTIONS
 WERE TAKEN WOULD GREATLY HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS.
 PLEASE KEEP IN MIND TO CLOUD/TRIANGLE
 ANY REVISED LOCATIONS ON PLANS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]