2006-01-13 00:00:00 | DENIED: |
| PLANS REVIEWED UNDER THE 2004 FBC. |
| PLANS DO NOT INDICATE WHICH CODE THE |
| BUIDLINGS ARE DESIGNED. |
| |
| 1.PROVIDE BUILDING TYPE, INDICATE |
| PROTECTED OR UNPROTECTED. |
| |
| 2.PLAN SHEET A2 SEPARATION BETWEEN THE |
| GARAGE AND THE RESIDENCE IS INDICATED AS |
| A 2 HOUR SEPARATION ACCORDING TO THE |
| WALL TYPE LISTED ON PLAN SHEET A-26. |
| MECHANICAL PLAN M1 INDICATES DUCTWORK |
| PENETRATING RATED WALL WITHOUT |
| PROTECTION.PLEASE INDICATE ON THE |
| PLANS COMPLIANCE WITH ALL THE |
| REQUIREMENTS LISTED UNDER 2004 FMC |
| 607.5.3 EXCEPTIONS 1 AND 2. |
| |
| 3.PLANS SHEET M-1 INDICATES BATHROOM |
| EXHAUST PENETRATING THROUGH 2ND & 3RD |
| FLOORS TO THE ROOF.PLEASE INDICATE |
| PROTECTION THROUGH RATED FLOOR. |
| |
| 4.PLAN SHEET M-3 & M-5 INDICATES |
| REFRIGERANT LINES & EXHAUST DUCT IN A |
| "CHASE".PLEASE CLARIFY IN THE "CHASE" |
| IS RATED.SHOW COMPLIANCE WITH 2004 FMC |
| 607.5.5.1.PLEASE NOTE, FIRE DAMPERS & |
| ACCESS DOORS ARE REQUIRED TO BE |
| INDENTIFFIED ON PLANS PER 2004 FMC |
| 607.8. |
| |
| 5.PLEASE NOTE, EXHAUST DUCT SHALL |
| COMPLY WITH 2004 FMC 501.4. |
| |
| 6.PLAN SHEET M-1 INDICATES "MATCH |
| LINE" M-2.M-2, M-4 & M-6 WERE NOT |
| SUBMITTED FOR |
| REVIEW. |
| |
| 7.PLAN SHEET M-3, DRYER EXHAUST |
| APPEARS TO EXCEED THE 25FT REQUIREMENT |
| IN 504.6 OF THE 2004 FMC. |
| |
| 8.PLAN SHEET M-3 & M-5 INDICATES |
| REFRIGERANT LINES & EXHAUST DUCT IN A |
| "CHASE".PLEASE CLARIFY IF THE "CHASE" |
| IS RATED.SHOW COMPLIANCE WITH 2004 FMC |
| 607.5.5.1.PLEASE NOTE, FIRE DAMPERS & |
| ACCESS DOORS ARE REQUIRED TO BE |
| IDENTIFIED ON PLANS PER 2004 FMC 607.8. |
| |
| 9.PLEASE PROVIDE A DETAIL OF THE |
| TERMINATION OF REFRIGERANT LINES & |
| EXHAUST DUCT LOCATED ON THE ROOF IN THE |
| HVAC EQUIPMENT ROOM. |
| |
| 10. PER 2004 FMC 501.2, EXHAUST AIR |
| SHALL BE DISCHARGED TO THE OUTDOORS AT A |
| POINT WHERE IT WILL NOT CREATE A |
| NUISANCE OR CANNOT BE READLY DRAWN IN BY |
| THE VENTILATING SYSTEM. |
| |
| 11. PLAN SHEET M-3 AHU-L DUCT PENETRATES |
| FLOOR AND CEILING PLEASE SHOW COMPLIANCE |
| WITH 2004 FMC 607.6. |
| |
| 12. PLEASE CLARIFY THE HVAC EQUIPMENT |
| ROOMS LOCATED ON THE ROOF.THE |
| CONDENSING UNITS ARE LOCATED IN THE |
| EQUIPMENT ROOMS.WILL THIS BE ENCLOSED? |
| PLEASE PROVIDE MANUFACTURER SUBMITTAL |
| FOR THE CONDENSERS INDICATING THEY ARE |
| PERMITTED TO BE INSTALLED IN AN ENCLOSED |
| AREA WHICH ESSENTIALLY IS INDOORS. |
| |
| 13. PLEASE PROVIDE DETAIL OF THE |
| MOUNTING OF THE CONDENSING UNITS. |
| |
| 14. PLEASE PROVIDE OUTSIDE AIR |
| CALCULATIONS IN ACCORDANCE WITH 2004 FMC |
| 403.3. |
| |
| 15. PLAN SHEET M-3 RETURN AIR FROM THE |
| BEDROOM AREAS ARE NOT SIZED PROPERLY. |
| RETURN AIR "JUMPERS" SHALL COMPLY WITH |
| 2004 FMC 601.4 EXCEPTION #1. |
| |
| 16. PLAN SHEET M-3 THE MASTER SUITE |
| SHALL BE SIZED IN ACCORDANCE WITH 2004 |
| FMC 601.4 EXCEPTION 1 AND 3.PLEASE |
| REVISE. |
| |
| 17. PLAN SHEET M-5 RETURN AIR FROM THE |
| BOTH BEDROOMS SHALL COMPLY WITH 2004 FMC |
| 601.4 EXCEPTION 1 AND 3. |
| |
| 18. AUH DETAIL DOES NOT INDICATE |
| OVERFLOW PROTECTION PER 2004 FMC |
| 307.2.3. |
| |