Plan Review Notes For Permit 05091674
Permit Number 05091674
Review Stop P
Sequence Number 4
Notes
Date Text
2007-02-08 14:07:47DENIED;
 1. BUILDING # 1
 A) FLAT DRAWINGS ON PAGE S-1 DOES NOT MATCH SANITARY
 RISER DIAGRAM ON PAGE P-1 FOR BAYS3,7,11,15,19, AND
 21.
 B) WATER SEVICE IS NOT LARGE ENOUGH. USE FBC-2004
 PLUMBING APPENDIX E TO HELP SIZE WATER SERVICE TO
 BUILDING.
 C) SUBMIT MANUFACTURE'S CUT SHEET ON VALVE BOX TO BE
 USED. IS IT RATED FOR TRAFFIC?
 D) MINIMUM SERVICE IS 3/4" AND 1/2" TO FIXTURES.
 E) WATER RISER DIAGRAM SHOWS VALVE ABOVE FLOOR, WHAT
 IS THAT USED FOR?
 2. BUILDING # 2;
 A) FLAT DRAWING ON PAGE S-2 DOES NOT MATCH SANITARY
 RISER DIAGRAM ON PAGE P-1 FOR BAYS
 2,4,6,8,10,12,14,16,18, & 31.
 ALSO B THRU ENOTES UNDER BUILDING # 1.
 3.BUILDING # 3
 A) UNITS 22,24, & 26.
 ALSO B THRU E FROM BUILDING # 1.
 4. ADD NOTE TO DRAWINGS, ALL PIPES RUNNING THROUGH OR
 UNDER A FOOTING OR WALL SHALL BE SLEEVED PER SECTION
 305.2,3,4, & 5.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695