2006-10-20 16:45:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 A. OK
 1. OK
 2. OK
 3. OK
  
 4. SHT P-1 PLUMBING RISER FOR BUILDING 1
 DOES NOT REFLECT THE FLOOR PLAN.
 BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT
 RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS
 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE
 OPPOSITE SIDE OF THE TOILET ROOM THAN
 THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW
 THE LAV STACKS VENTING THE W/C'S. - L/T
 SHALL NOT DRAIN THROUGH THE WET VENT OF
 THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF
 THE BATHROOM GROUP.
 SECTION 909.1. (SEE RED LINE EXAMPLE ONE
 SET OF PLANS).
 ****RESPONSE NOTED, BUT BAYS 9, 10, 13,
 17, 20 DO NOT REFLECT THE FLOOR PLANS.
 THE FIXTURES ARE TURNED TO THE WRONG
 SIDE OF THE VENT PIPING. SEE FLOOR PLAN.
 - SHOW ALL PIPE SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. THE 1-1/4" SANITARY TO THE
 LAUNDRY SINK DOES NOT MEET CODE. TABLE 709.1.-BAYS
 3, 7, 11, 15, 19, & 21 THE BRANCH LINES DO NOT REFLECT
 THE FLOOR PLAN PIPING LAYOUT. BAYS 9 THRU 21 THE PIPING
 TO THE FIXTURES ARE FACING THE WRONG WAY. - NOT ALL
 PIPE SIZES ARE SHOWN. SECTION 104.2.1, TABLES 710.1(1)
 & 710.1(2).THE LAVS IN BAYS 1, 5, 9, 13, 17, & 20 ARE
 NOT VENTED AS SHOWN AND INDICATES THAT THE TRAP IS
 UNDERGROUND. SECTIONS 104.2.1 AND 901.2.1.THE FLOOR
 PLAN ON SHT S-1 SHOWS CLEANOUTS UPSTREAM OF THE W/C'S.
 THESE ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CLARIFY.
  
 5. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 2 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE PREVIOUS COMMENT AND ADJUST
 RISER TO FLOOR PLAN AND PIPE PER CODE.
 SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN
 CHANGED FOR ALL UNITS. ALL BAYS, THE 1-1/4" SANT. TO
 THE LAUNDRY SINK DOES NOT MEET CODE. ALL BAYS, THE LAV
 IS NOT VENTED AS SHOWN, AND THE TRAP IS INDICATED AS
 BEING UNDERGROUND AS SHOWN.SECTIONS 104.2.1, 901.2.1
 AND TABLE 709.1. SHT S-2 INDICATES CLEANOUTS UPSTREAM
 OF THE W/C'S. THE SANT. RISER DIAGRAM DOES NOT REFLECT
 THIS. PLEASE CLARIFY.
  
 6. SHT P-1 PLUMBING RISER DIAGRAM FOR
 BUILDING 3 DOES NOT REFLECT THE FLOOR
 PLAN. (SEE COMMENT #4 AND ADJUST RISER
 TO REFLECT THE FLOOR PLAN, AND PIPE PER
 CODE. SECTIONS 106.1.1 & 909.1.
 ****RESPONSE NOTED, BUT SHOW ALL PIPE
 SIZES.
 ******RESPONSE NOTED, BUT THE 1-1/4" SANT. TO THE
 LAUNDRY SINKS DOES NOT MEET CODE. TABLE 709.1. THE LAVS
 ARE NOT VENTED AS SHOWN AND THE TRAPS ARE UNDERGROUND
 AS PIPED. SECTION 901.2.1. SHT S-3 SHOWS CLEANOUTS
 UPSTREAM OF THE W/C'S ON THE FLOOR PLAN BUT THE SANT.
 RISER DOES NOT REFLECT THIS. PLEASE CLARIFY.
  
 7. SHT P-1 TYPICAL COLD RISER DOES NOT
 REFLECT THE FLOOR PLANS. SUBMIT A WATER
 RISER DIAGRAM FOR EACH BUILDING THAT
 REFLECT THE FLOOR PLAN OF THAT BUILDING.
 SHOW ALL PIPE SIZES, VALVES, INDICATE
 BAY NUMBER, INDICATE PIPING MATERIAL.
 INDICATE IF WATER IS UNDERGROUND OR
 ABOVE GROUND. - AN RPZV BACKFLOW IS
 REQUIRED FOR EACH BUILDING. SECTIONS
 106.1.1, 606.1, 606.2, 608.13.2.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE FIXTURES ARE LOCATED EAST TO WEST IN
 THE TOILET ROOM AND THE FIXTURE LAYOUT
 ON THE RISER IS FROM SOUTH TO NORTH.
 WATER SERVICE IS NOT AS SHOWN ON THE C-1
 SHEET. SEPARATE BACKFLOW REQUIRED FOR
 EACH BUILDING. SHOW ALL PIPE SIZES.
 INDICATE PIPING MATERIAL.
 ******RESPONSE NOTED, BUT NO MENTION OF THE MATERIAL
 FOR THE WATER PIPING WAS INDICATED. ALL BAYS ALL
 BUILDINGS SHOW A VALVE ABOVE THE FLOOR DOWNSTREAM OF
 ALL W/C'S. PLEASE INDICATE WHAT THAT VALVE IS FOR.
 SECTION 104.2.1. - BLDGS 2 & 3 WATER RISER DIAGRAMS DO
 NOT REFLECT THE FLOOR PLAN FIXTURE LAYOUT. INDICATE
 WHATE THE VALVE DOWNSTREAM OF ALL WATER CLOSETS IS FOR.
 SECTION 104.2.1.
  
 8. OK
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
  
 **************NEW COMMENT**************
  
 1C. INFORMATIONAL - SEPARATE IRRIGATION PLANS AND
 PERMIT ARE REQUIRED. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS