Date |
Text |
2007-03-17 15:00:15 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEWS**** |
| |
| A. OK |
| 1. OK |
| 2. OK |
| 3. OK |
| |
| 4. SHT P-1 PLUMBING RISER FOR BUILDING 1 |
| DOES NOT REFLECT THE FLOOR PLAN. |
| BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT |
| RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS |
| 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE |
| OPPOSITE SIDE OF THE TOILET ROOM THAN |
| THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW |
| THE LAV STACKS VENTING THE W/C'S. - L/T |
| SHALL NOT DRAIN THROUGH THE WET VENT OF |
| THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF |
| THE BATHROOM GROUP. |
| SECTION 909.1. (SEE RED LINE EXAMPLE ONE |
| SET OF PLANS). |
| ****RESPONSE NOTED, BUT BAYS 9, 10, 13, |
| 17, 20 DO NOT REFLECT THE FLOOR PLANS. |
| THE FIXTURES ARE TURNED TO THE WRONG |
| SIDE OF THE VENT PIPING. SEE FLOOR PLAN. |
| - SHOW ALL PIPE SIZES. |
| ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN |
| CHANGED FOR ALL UNITS. THE 1-1/4" SANITARY TO THE |
| LAUNDRY SINK DOES NOT MEET CODE. TABLE 709.1.-BAYS |
| 3, 7, 11, 15, 19, & 21 THE BRANCH LINES DO NOT REFLECT |
| THE FLOOR PLAN PIPING LAYOUT. BAYS 9 THRU 21 THE PIPING |
| TO THE FIXTURES ARE FACING THE WRONG WAY. - NOT ALL |
| PIPE SIZES ARE SHOWN. SECTION 104.2.1, TABLES 710.1(1) |
| & 710.1(2).THE LAVS IN BAYS 1, 5, 9, 13, 17, & 20 ARE |
| NOT VENTED AS SHOWN AND INDICATES THAT THE TRAP IS |
| UNDERGROUND. SECTIONS 104.2.1 AND 901.2.1.THE FLOOR |
| PLAN ON SHT S-1 SHOWS CLEANOUTS UPSTREAM OF THE W/C'S. |
| THESE ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| CLARIFY. |
| **********RESPONSE NOTED, BUT BAY #3 STILL DOES NOT |
| REFLECT THE FLOOR PLAN, AND NOW BAY #'S 9, 13, 17, & 20 |
| DO NOT REFLECT THE FLOOR PLAN. ALSO THE BUILDING DRAIN |
| DOES NOT REFLECT THE FLOOR PLAN IN THATTHE FLOOR PLAN |
| INDICATES ONE DRAIN FOR EVERY TWO BAYS, WHEREAS THE |
| RISER SHOWS EACH BAY EXITING THE BUILDING SEPARATELY. |
| PLEASE CORRELATE FLOOR PLAN & RISER DIAGRAM. |
| |
| 5. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| BUILDING 2 DOES NOT REFLECT THE FLOOR |
| PLAN. (SEE PREVIOUS COMMENT AND ADJUST |
| RISER TO FLOOR PLAN AND PIPE PER CODE. |
| SECTIONS 106.1.1 & 909.1. |
| ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| SIZES. |
| ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN |
| CHANGED FOR ALL UNITS. ALL BAYS, THE 1-1/4" SANT. TO |
| THE LAUNDRY SINK DOES NOT MEET CODE. ALL BAYS, THE LAV |
| IS NOT VENTED AS SHOWN, AND THE TRAP IS INDICATED AS |
| BEING UNDERGROUND AS SHOWN.SECTIONS 104.2.1, 901.2.1 |
| AND TABLE 709.1. SHT S-2 INDICATES CLEANOUTS UPSTREAM |
| OF THE W/C'S. THE SANT. RISER DIAGRAM DOES NOT REFLECT |
| THIS. PLEASE CLARIFY. |
| **********RESPONSE NOTED, BUT THE RISER DIAGRAM STILL |
| DOES NOT REFLECT THE FLOOR PLAN. ALSO THE BUILDING |
| DRAIN ON THE FLOOR PLAN SHOWS THE BUILDING DRAIN |
| EXITING THE BAYS 2 THRU 18 TO THE EAST SIDE AND THE |
| OTHER BAYS EXITING ON THE WEST SIDE OF THE BUILDING, |
| WHEREAS THE RISER SHOWS ALL UNITS EXITING THE WEST SIDE |
| OF THE BUILDING. PLEASE CORRELATE FLOOR PLAN & RISER |
| DIAGRAM. |
| |
| 6. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| BUILDING 3 DOES NOT REFLECT THE FLOOR |
| PLAN. (SEE COMMENT #4 AND ADJUST RISER |
| TO REFLECT THE FLOOR PLAN, AND PIPE PER |
| CODE. SECTIONS 106.1.1 & 909.1. |
| ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| SIZES. |
| ******RESPONSE NOTED, BUT THE 1-1/4" SANT. TO THE |
| LAUNDRY SINKS DOES NOT MEET CODE. TABLE 709.1. THE LAVS |
| ARE NOT VENTED AS SHOWN AND THE TRAPS ARE UNDERGROUND |
| AS PIPED. SECTION 901.2.1. SHT S-3 SHOWS CLEANOUTS |
| UPSTREAM OF THE W/C'S ON THE FLOOR PLAN BUT THE SANT. |
| RISER DOES NOT REFLECT THIS. PLEASE CLARIFY. |
| *********RESPONSE NOTED, BUT THE BUILDING DRAIN ON THE |
| RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN LAYOUT. |
| |
| 7. SHT P-1 TYPICAL COLD RISER DOES NOT |
| REFLECT THE FLOOR PLANS. SUBMIT A WATER |
| RISER DIAGRAM FOR EACH BUILDING THAT |
| REFLECT THE FLOOR PLAN OF THAT BUILDING. |
| SHOW ALL PIPE SIZES, VALVES, INDICATE |
| BAY NUMBER, INDICATE PIPING MATERIAL. |
| INDICATE IF WATER IS UNDERGROUND OR |
| ABOVE GROUND. - AN RPZV BACKFLOW IS |
| REQUIRED FOR EACH BUILDING. SECTIONS |
| 106.1.1, 606.1, 606.2, 608.13.2. |
| ****RESPONSE NOTED, BUT THE WATER RISER |
| DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| THE FIXTURES ARE LOCATED EAST TO WEST IN |
| THE TOILET ROOM AND THE FIXTURE LAYOUT |
| ON THE RISER IS FROM SOUTH TO NORTH. |
| WATER SERVICE IS NOT AS SHOWN ON THE C-1 |
| SHEET. SEPARATE BACKFLOW REQUIRED FOR |
| EACH BUILDING. SHOW ALL PIPE SIZES. |
| INDICATE PIPING MATERIAL. |
| ******RESPONSE NOTED, BUT NO MENTION OF THE MATERIAL |
| FOR THE WATER PIPING WAS INDICATED. ALL BAYS ALL |
| BUILDINGS SHOW A VALVE ABOVE THE FLOOR DOWNSTREAM OF |
| ALL W/C'S. PLEASE INDICATE WHAT THAT VALVE IS FOR. |
| SECTION 104.2.1. - BLDGS 2 & 3 WATER RISER DIAGRAMS DO |
| NOT REFLECT THE FLOOR PLAN FIXTURE LAYOUT. INDICATE |
| WHATE THE VALVE DOWNSTREAM OF ALL WATER CLOSETS IS FOR. |
| SECTION 104.2.1. |
| **********RESPONSE NOTED, BUT ONLY THE WATER MAIN PIPE |
| SIZE IS INDICATED. PLEASE SHOW ALL PIPE SIZES. AT THE |
| VERY LEAST SHOW A TYPICAL BAY PIPING WILL ALL SIZES |
| INDICATED. |
| |
| 8. OK |
| **************NEW COMMENTS************** |
| |
| 1B. OK |
| 2B. OK |
| 3B. OK |
| |
| **************NEW COMMENT************** |
| |
| 1C. INFORMATIONAL - SEPARATE IRRIGATION PLANS AND |
| PERMIT ARE REQUIRED. SECTION 104.3.1.1. |
| |
| ************NEW COMMENTS************ |
| |
| 1D. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B)AND |
| THE DESIGN PROFESSIONAL. THIS IS GIVEN AS A NOTICE. |
| |
| 2D. PLANS SHALL BE SUBMITTED IN TWO OR MORE SETS OF |
| PLANS. PLEASE INSERT ALL PLUMBING PLANS IN THE SETS OF |
| PLANS WHEN SUBMITTING. SECTION 106.1. |
| |
| 3D. SHT SP-1 DRAWING INDEX DOES NOT INDICATE SHT P-2. |
| PLEASE CORRELATE INDEX AND SHEETS SUBMITTED. SECTION |
| 106.1.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |