2008-02-19 09:49:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| REVISION DENIED: |
| |
| NOTE: THE PLUMBING SUBMITTAL FROM 2/1/08 SHOULD HAVE |
| BEEN SUBMITTED AS A PLUMBING REVISION TO THE MASTER |
| PERMIT #05091674. ANY FUTURE REVISIONS SHALL BE |
| SUBMITTED WITH FEES PAID BEFORE PLAN REVIEW. THE |
| FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. ORIGINAL PLUMBING SHEETS P-1 AND P-2 WERE SIGNED |
| AND SEALED BY ARCHITECT STEPHAN A. YECKES (AR#7444). |
| ANY REVISIONS TO THESE PLUMBING SHEETS SHALL BE BY THE |
| DESIGN PROFESSIONAL OF RECORD WITH THE REQUIRED TITLE |
| BLOCK INFORMATION. PER CHAPTER 481, FLORIDA |
| STATUTES,PART 1. |
| |
| 2. SHEET BUILDING (1) 12 UNITS TOTAL, SANITARY RISER |
| DIAGRAM: |
| |
| A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR |
| ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES. |
| PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS. |
| |
| B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE |
| CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER |
| FBC PLUMBING SECTION *701.1 SCOPE. |
| |
| 3. SHEET BUILDING (2) 17 UNITS TOTAL, SANITARY RISER |
| DIAGRAM: |
| |
| A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR |
| ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES. |
| PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS. |
| |
| B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE |
| CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER |
| FBC PLUMBING SECTION *701.1 SCOPE. |
| |
| C} THE 3" HORIZONTAL DRY VENT IN LAST UNIT IS NOT |
| ALLOWED. PER FBC PLUMBING SECTION *905.3 VENT |
| CONNECTION TO DRAINAGE SYSTEM. |
| |
| 4. SHEET BUILDING (3) 3 UNITS, SANITARY RISER |
| DIAGRAM:CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS |
| FOR ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND |
| LAVATORIES. PER FBC PLUMBING SECTION *1002.1 FIXTURE |
| TRAPS. |
| |
| 5. SHEET WATER SERVICE 32 UNITS: |
| |
| A} PLEASE CLEARLY INDICATE THE SIZING TO ALL MAINS AND |
| BRANCHES, THE WAY ITS BEING INDICATED IS CONFUSING. PER |
| FBC PLUMBING SECTION *601.1 SCOPE. |
| |
| B} PLEASE CLARIFY IF IT IS THE INTENT TO DELETE ALL |
| FULL-OPEN VALVES AND INTERIOR WATER PIPING TO THE |
| FIXTURES AS IS APPROVED ON SHEET P-2. PER CITY OF WPB |
| AMENDMENTS TO CHAPTER 1, SECTION *106.1.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |