Plan Review Notes
Plan Review Notes For Permit 05091703
Permit Number 05091703
Review Stop M
Sequence Number 1
Notes
Date Text
2006-01-13 00:00:00DENIED:
 PLANS REVIEWED UNDER THE 2004 FBC.
 PLANS DO NOT INDICATE WHICH CODE THE
 BUIDLINGS ARE DESIGNED.
  
 1.PROVIDE BUILDING TYPE, INDICATE
 PROTECTED OR UNPROTECTED.
  
 2.PLAN SHEET A2 SEPARATION BETWEEN THE
 GARAGE AND THE RESIDENCE IS INDICATED AS
 A 2 HOUR SEPARATION ACCORDING TO THE
 WALL TYPE LISTED ON PLAN SHEET A-26.
 MECHANICAL PLAN M1 INDICATES DUCTWORK
 PENETRATING RATED WALL WITHOUT
 PROTECTION.PLEASE INDICATE ON THE
 PLANS COMPLIANCE WITH ALL THE
 REQUIREMENTS LISTED UNDER 2004 FMC
 607.5.3 EXCEPTIONS 1 AND 2.
  
 3.PLANS SHEET M-1 INDICATES BATHROOM
 EXHAUST PENETRATING THROUGH 2ND & 3RD
 FLOORS TO THE ROOF.PLEASE INDICATE
 PROTECTION THROUGH RATED FLOOR.
  
 4.PLAN SHEET M-3 & M-5 INDICATES
 REFRIGERANT LINES & EXHAUST DUCT IN A
 "CHASE".PLEASE CLARIFY IN THE "CHASE"
 IS RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.5.5.1.PLEASE NOTE, FIRE DAMPERS &
 ACCESS DOORS ARE REQUIRED TO BE
 INDENTIFFIED ON PLANS PER 2004 FMC
 607.8.
  
 5.PLEASE NOTE, EXHAUST DUCT SHALL
 COMPLY WITH 2004 FMC 501.4.
  
 6.PLAN SHEET M-1 INDICATES "MATCH
 LINE" M-2.M-2, M-4 & M-6 WERE NOT
 SUBMITTED FOR
 REVIEW.
  
 7.PLAN SHEET M-3, DRYER EXHAUST
 APPEARS TO EXCEED THE 25FT REQUIREMENT
 IN 504.6 OF THE 2004 FMC.
  
 8.PLAN SHEET M-3 & M-5 INDICATES
 REFRIGERANT LINES & EXHAUST DUCT IN A
 "CHASE".PLEASE CLARIFY IF THE "CHASE"
 IS RATED.SHOW COMPLIANCE WITH 2004 FMC
 607.5.5.1.PLEASE NOTE, FIRE DAMPERS &
 ACCESS DOORS ARE REQUIRED TO BE
 IDENTIFIED ON PLANS PER 2004 FMC 607.8.
  
 9.PLEASE PROVIDE A DETAIL OF THE
 TERMINATION OF REFRIGERANT LINES &
 EXHAUST DUCT LOCATED ON THE ROOF IN THE
 HVAC EQUIPMENT ROOM.
  
 10. PER 2004 FMC 501.2, EXHAUST AIR
 SHALL BE DISCHARGED TO THE OUTDOORS AT A
 POINT WHERE IT WILL NOT CREATE A
 NUISANCE OR CANNOT BE READLY DRAWN IN BY
 THE VENTILATING SYSTEM.
  
 11. PLAN SHEET M-3 AHU-L DUCT PENETRATES
 FLOOR AND CEILING PLEASE SHOW COMPLIANCE
 WITH 2004 FMC 607.6.
  
 12. PLEASE CLARIFY THE HVAC EQUIPMENT
 ROOMS LOCATED ON THE ROOF.THE
 CONDENSING UNITS ARE LOCATED IN THE
 EQUIPMENT ROOMS.WILL THIS BE ENCLOSED?
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 FOR THE CONDENSERS INDICATING THEY ARE
 PERMITTED TO BE INSTALLED IN AN ENCLOSED
 AREA WHICH ESSENTIALLY IS INDOORS.
  
 13. PLEASE PROVIDE DETAIL OF THE
 MOUNTING OF THE CONDENSING UNITS.
  
 14. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 403.3.
  
 15. PLAN SHEET M-3 RETURN AIR FROM THE
 BEDROOM AREAS ARE NOT SIZED PROPERLY.
 RETURN AIR "JUMPERS" SHALL COMPLY WITH
 2004 FMC 601.4 EXCEPTION #1.
  
 16. PLAN SHEET M-3 THE MASTER SUITE
 SHALL BE SIZED IN ACCORDANCE WITH 2004
 FMC 601.4 EXCEPTION 1 AND 3.PLEASE
 REVISE.
  
 17. PLAN SHEET M-5 RETURN AIR FROM THE
 BOTH BEDROOMS SHALL COMPLY WITH 2004 FMC
 601.4 EXCEPTION 1 AND 3.
  
 18. AUH DETAIL DOES NOT INDICATE
 OVERFLOW PROTECTION PER 2004 FMC
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.