2005-10-14 00:00:00FAILED:
  
 1. CIVIL PLANS MUST BE REVIEWED AND
 APPROVED FOR ALL THE CONNECTIONS TO THE
 CITY' SERVICES, 494-1085 ATT; MANNY
 GONZALEZ.
 2. PLEASE SUBMIT STORM WATER
 CALCULATIONS FOR OUR REVIEW AND
 APPROVAL.NOTE THAT SITE MUST BE
 DESIGNED PER CITY' REQUIREMENTS AND
 CRITERIA.CALC. MUST BE SIGNED AND
 SEALED BY THE C.E.O.R
 3. POLLUTION PREVENTION PLANS MUST BE
 INCLUDED IN CIVIL PLANS, SILT FENCE,
 TURBIDITY BARRIER, ECT..
 4.PLEASE SUBMIT A COPY OF THE SFWMD
 PERMIT, FOR OUR RECORD.
 5. PLEASE REFER TO ARCHITECTURAL PLANS
 FOR DUMPSTER ENCLOSURE'S DIMENSIONS.
 NOTE THAT, THEY MUST BE SIZED PER CITY
 REQUIREMENTS IF CITY PICK-UP.
 6. STREETSCAPING AND SIDEWALKS, ETC.
 MUST BE COORDINATED WITH LATEST FDOT
 PLANS FOR RECONSTRUCTION OF DIXIE AND
 GREGORY RD.
 7. CIVIL PLANS MUST BE INCLUDED IN ALL
 THREE SETS, ONLY ONE SET HAS THE CIVIL.
 8. NOTE THAT CITY'S STANDARDS AND
 DETAILS CAN BE OBTAINED FROM PUBLIC
 UTILITIES AND ENGINEERING , 494-1085.
 9.FIRE HYD. MUST BE PROVIDED
 THROUGHOUT THE PROPOSED SITE.
 10. DOMESTIC WATER SYS. AS PROPOSED;
 METERS AND DDCV LOCATIONS ECT. MUST BE
 VERIFIED WITH PUBLIC UTILITIES AND
 ENGINEERING.
 11. ALL VERTICAL CLEARANCES FOR
 UNDERGROUND UTILITIES MUST BE SHOWN.
 12. A SEPARATE R.O.W PERMIT FOR ALL THE
 WORKS WITHIN PUBLIC R.O.W IS REQUIRED;
 CONTACT PUBLIC UTILITIES AND ENGINEERING
 AT MIN. 48HR PRIOR TO ANY WORK BEGINS,
 494-1086, WINDEL PALMER. NOTE TO G.C
 13. ACCESS RAMP PER INDEX 304 FDOT TO
 THE SITE MUST BE PROVIDED.
 14. DETAILS FOR THE STOP AND HANDICAP
 SIGNS SHOULD BE INCLUDED IN CIVIL, AND
 NOTE THAT PARKING STALLS MUST BE PAINTED
 WITH DOUBLE 4" WIDE, DETAILS SHOULD BE
 SHOWN.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI