2005-10-14 00:00:00 | FAILED: |
| |
| 1. CIVIL PLANS MUST BE REVIEWED AND |
| APPROVED FOR ALL THE CONNECTIONS TO THE |
| CITY' SERVICES, 494-1085 ATT; MANNY |
| GONZALEZ. |
| 2. PLEASE SUBMIT STORM WATER |
| CALCULATIONS FOR OUR REVIEW AND |
| APPROVAL.NOTE THAT SITE MUST BE |
| DESIGNED PER CITY' REQUIREMENTS AND |
| CRITERIA.CALC. MUST BE SIGNED AND |
| SEALED BY THE C.E.O.R |
| 3. POLLUTION PREVENTION PLANS MUST BE |
| INCLUDED IN CIVIL PLANS, SILT FENCE, |
| TURBIDITY BARRIER, ECT.. |
| 4.PLEASE SUBMIT A COPY OF THE SFWMD |
| PERMIT, FOR OUR RECORD. |
| 5. PLEASE REFER TO ARCHITECTURAL PLANS |
| FOR DUMPSTER ENCLOSURE'S DIMENSIONS. |
| NOTE THAT, THEY MUST BE SIZED PER CITY |
| REQUIREMENTS IF CITY PICK-UP. |
| 6. STREETSCAPING AND SIDEWALKS, ETC. |
| MUST BE COORDINATED WITH LATEST FDOT |
| PLANS FOR RECONSTRUCTION OF DIXIE AND |
| GREGORY RD. |
| 7. CIVIL PLANS MUST BE INCLUDED IN ALL |
| THREE SETS, ONLY ONE SET HAS THE CIVIL. |
| 8. NOTE THAT CITY'S STANDARDS AND |
| DETAILS CAN BE OBTAINED FROM PUBLIC |
| UTILITIES AND ENGINEERING , 494-1085. |
| 9.FIRE HYD. MUST BE PROVIDED |
| THROUGHOUT THE PROPOSED SITE. |
| 10. DOMESTIC WATER SYS. AS PROPOSED; |
| METERS AND DDCV LOCATIONS ECT. MUST BE |
| VERIFIED WITH PUBLIC UTILITIES AND |
| ENGINEERING. |
| 11. ALL VERTICAL CLEARANCES FOR |
| UNDERGROUND UTILITIES MUST BE SHOWN. |
| 12. A SEPARATE R.O.W PERMIT FOR ALL THE |
| WORKS WITHIN PUBLIC R.O.W IS REQUIRED; |
| CONTACT PUBLIC UTILITIES AND ENGINEERING |
| AT MIN. 48HR PRIOR TO ANY WORK BEGINS, |
| 494-1086, WINDEL PALMER. NOTE TO G.C |
| 13. ACCESS RAMP PER INDEX 304 FDOT TO |
| THE SITE MUST BE PROVIDED. |
| 14. DETAILS FOR THE STOP AND HANDICAP |
| SIGNS SHOULD BE INCLUDED IN CIVIL, AND |
| NOTE THAT PARKING STALLS MUST BE PAINTED |
| WITH DOUBLE 4" WIDE, DETAILS SHOULD BE |
| SHOWN. |
| |
| IF ANY QUESTION PLEASE CONTACT 805-6723 |