Plan Review Notes
Plan Review Notes For Permit 05091703
Permit Number 05091703
Review Stop M
Sequence Number 2
Notes
Date Text
2006-07-05 00:00:00DENIED:2001 FBC/BUILDING #4
 RESPONSE TO COMMENTS DATED 1/13/06
  
 COMMENT #1 - OK
 COMMENT #2 - OK
 COMMENT #3 - OK
 COMMENT #4 - OK PLEASE CLARIFY PLAN
 SHEET M-8 EXHAUST DUCT ROOF CAP DETAIL.
 WILL EACH TOILET EXHAUST TERMINATE TO
 THE OUTDOORS OR WILL THIS BE A
 'SUB-DUCT' METHOD?
 COMMENT #5 - OK
 COMMENT #6 - OK
 COMMENT #7 - PLEASE DNOTE, THE 2001 FMC
 DOES NOT GIVE THE OPTION FOR THE
 INSTALLATION OF BOOSTER FANS ON THE
 DRYER EXHAUST.THIS MUST BE SUBMITTED
 TO THE BUILDING OFFICAL UNDER "ALTERNATE
 MATERIALS & METHODS" 2001 AMENDMENTS TO
 THE 2001 FBC 103.7.1.PLEASE PROVIDE
 SUBMITTAL FOR THE BOOSTER FAN.NOTE #3
 ON M-3 INDICATES THE BOOSTER FAN IS
 "MANUFACTURER'S RECOMMENDED" UL LISTED
 BOOSTER FAN.PLEASE ALSO PROVIDE A
 LETTER FROM AN ENGINEER EMPLOYED BY THE
 MANUFACTURER GIVING THE MANUFACTURER'S
 APPROVAL FOR THIS INSTALLATION.
 COMMENT #8 - OK
 COMMENT #9- PLEASE NOTE, SHAFT
 ENCLOSING THE REFRIGERANT LINES SHALL BE
 VENTED IN ACCORDANCE WITH ASHRAE 15-1992
 SECTUIB 11.12.3 (B).
 COMMENT #10 - OK
 COMMENT #11 - AHU-L DUCT SHALL BE IN A
 RATED SHAFT IN ACCORDANCE WITH 2001 FMC
 607.4.
 COMMENT #12 - OK
 COMMENT #13 - RESPONSE INDICATES PRODUCT
 APPROVAL FOR THE CONDENSING UNIT STANDS
 IS ATTACHED TO THE PLANS.PLEASE NOTE,
 PRODUCT APPROVAL IS NOT ATTACHED TO
 PERMIT APPLICATION OR PLAN.PLEASE
 PROVIDE FLORIDA STATE PRODUCT APPROVAL.
 COMMENT #14 - OK
 COMMENT #15 - OK
 COMMENT #16 - OK
 COMMENT #17 - OK
 COMMENT #18 - RESPONSE INDICATES FLOAT
 SWITCH FOR OVERFLOW PROTECTION.PLEASE
 INDICATE LOCATION OF THE FLOAT SWITCH.
 PLEASE NOTE, FLOAT SWITCH IS NOT TO BE
 INSTALLED IN THE PRIMARY DRAIN PAN.IT
 SHALL BE INSTALLED IN THE OVERFLOW OR
 SECONDARY DRAIN SHOULD THIS UNIT BE A
 BOTTOM RETURN. SHOULD THE RETURN BE
 LOCATED IN THE SIDE AN AUXILIARY DRAIN
 PAN WILL BE REQUIRED.
  
 ****************NEW COMMENTS************
 19. PLAN SHEET M-3 NOTE 2 INDICATES
 RETURN AIR THROUGH LOUVERED DOOR AT THE
 AHU CLOSET.PLEASE NOTE, LOUVERED DOOR
 & FRAME SHALL BE NON-COMBUSTIBLE AS
 REQUIRED PER 2001 FMC 602.2.1.
  
 20. PLAN SHEET M-5 SHOWS REFRIGERANT
 LINES THROUGH THE STAIRWELL.PER 2001
 FBC 1006.1.3.1 THIS IS PROHIBITED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATT KRAUSS AT (561)805-6719.