2008-02-19 09:49:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 NOTE: THE PLUMBING SUBMITTAL FROM 2/1/08 SHOULD HAVE
 BEEN SUBMITTED AS A PLUMBING REVISION TO THE MASTER
 PERMIT #05091674. ANY FUTURE REVISIONS SHALL BE
 SUBMITTED WITH FEES PAID BEFORE PLAN REVIEW. THE
 FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. ORIGINAL PLUMBING SHEETS P-1 AND P-2 WERE SIGNED
 AND SEALED BY ARCHITECT STEPHAN A. YECKES (AR#7444).
 ANY REVISIONS TO THESE PLUMBING SHEETS SHALL BE BY THE
 DESIGN PROFESSIONAL OF RECORD WITH THE REQUIRED TITLE
 BLOCK INFORMATION. PER CHAPTER 481, FLORIDA
 STATUTES,PART 1.
  
 2. SHEET BUILDING (1) 12 UNITS TOTAL, SANITARY RISER
 DIAGRAM:
  
 A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR
 ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES.
 PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS.
  
 B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE
 CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER
 FBC PLUMBING SECTION *701.1 SCOPE.
  
 3. SHEET BUILDING (2) 17 UNITS TOTAL, SANITARY RISER
 DIAGRAM:
  
 A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR
 ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES.
 PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS.
  
 B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE
 CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER
 FBC PLUMBING SECTION *701.1 SCOPE.
  
 C} THE 3" HORIZONTAL DRY VENT IN LAST UNIT IS NOT
 ALLOWED. PER FBC PLUMBING SECTION *905.3 VENT
 CONNECTION TO DRAINAGE SYSTEM.
  
 4. SHEET BUILDING (3) 3 UNITS, SANITARY RISER
 DIAGRAM:CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS
 FOR ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND
 LAVATORIES. PER FBC PLUMBING SECTION *1002.1 FIXTURE
 TRAPS.
  
 5. SHEET WATER SERVICE 32 UNITS:
  
 A} PLEASE CLEARLY INDICATE THE SIZING TO ALL MAINS AND
 BRANCHES, THE WAY ITS BEING INDICATED IS CONFUSING. PER
 FBC PLUMBING SECTION *601.1 SCOPE.
  
 B} PLEASE CLARIFY IF IT IS THE INTENT TO DELETE ALL
 FULL-OPEN VALVES AND INTERIOR WATER PIPING TO THE
 FIXTURES AS IS APPROVED ON SHEET P-2. PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION *106.1.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]