2006-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS 1 THRU 7 (CIVIL) SHEETS, THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED
 ON THE TITLE BLOCK OF EACH SHEET. FAC
 61G15-23.003 & FS 471.025.
 2. SHT 1 OF 7 PROPOSED CLUBHOUSE SHOWS
 NO SANT. OR WATER SERVICE. PLEASE
 CLARIFY. SECTION 104.2.1.
 3. SHT 1 & 2 OF 7 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE OF EACH
 BUILDING. SECTION 608.13.2.
 4. SHT SP-1, SP-2, A1 THRU A.28
 ARCHITECTS BUSINESS NUMBER IS REQUIRED
 IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219.
 5. SHT A-7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SF OF EACH DRAINED AREA, WITH 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND AREA OFF ROOFS THAT DRAIN
 ONTO THE ROOF AREAS FROM ABOVE IN
 CALCULATIONS. SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS/SCUPPERS. INDICATE
 THE SF OF STAIR ROOF, AND SHOW THE SIZE
 OF THE GUTTERS, SIZE OF DOWNSPOUTS,
 SLOPE OF GUTTERS AND INDICATE HIGH POINT
 OF GUTTERS. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 6. SHT A.18 LAVS IN THE POWDER ROOMS OF
 THE TOWNHOUSES SHALL BE COVERED PER FHA
 DESIGN MANUAL PAGES 7, 7.33, & 7.35
 EXCEPTION. LAV SHALL BE CENTERED ON THE
 48" LENGTH OF THE PARALLEL CLEAR FLOOR
 SPACE, OR BE A FRONTAL APPROACH. PAGE
 7.47. LAVS SHALL BE 34" TO RIM PER PAGE
 7.52. (SEE DETAIL #2).
 7. SHT A.18 FIRST DETAIL #3, SHOWER
 CLEAR FLOOR SPACE SHALL BE PARALLEL TO
 THE FIXTURE AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56. LAV PARALLEL CLEAR
 FLOOR SPACE SHALL BE CENTERED ON THE LAV
 A MINIMUM OF 2' OFF THE WALL. INDICATE
 MEASUREMENT FROM WALL TO CENTER OF LAV
 FOR ALL DETAILS.
 8. SHT A.18 DETAIL #4, A 60" DIAMETER
 TURNING CIRCLE IS REQUIRED IN A "U"
 SHAPED KITCHEN THAT HAS A SINK, RANGE,
 OR COOKTOP AT ITS BASE. THIS IS IN
 ADDITION TO THE CLEAR FLOOR SPACE. PAGE
 7.9.
 9. SHT A.19 ALL BATHROOM DETAILS, SHOW
 HEIGHT OF LAVS. ALL W/C'S TO BE 18" OFF
 WALL TO CENTER OF FIXTURE & MEASUREMENTS
 FOR ALL W/C OPENINGS TO SHOWN ON PLANS.
 MINIMUM 33" REQUIRED. SEE PAGES 7.43,
 7.44, 7.45, & 7.46.
 10. ALL E,M & P SHEETS. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE
 NUMBER ON EACH SHEET. FAC
 61G15-23.002(2) & FAC 471.025.
 11. SHTS P-3 & P-4 SHOWS 4" UP TO THE
 3RD FLOOR FOR THE SANT. RISER. P-5 & P-6
 SHOW 3" ON ALL. PLEASE CORRELATE SECTION
 104.2.1.
 12. SHT P-7 SHOW 3" RWLS ROOF DRAINS
 ISOMETRIC AS "3" RWL BELOW SLAB" PLEASE
 CLARIFY. SECTION 104.2.1.
 13. SHT P-7 SHOW THE LOCATION OF ALL
 SECONDARY ROOF DRAINS/SCUPPERS. SHOW THE
 SIZE OF EACH DRAIN OR THE HEIGHT & WIDTH
 OF EACH SCUPPER, PIPING WITH SIZING,
 MEASUREMENT OFF THE ROOF TO THE FLOW
 LINE ETC. SECTIONS 104.2.1, 1106, & 1107
 14. SHT P-8 SANT. RISER DIAGRAM
 ISOMETRIC DOES NOT REFLECT THE FLOOR
 PLANS. THE RISER NUMBERS ARE OPPOSITE OF
 THE FLOOR PLANS. THE LAYOUTS OF SOME
 UNITS ON THE 1ST FLOOR DO NOT REFLECT
 THE FLOOR PLAN. THE SECOND FLOOR RISER
 DOES NOT REFLECT THE FLOOR PLAN AS THEY
 ARE OPPOSITE OF THE FLOOR PLAN ON MOST
 RISERS, AND SOME RISERS ARE MISSING
 FIXTURES & RISERS. 3RD FLOOR RISERS ARE
 OPPOSITE OF FLOOR PLAN. CORRELATE THE
 RISER DIAGRAMS WITH THE FLOOR PLANS,
 CHECK ALL PIPE SIZES WITH FLOOR PLANS.
 INDICATE DFUS AS THEY ACCUMULATE IN THE
 SYSTEM.SECTION 104.2.1 AND TABLE
 710.1(1).
 15. SHTS P-9 & P-10 WATER RISER DIAGRAM
 ISOMETRIC DOES NOT REFLECT THE FLOOR
 PLAN. RISER SHOWS 1" COLD WATER SERVICE
 UP TO PENTHOUSE LEVEL, BUT FLOOR PLAN
 SHOWS 1-1/2" COLD WATER SERVICE UP TO
 PENTHOUSE LEVEL ON SHTS P-1 THRU P-4.
 PLEASE CORRELATE FLOOR PLANS AND RISER
 DIAGRAMS.
 16. SHTS P-9 & P-10 WATER RISER DIAGRAM
 ISOMETRICS, AIR CHAMBERS ARE NOT
 APPROVED. AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9, (W/M, ICE
 MAKER, DISHWASHER), SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 17. SHT P-9 SHOWN THE WATER HEATERS IN
 AN EMERGENCY PAN, WHERE AS P-10 SHOWS NO
 PAN. W/H'S ON THE FIRST FLOOR ARE DO NOT
 REQUIRE A HEATER PAN UNLESS THEY ARE ON
 A SHELF. PLEASE CLARIFY. SECTIONS
 104.2.1. & 504.8.
 18. SUBMIT A WATER HEATER DETAIL SHOWING
 ALL PIPE SIZES, VALVES, THERMAL
 EXPANSION CONTROL, P/T VALVE SHOWING
 PIPING AND INDICATING THE TERMINATION
 POINT. SECTIONS 104.2.1, 504.7.1, AND
 607.3.2.
 19. SHT P-11 PLUMBING GENERAL NOTES:
 E-22 AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM REFERENCE. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  